Under the operation parameters interface, press the ENTER key to enter the battery type setting,
press the DOWN key to select the battery type (lead-acid battery, colloidal battery, liquid
battery, lithium battery), and then press the ENTER key to confirm, after hear the continuous tone
and press the MENU key to return to the previous menu.
Under the operation parameter, press the DOWN key to select the charge voltage setting and
press the ENTER key to enter the charge voltage setting. Press the UP key to move the cursor,
press the DOWN key to enter the value, press the ENTER key to confirm the save, and press the
MENU key. Press MENU Key to return to the previous menu.
Under the operation parameters interface, press the DOWN key to select the rated voltage setting
and press the ENTER key to enter the rated voltage setting. Press the DOWN key to select the
rated voltage level (auto identification, 12V, 24V, 36V, 48V). Press the ENTER key to confirm and
after hear the continuous tone and press the MENU key to return to the previous menu.
Lithium battery series only have float (constant voltage) charging mode, and the equalizing
chargemode is use by lead-acid battery series.
Under the operation parameters interface, press the DOWN key to select the charge current
setting and press the ENTER key to enter the charge current setting. Press the UP key to move
the cursor, press the DOWN key to enter the value, press the ENTER key to confirm the save,
and after hear the continuous tone and press the MENU key to return to the previous menu.
The set value of charge current can not be greater than the current maximum value
The factory default is to automatically recognize the rated voltage grade. The automatic
identification of rated voltage grade only identify lead-acid battery series. Lithium battery is not
included in the automatic identification range. When the voltage grade is automatically recognized
the setting of charge voltage and the discharge lower limit voltage are not allowed. It must be
manually set the voltage grade first, and then to set the charge voltage and discharge lower limit
voltage.