Goodrive100-PV Series Solar Pumping VFD
Function parameters
42
Function
code
Name
Detailed illustration of parameters
Default Modify
sudden power
loss
P11.02
Frequency
decrease ratio at
sudden power loss
Setting range: 0.00Hz–P00.03/s
After the power loss of the grid, the bus
voltage drops to the sudden frequency
decrease point, the VFD begin to
decrease the running frequency at
P11.02, to make the VFD generate
power again. The returning power can
maintain the bus voltage to ensure a
rated running of the VFD until the
recovery of power.
Voltage
degree
220V
400V
Frequency
decrease
point
260V
460V
0.00Hz/s
○
P15 Group Special functions for PV inverters
P15.00
PV inverter
selection
0: Invalid
1: Enable
0 means the function is invalid and the
group of parameters cannot be used
1 means the function is enabled, and
P15 parameters can be adjusted
1
◎
P15.01
Vmpp voltage
reference
0: Voltage reference
1: Max. power tracking
0 means to apply voltage reference
mode. The reference is a fixed value
and given by P15.02.
1 means to apply the reference voltage
1
◎