SYSTEM SETUP 

Depending on the requirement of the application, Optiport E-2 can be 
used in the following different ways: 
 

 

One Optiport E-2 with one drive 

 
 
 
 
 
 
 
 

 

One Optiport E-2 with multiple drives 

 
 
 
 
 
 
 
 
 
 

Note: The splitter is available from Invertek Drives Ltd on request. 
 

REAL TIME OPERATION 

 
Once the communication has been setup between the drive and 
Optiport E-2, the user can control the Optidrive E-2 by using the 
control buttons on the front panel of the Optiport. 

 
To monitor or change a parameter value  

 

 

Press and hold the 

NAVIGATE

 key for more than 1s when the 

drive is displaying “

StoP

”.  The display changes to 

P-01

indicating parameter 01 in parameter group 1.   

 

Press and release the 

NAVIGATE

 key to display the value of this 

parameter.   

 

Change to the required value using the 

UP

 and 

DOWN

 keys. 

 

Press and release the 

NAVIGATE

 key once more to store the 

change.  

 

Press and hold the 

NAVIGATE

 key for more than 1s to return to 

real-time mode. The display shows “

StoP

”  if the drive is stopped 

or the real-time information (e.g. speed, current or power) if the 
drive is running. 

 

 

USER INTERFACE 

 

 
 
 
 
 
 
 
 
 
 
 
 
NAVIGATE:

  

Used to display real-time information, to access and exit parameter 
edit mode and to store parameter changes 
 

UP:

 

Used to increase speed in real-time mode or to increase parameter 
values in parameter edit mode 
 

DOWN:

 

Used to decrease speed in real-time mode or to decrease parameter 
values in parameter edit mode 

 
RESET / STOP:

  

When drive is in trip mode, this button is used to reset a tripped drive. 
In normal application, when in Keypad mode, this button is used to 
stop a running drive. 

 

 

 
START:

 

When in keypad mode, the button is used to start a stopped drive or 
to reverse the direction of rotation if bi-directional keypad mode is 
enabled (See drive user guide for more information).

 

 

NOTES 

 

 

EASY STARTUP 

 

To setup the communication address 

By default, the Optiport E-2 will try to communicate with the drive that 
has address 1 in the network after powering up for the first time. 
 The Optiport E-2 will display “

SCAN..

” after power up, which indicates 

that the Optiport E-2 is searching the drive with the correct drive 
address in the network. Once the drive has been found, the message 

Load..

” will be displayed on the Optiport display window, which 

indicates that the Optiport is reading the configuration information from 
the drive. Usually it will take 1~2 seconds for the Optiport to read this 
information. After the data has been loaded, Optiport E-2 will display 
the drive real time status. 
If the Optiport E-2 doesn’t find the drive in the network, i.e. there is only 
one drive in the network and its address is not equal to 1, the Optiport 
E-2 communication address will be displayed on the monitor window as 

Adr-01

”. The user can then adjust the address from 1 to 63 by using 

the 

UP

 or 

DOWN

 buttons on the Optiport E-2.  

Once the address has been changed to a value to match that of the 
drive, the 

STOP

 button must be pressed to enable the Optiport E-2 to 

search for the drive again. 
Once the communication between Optiport and drive has been set up,  
user can change the Optiport address to set up communication with 
another drive in the same drive network at anytime.   
Pressing the 

STOP

 and 

DOWN

 buttons together results in the message 

“Adr-XX”, where “XX” represents the present address. Using the 

UP

 or 

DOWN

 button to select the desired drive address. After selecting the 

new address, pressing 

STOP

 and 

DOWN

 button together again will 

result in Optiport E-2 establishing communications with the drive that 
has this address. 
 
 
 
 
 

Locking access to the parameters 

  To prevent unauthorised access to the parameters via the Optiport, 

set P-38 = 1. Once this parameter has been set, access to 
parameters via the Optiport E-2 will be prevented. 

  The Operational information (speed, current, power etc) can be still 

accessed as normal and the drive can still be controlled from the 
keypad. 

  To unlock parameter access, change P2-38 back to 0 via the drive 

keypad directly. 

 

Presetting target speed in keypad mode 

Set P-12 = 1 or 2 to enable the keypad control, ensuring that P-31 = 1 
or 3 to enable the drive to start from the preset speed.  
Whilst the drive is stopped, press the 

STOP

 key. The value of the 

digital potentiometer will be displayed, indicating target speed. Use the 

UP

 and 

DOWN

 keys to select the required target speed. 

