INSTALLATION AND ASSEMBLY

22

iV-Office ventilation device | Installation instructions

4.4  Installing the wall sleeve

Measuring tape, angle grinder, spirit level, non-pressing 2K polyurethane foam, cutter, 

mounting wedge set and styrofoam discs

Requirements:

• 

The wall opening Ø 270 mm is finished.

•  The cables to the wall opening of the ventilation 

device has been laid.

 

Determine the exact wall thickness X: 

D = Exterior rendering, incl. other superstructures 

       if applicable. 

C = Insulation, if applicable incl. air gap 

B = Masonry, incl. relining if applicable 

A = Interior plaster

 

X = 

A+B+C+D

 

Cut the wall sleeve to the 

determined dimension 

X

.

Be careful

 

not 

to cut away the cut-out for 

the fan connecting cable.

 

Remove the styrofoam discs from the wall sleeve.

 

Insert the wall sleeve into the wall opening so it is 

flush with the interior wall.

 

Note the thickness of the plaster.

The recess for the connecting cables is 

located on the interior wall side and near 

the cables laid to the wall opening.

 

Guide all connecting cables through the cut-out in 

the wall sleeve.

X = ?

D

A

B

C

X

!

!

Содержание iV-Office

Страница 1: ...Ventilation device with heat recovery www inventer eu Installation instructions iV Office...

Страница 2: ...bed com ponents Nevertheless deviations may still occur therefore no guarantee of compliance can be provided This documentation describes the functionality of the standard scope For reasons of clarity...

Страница 3: ...18 4 2 Create wall opening 19 4 3 Laying the cables to the wall opening of the ventilation device 20 4 4 Installing the wall sleeve 22 4 5 Installing the ventilation device s external termination 24...

Страница 4: ...ates the severity of the potential hazard unless the preventive measures are taken DANGER means Imminent danger of serious injury or death WARNING means Possible danger of serious injury or death CAUT...

Страница 5: ...s liability insurance association Use the device system exclusively for the applications that are described in this documentation and only in conjunction with components that are recommended authorise...

Страница 6: ...e of the components especially the thermal accumulator NOTICE In order to avoid algae growth around the external terminations the instructions for installation must be followed exactly apply all seali...

Страница 7: ...he ventilation device Qualified personnel The equipment system may only be set up operated and cleaned in conjunction with this documentation and the documentation for the controllers Installation ele...

Страница 8: ...ensure more efficient flow through the thermal accumulator The sound absorbing Inventin lining and the unique geometry of the Xenion EFP reversible fan effectively reduce the passage of sound The stan...

Страница 9: ...ion hood base plate 2 Flex Office ring insert pre installed 3 Weather protection hood cover 4 R D250 wall sleeve 5 Recess for controller connecting cable 6 Sound insulation lining Inventin 7 Thermal a...

Страница 10: ...extract air After 70 seconds the reversing fan changes the direction of rotation each time After the direction of rotation has changed the heat accumulator releases the stored heat energy to the incom...

Страница 11: ...rated wind pressure stabiliser in the Xenion EFP reversible fan the air flow in the system is kept almost constant even in the event of weather related pressure fluctuations Thus the sensitivity of th...

Страница 12: ...zone control No No Operating concept Switch Touch Operating modes Heat recovery Unidirectional ventilation OFF standard version only Heat recovery Unidirectional ventilation OFF standard version only...

Страница 13: ...ing concept Touch Weekly timer Operating modes Heat recovery Through ventilation OFF Functions Pause function 1 8h per zone Dehumidification with variable air volume flow Fan speed 4 Output levels fre...

Страница 14: ...spray is possible Observe the specifications of VDE 0100 when choosing the installation location Minimum distances of the wall opening for the ventilation device Minimum distances to components buildi...

Страница 15: ...right 2 Contour of weather protection hood3 3 Reveal 4 Door window frame 5 Bottom edge of lintel4 1 Minimum distance to adjacent components on the interior wall 3 Recommendation Attach the hood at lin...

Страница 16: ...iant Figure 3 Sectional drawing of the iV Office ventilation device A Interior plaster interior structure B Masonry C Insulation D Render 1 Inner cover base plate 2 Flair XL adapter 3 Inner cover pane...

Страница 17: ...se plate 2 Flex Office insert pre assembled 3 Exterior wall fixing hole 4 Protective grid 5 Weather protection hood cover 6 Drip rail Flair XL inner cover Figure 5 Dimensional drawing of the Flair XL...

Страница 18: ...nent 1 External termination 1 a Flex Office WSH cover 1 b Flex Office WSH base plate 1 c Exterior wall fixing elements 1 d Sealing tape 2 R D250 wall sleeve 2 a Styrofoam discs 2 b Mounting wedges set...

