Goodrive600 series high-performance multifunction VFD
Function parameter list
-247-
Function
code
Name
Description
Default Modify
2: Communication
P00.02
Communication mode of
running commands
0: Modbus
1: CANopen
2: Ethernet
3: EtherCAT/PROFINET
4: PLC
5: Wireless communication
6: PROFIBUS-DP/DeviceNet
Note: The options 2, 3, 4, 5, and 6 are add-on
functions and are available only when
corresponding expansion cards are
configured.
0
○
P00.03
Max. output frequency
Used to set the max. output frequency of the
inverter unit. Pay attention to the function code
because it is the foundation of the frequency
setting and the speed of acceleration (ACC) and
deceleration (DEC).
Setting range: Max (P00.04,10.00)
–630.00Hz
50.00Hz
◎
P00.04
Upper limit of running
frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the inverter
unit, which is lower than or equal to the max.
output frequency.
When the set frequency is higher than the upper
limit of the running frequency, the upper limit of
the running frequency is used for running.
Setting range: P00.05
–P00.03 (Max. output
frequency)
50.00Hz
◎
P00.05
Lower limit of running
frequency
The lower limit of the running frequency is the
lower limit of the output frequency of the inverter
unit.
When the set frequency is lower than the lower
limit of the running frequency, the lower limit of
the running frequency is used for running.
Note: Max. output frequency ≥ Upper limit of
frequency ≥ Lower limit of frequency
Setting range: 0.00Hz
–P00.04 (Upper limit of
running frequency)
0.00Hz
◎
P00.06
Setting channel of A
frequency command
0: Keypad
1: AI1
2: AI2
3: AI3
4: Reserved
5: Simple PLC program
6: Multi-step speed running
7: PID control
8: Modbus communication
9: CANopen communication
10: Ethernet communication
0
○
P00.07
Setting channel of B
frequency command
14
○