STANDARDS CONFORMITY
An Optidrive fitted with this Option complies with the following standards:
CE-marked for Low Voltage Directive.
IEC 664-1 Insulation Coordination within Low Voltage Systems.
UL 840 Insulation Coordination for electrical equipment.
EN50081-2 EMC Generic Emissions Standard, Industrial Level.
EN50082-2 EMC Generic Immunity Standard, Industrial Level.
Enclosure ingress protection, EN60529 IP00, NEMA 250.
Flammability rating according to UL 94.
WARRANTY
All Invertek Drives Ltd (IDL) products carry a 2-year warranty, valid from the
date of manufacture.
Complete Warranty Terms and Conditions are available upon request from your
IDL Authorized Distributor.
DECLARATION
All rights reserved. No part of this User Guide may be reproduced or
transmitted in any form or by any means, electrical or mechanical including
photocopying, recording or by any information storage or retrieval system
without permission in writing from the publisher.
Copyright Invertek Drives Ltd ©2011
The manufacturer accepts no liability for any consequences resulting from
inappropriate, negligent or incorrect installation.
The contents of this User Guide are believed to be correct at the time of
printing. In the interests of a commitment to a policy of continuous
improvement, the manufacturer reserves the right to change the specification
of the product or its performance or the contents of the User Guide without
notice.
SAFETY
This option is specifically designed to be used with the Optidrive P2 and
HVAC variable speed drive product ranges and is intended for professional
incorporation into complete equipment or systems. If installed incorrectly it
may present a safety hazard. The Optidrive P2 / HVAC use high voltages and
currents, carry a high level of stored electrical energy, and are used to control
mechanical plant that may cause injury. Close attention is required to system
design and electrical installation to avoid hazards in either normal operation or
in the event of equipment malfunction.
System design, installation, commissioning and maintenance must be carried
out only by personnel who have the necessary training and experience. They
must read carefully this safety information and the instructions in this Guide
and follow all information regarding transport, storage, installation and use of
the Option module, including the specified environmental limitations.
Please read the SAFETY NOTICE carefully, and all Warning and Caution
boxes elsewhere.
CAUTION
Store the Optidrive Option Module in its box until required. It should be stored
in a clean and dry environment. Temperature range
–40
o
C to +60
o
C.
Install the Option Module into the Optidrive by inserting the module into the
option module port of the Optidrive as shown in the mechanical installation
section. Do not use undue force in inserting the option module into the port.
WARNING
Optidrives and the Option Modules should be installed only by qualified
electrical persons and in accordance with local and national regulations and
codes of practice.
Electric shock hazard!
Disconnect and
ISOLATE
the Optidrive before
attempting any work on it. High voltages are present at the terminals and within
the drive for up to 10 minutes after disconnection of the electrical supply.
Where the electrical supply to the drive is through a plug and socket
connector, do not disconnect until 10 minutes have elapsed after turning off the
supply.
OPTIDRIVE P2 / HVAC EXTENDED
I/O MODULE
User Guide
SAFETY NOTICES
WARNING
is given where there is a hazard that could lead to injury or death
of personnel.
CAUTION
is given where there is a hazard that could lead to damage to
equipment.
It is the responsibility of the installer to ensure that the equipment or system
into which the product is incorporated complies with the EMC legislation of the
country of use. Within the European Union, equipment into which this product
is incorporated must comply with 89/336/EEC, Electromagnetic Compatibility.
Invertek Drives Ltd
Offa’s Dyke Business Park
Welshpool
Powys
SY21 8JF
UK
Tel: +44 (0) 1938 556868 email:
Fax: +44 (0) 1938 556 869 Web:
www.invertek.co.uk
Part No.
82-OPT-2-EXTIO-IN
Version 1.00 / January 2011
WARNING
Within the European Union, all machinery in which this product is used
must comply with the Directive 89/392/EEC, Safety of Machinery. In
particular, the equipment should comply with EN60204-1.
SPECIFICATIONS
Model Number:
OPT-2-EXTIO-IN
Compatibility:
Optidrive P2 / HVAC (ODP-2 / ODV-2)
Digital Input x 3:
8-30V DC Input
Digital Input Response Time:
< 8ms
Max Relay switching voltage:
250V AC / 30V DC
Max Relay switching current:
6A (250V AC) / 5A (30V DC)
Environnemental :
-
10ºC … +50ºC
Conformity:
IP20, UL94V-0
Terminal Torque:
0.5Nm (4.5 Ib-in)