Страница 19: ...he minimum distances and the installation position of the ventilation device Consult your planner before installation if you are at all uncertain Create the wall opening through core drilling Power dr...

Страница 20: ...reversible fan NOTICE Cable to the wall opening of the ventilation device not laid No connection of the reversible fan possible Routing of the cables to the wall opening for the ventilation device mus...

Страница 21: ...rminal blocks Ventilation devices Ventilation devices Operated in pairs Operated in pairs Principle sketches for cable laying The corresponding connection diagrams and assembly steps for installing th...

Страница 22: ...other superstructures if applicable C Insulation if applicable incl air gap B Masonry incl relining if applicable A Interior plaster X A B C D Cut the wall sleeve to the determined dimension X Be care...

Страница 23: ...ing the free space between the wall sleeve and masonry insert styrofoam discs Insert the styrofoam discs into the wall sleeve from the inside and outside NOTICE Interruption of the thermal insulation...

Страница 24: ...around the weather protection hood consult your planner regarding this Installing the Flex Office weather protection hood Spirit level pen power drill with 8mm drill bit cordless screwdriver rawl plu...

Страница 25: ...he base plate to exterior walls with insulation or when using the Simplex wall installation system use wallplugs for insulation for fixing purposes These are not included in the scope of supply they a...

Страница 26: ...t sound Inventin is a sensitive material To safeguard its sound insulating function handle the lining with care Cutter Requirements The external termination is fitted Remove the styrofoam disc from th...

Страница 27: ...ilation device Installation instructions Shorten the sound insulation lining on the inner wall side with a cutter so it is flush with the wall sleeve Do not damage the connecting cable on the interior...

Страница 28: ...tted The sound insulation lining is inserted Insert the thermal accumulator from the interior into the lined wall sleeve The handle points towards the interior The connecting cables protrude into the...

Страница 29: ...the cable entry Before installation check whether any adjustment of the inner cover adapter needs to be made If necessary change the position of the cable entry so that it matches the conditions of t...

Страница 30: ...rill the four holes with 6 mm min 40 mm deep Insert the rawl plugs Route the fan BUS from behind through the cable entry of the prepared base plate NOTICE If the base plate of the inner cover is twist...

Страница 31: ...ules onto the cables cable cross section 0 75 mm Loosen the plug connections on the reversible fans of the two ventilation devices Align the plug connectors on the ventilation devices so that the clam...

Страница 32: ...mode Brown cable DIR2 V in the left pole Green cable VOUT IV in the middle pole White cable DIR1 III in the right pole Reconnect the connected plug in connector to the plug in connector on the reversi...

Страница 33: ...VOUT IV Operating voltage Green CCW Black DIR2 V Signal direction 2 Brown DIR1 III Signal direction 1 White The reversible fan is connected to the controller 4 9 Check function and complete fan instal...

Страница 34: ...e plate The tab on the filter ring faces the inside and is located in the cut out provided in the base plate Place the panel on the four spacers The position arrows on the back of the inner cover pane...

Страница 35: ...e level distance 2 m dB A 14 41 Standard sound level difference dB 43 52 Thermal efficiency of heat recovery w 0 88 Input voltage V DC 6 16 Power consumption W 1 5 Specific fan power input W m h 0 14...

Страница 36: ...e following information from the product data sheet Energy efficiency class SEC class Sound power level Lwa Maximum air flow supply air 2016 1254 2014 49 dB A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI A...

Страница 37: ...temperature change t 88 h Maximum air flow rate m h 90 i Electrical input power incl control W 9 j Sound power level Lwa dB A 49 k Reference air flow m h 63 l Reference pressure difference Pa 0 m SEL...

Страница 38: ...imum air flow rate m h 90 i Electrical input power incl control W 9 j Sound power level Lwa dB A 49 k Reference air flow m h 63 l Reference pressure difference Pa 0 m SEL W m h 0 14 n Control factor 1...

Страница 39: ...06 1508 0182 1508 01861 Flex Office weather protection hood Nord RAL 7011 1508 0184 Flex Office weather protection hood anthracite RAL 7016 1508 0183 1508 01871 Flex Office weather protection hood cus...

Страница 40: ...mode The rotational speed of the fan is too low Increase the output level Noises Foreign body in the fan Remove foreign body from the fan Clean the ventilation system Thermal accumulator is not correc...

Страница 41: ...about the warranty is available at www inventer eu guarantee 9 Service Claims Check the delivery for completeness and transport damage upon receipt using the delivery note Report missing items immedia...

Страница 42: ...Item number 5001 0043 Version 2 0 06 2022 Subject to modifications We accept no liability for printing errors inVENTer GmbH Ortsstra e 4a D 07751 L bersch tz Germany www inventer eu...

Отзывы: