Goodrive20-EU series VFD
Function parameters
67
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P06.17
Lower limit of
AO1 output
The above function codes define the relative
relation between the output value and analog
output. When the output value exceeds the
range of set maximum or minimum output, it will
count according to the low-limit or upper-limit
output.
When the analog output is current output, 1mA
equals to 0.5V.
In different cases, the corresponding analog
output of 100% of the output value is different.
Refer to each application for detailed
information.
10V (20mA)
0.0%
100.0%
AO
Setting range of P06.17: -100.0%
– P06.19
Setting range of P06.18: 0.00V
– 10.00V
Setting range of P06.19: P06.17
– 100.0%
Setting range of P06.20: 0.00V
– 10.00V
Setting range of P06.21: 0.000s
– 10.000s
Setting range of P06.22:- 100.0%
– P06.24
Setting range of P06.23: 0.00V
– 10.00V
Setting range of P06.24: P06.22
– 100.0%
Setting range of P06.25: 0.00V
– 10.00V
Setting range of P06.26: 0.000s
– 10.000s
0.0%
○
P06.18
Corresponding
AO1 output to
the lower limit
0.00V
○
P06.19
Upper limit of
AO1 output
100.0%
○
P06.20
Corresponding
AO1 output of
the upper limit
10.00V
○
P06.21
AO1 output
filter time
0.000s
○
P06.22
Lower limit of
AO2 output
0.0%
○
P06.23
Corresponding
AO2 output to
the lower limit
0.00V
○
P06.24
Upper limit of
AO2 output
100.0%
○
P06.25
Corresponding
AO2 output to
the upper limit
10.00V
○
P06.26
AO2 output
filter time
0.000s
○
P07 Group Human-Machine Interface
P07.00 User password
0
– 65535
The password protection will be valid when
setting any non-zero number.
00000: Clear the previous user's password, and
make the password protection invalid.
After the user's password becomes valid, if the
password is incorrect, users cannot enter the
parameter menu. Only correct password can
make the user check or modify the parameters.
0
○