 Press the 

STOP

 key to return to the real time display showing “

StoP

”, 

or the 

START

 key to start the drive ramping up to the target speed. 

 
To vary the speed in real time in keypad control mode 

Press the 

START

 key. The drive will ramp up to the preset speed set in 

the digital potentiometer (assuming P-31 = 1). 
Press 

UP

 to increase speed.  

The drive will run forward, increasing speed until the 

UP

 button is 

released. The maximum speed is the speed set in P-01. 
Press 

DOWN

 to decrease speed.  

The drive will decrease speed until the 

STOP

 button is released. The 

minimum speed is the speed set in P-02. 
Pressing the 

STOP

 key to stop the drive (suppose P-31 = 1).  

The drive will decelerate to stop at the selected deceleration ramp. 
The display will finally show “

StoP

” at which point the drive is disabled. 

Pressing the 

START

 key once more results in the drive running back 

up to the speed at which it was previously running (digital potentiometer 
value). (assuming P-31 = 1) 
 
 
 
 
 
 

To reverse direction of rotation with P1-12 = 2 

Press the 

START

 key. The drive ramps up to the preset speed as set in 

the digital potentiometer (assuming P-31 = 1). 
Press 

UP

 or 

DOWN

 to increase or decrease the speed.  

Press the 

START

 key again. The motor will reverse its direction of 

rotation. 
Press the 

STOP

 key to decelerate the motor to standstill. 

Whenever the drive is started, it will start with a positive speed unless 
the direction is negated by the digital inputs on the user terminals 

 

DRIVE TRIP CODE 

 

Fault Code 

What has happened 

P-deF Default 

parameters 

loaded 

O-I 

 

Over current on drive output. 

Excess load on the motor. 

Over temperature on the heatsink 

I.t-trP 

Drive has tripped on overload after delivering 

>100%  of value in P-08 for a period of time. 

OI-b 

Brake channel over current 

OL-br 

Brake resistor overload 

PS-Trp 

Internal power stage fault 

O-Uolt 

Over voltage on DC bus 

U-Uolt 

Under voltage on DC bus 

O-t Heatsink 

over 

temperature 

U-t Under 

temperature 

th-Flt 

Faulty thermistor on heatsink. 

E-triP 

External trip (on dig. Input 2 or 3) 

SC-trP 

Comms loss trip 

P-LOSS 

Input phase loss trip 

SPIN-F 

Spin start failed 

data-F 

Internal memory fault. Parameters not saved, 

defaults reloaded. 

4-20F 

Current analog input out of range 

 

For detail trouble shooting information, please refer to the 

corresponding drive user guide. 

 
 

UNDERSTANDING THE DISPLAY MESSAGES 

 
Optiport E-2 uses various display messages to indicate different 
working status. See the following table for more information. 

 

Message Explanation 

SCAN.. 

The Optiport E-2 is searching for the drive in the 
network. 

LOAD.. 

The Optiport E-2 has found the drive in the network 
and is loading the initialisation information from the 
drive.  

Err-SC 

The Optiport E-2 has lost the communication link to 
the drive. 

Adr-XX 

Indicates the Optiport E-2 address, where XX= 1…63 

 
 

 

TROUBLE SHOOTING 

 

Symptom Explanation 

‘Adr-XX’ 
displayed after 
‘SCAN..’ 
message 

Optiport E-2 failed to find the drive with the 
specified address in the network. 
Check that the RJ45 data cable connection is 
correct. Check that the drive with address XX 
is available in the whole network. 
If XX > 1 and only one Optiport E-2 is 
connected, then check the Optiport E-2 device 
number, make sure the number is 1. 

Display ‘Err-SC’ 

Check the electrical connection, and make 
sure the cable is connected correctly between 
the Opitport E-2 and drive. Press ‘

STOP

’ 

button to enable the Optiport E-2 to search the 
drive again. 

 
 
 
 
 
 

 

NAVIGATE 

START 

STOP DOWN 

UP 

 

8.8.8.8.8.8. 

 

NOTE 

For detailed parameter listing and functional setup, please refer 

to the corresponding Optidrive E-2

 

user guide 

 
 
 
 
 
 
 

 

Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been 

made to provide accurate and up to date information, the information contained in this brochure 

should be used for guidance purposes only and does not form the part of any contract. 

NOTE 

The hardware enable on the drive must be present when using 

keypad control mode. 

 