Goodrive20-EU series VFD
Function parameters
63
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
AI2
Corresponding
setting
100%
-100%
-10V
Al3
AI1/AI2
20mA
AI
10V
Input filter time: this parameter is used to adjust
the sensitivity of the analog input. Increasing the
value properly can enhance the anti-interference
of the analog, but weaken the sensitivity of the
analog input
Note:
AI1 supports 0
– 10V input and AI2
supports 0
– 10V or 0 – 20mA input, when AI2
selects 0
– 20mA input, the corresponding
voltage of 20mA is 10V. AI3 can support the
output of -10V
– +10V.
Setting range of P05.32: 0.00V
Setting range of P05.33: -100.0%
– 100.0%
Setting range of P05.34: P05.32
– 10.00V
Setting range of P05.35: -100.0%
– 100.0%
Setting range of P05.36: 0.000s
– 10.000s
Setting range of P05.37: 0.00V
Setting range of P05.38: -100.0%
– 100.0%
Setting range of P05.39: P05.37
– 10.00V
Setting range of P05.40: -100.0%
– 100.0%
Setting range of P05.41: 0.000s
– 10.000s
Setting range of P05.42: -10.00V
Setting range of P05.43: -100.0%
– 100.0%
Setting range of P05.44: P05.42
Setting range of P05.45: -100.0%
– 100.0%
Setting range of P05.46: P05.44
– 10.00V
Setting range of P05.48: 0.000s
– 10.000s
P05.39
Upper limit of
AI2
10.00V
○
P05.40
Corresponding
setting of
the upper limit
of AI2
100.0%
○
P05.41
AI2 input filter
time
0.100s
○
P05.42
Lower limit of
AI3
-10.00
V
○
P05.43
Corresponding
setting of the
lower limit of
AI3
-100.0
%
○
P05.44
Middle value of
AI3
0.00V
○
P05.45
Corresponding
middle setting
of AI3
0.0%
○
P05.46
Upper limit of
AI3
10.00V
○
P05.47
Corresponding
setting of
the upper limit
of AI3
100.0%
○
P05.48
AI3 input filter
time
0.100s
○
P05.50
Lower limit
frequency of
HDI
0.000kHz
0.000
kHz
○
Содержание GD20-004G-2-EU
Страница 1: ......