
page 4
oblica
| tipi installation and User ManUal
MINIMUM CLEARANCE – INTERNAL
2.1 clearance from non-combustible surfaces
(eg masonry)
100mm minimum clearance is required from fully
non-combustible surfaces.
100
100
Non Combustible
Non Combus
tibl
e
Glass (frameless or aluminium frame)
Glas
s (fr
amel
es
s or aluminium fr
ame)
600mm
600mm
Combustible
Combus
tibl
e
750mm
700mm
Combustible
Combus
tibl
e
700mm
700mm
2.2 clearance from glass
600mm minimum clearance is required from normal
non-combustible glass.
2.3 clearance from combustible surfaces
(eg timber joist & concrete)
clearances may be reduced with the application of
heat shielding to walls in accordance to the
australian Building code.
For information on heat shielding please contact our
office on 03 9416 0400 or email [email protected].
important:
Frames must also be considered. Timber window
frames must be treated as combustible surfaces
(see 2.3). aluminium frames can be treated as
non-combustible surfaces (see 2.2).
2. pre-installation
(continued)
100
100
Non Combustible
Non Combus
tibl
e
Glass (frameless or aluminium frame)
Glas
s (fr
amel
es
s or aluminium fr
ame)
600mm
600mm
Combustible
Combus
tibl
e
750mm
700mm
Combustible
Combus
tibl
e
700mm
700mm
100
100
Non Combustible
Non Combus
tibl
e
Glass (frameless or aluminium frame)
Glas
s (fr
amel
es
s or aluminium fr
ame)
600mm
600mm
Combustible
Combus
tibl
e
750mm
700mm
Combustible
Combus
tibl
e
700mm
700mm
100
100
Non Combustible
Non Combus
tibl
e
Glass (frameless or aluminium frame)
Glas
s (fr
amel
es
s or aluminium fr
ame)
600mm
600mm
Combustible
Combus
tibl
e
750mm
700mm
Combustible
Combus
tibl
e
700mm
700mm
configuration 1 – Parallel installation
configuration 2 – corner installation