Goodrive100-PV Series Solar Pumping VFD
Function parameters
47
Function
code
Name
Detailed illustration of parameters
Default Modify
timing will clear automatically.
P15.13
Empty-water level
threshold
0.0–100.0%
This code is valid when P15.11 water
level control is based on analog input.
If the detected water level control
analog signal is greater than the water
level threshold P15.13 and keeps in the
state after the delay time P15.16, the
system reports A- tL and sleeps. If the
delay time is not reached (that means
non-continuous), the delay time is
automatically
cleared.
When
the
detected water level control analog
signal is less than the water level
threshold, the delay counts.
During the empty-water alarm, if the
detected water level control analog
signal is less than the water level
threshold P15.13 and delay counts, the
empty-water alarm is cleared after the
delay time set by P15.17 in this
continuous state. In the non-continuous
state, the delay time is automatically
cleared.
75.0%
○
P15.14
Full water delay
0–10000s
Time setting of full water delay (This
function code is still valid when the
digital indicates the full-water signal.)
5s
○