Detailed Function Description
54
20
Disable torque
control
Torque control is disabled. Inverter will work in speed
control mode.
21
UP/DOWN
invalid
temporarily
UP/DOWN setting is invalid and will not be cleared. When
this terminal is disabled, UP/DOWN setting before will be
valid again.
22~25 Reserved
Reserved
Multi-step speed reference terminal status and according step value table:
Terminal
Step
Multi-step
speed
reference1
Multi-step
speed
reference2
Multi-step
speed
reference3
0 OFF OFF OFF
1 ON
OFF
OFF
2 OFF ON OFF
3 ON ON
OFF
4 OFF
OFF ON
5 ON
OFF
ON
6 OFF ON ON
7 ON ON ON
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.04
ON/OFF filter times
1~10
1~10
5
This parameter is used to set filter strength of terminals (S1~S4). When interference is
heavy, user should increase this value to prevent malfunction.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.05
FWD/REV
control
mode
0: 2-wire control mode 1
1: 2-wire control mode 2
2: 3-wire control mode 1
3: 3-wire control mode 2
0~3 0
This parameter defines four different control modes that control the inverter operation
through external terminals.
0: 2-wire control mode 1: Integrate START/STOP command with run direction.
K1 K2
Run
command
Содержание CHE100-004G-2
Страница 7: ......
Страница 11: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverters 15kw and below...
Страница 13: ...Introduction 6 Figure1 5 Dimension 0 75 15kW Figure 1 6 Dimension 18 5 110kW Figure 1 7 Dimension 132 315kW...
Страница 20: ...Installation 13 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Страница 22: ...Wiring 15 4 1 Connection of Peripheral Devices Figure 4 1 Connection of peripheral devices...