background image

STANDARDS CONFORMITY  

An Optidrive fitted with this Option complies with the following standards: 
 

  CE-marked for Low Voltage Directive. 

 

  IEC 664-1 Insulation Coordination within Low Voltage Systems. 

 

  UL 840 Insulation Coordination for electrical equipment. 

 

  EN50081-2 EMC Generic Emissions Standard, Industrial Level. 

 

  EN50082-2 EMC Generic Immunity Standard, Industrial Level. 

 

  Enclosure ingress protection, EN60529 IP00, NEMA 250. 

 

  Flammability rating according to UL 94. 

 
 

 

WARRANTY 

All Invertek Drives Ltd (IDL) products carry a 2-year warranty, valid from the 

date of manufacture. 

 

Complete Warranty Terms and Conditions are available upon request from your 

IDL Authorized Distributor. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

DECLARATION 

All  rights  reserved.  No  part  of  this  User  Guide  may  be  reproduced  or 
transmitted  in  any  form  or  by  any  means,  electrical  or  mechanical  including 
photocopying,  recording  or  by  any  information  storage  or  retrieval  system 
without permission in writing from the publisher. 
 

Copyright Invertek Drives Ltd ©2011 

 

The  manufacturer  accepts  no  liability  for  any  consequences  resulting  from 
inappropriate, negligent or incorrect installation. 

 

The  contents  of  this  User  Guide  are  believed  to  be  correct  at  the  time  of 
printing.  In  the  interests  of  a  commitment  to  a  policy  of  continuous 
improvement, the manufacturer reserves the right to change the specification 
of  the  product  or  its  performance  or  the  contents  of  the  User  Guide  without 
notice. 

 

 

SAFETY 

This  option  is  specifically  designed  to  be  used  with  the  Optidrive  P2  and 
HVAC  variable  speed  drive  product  ranges  and  is  intended  for  professional 
incorporation  into  complete  equipment  or  systems.  If  installed  incorrectly  it 
may present a safety hazard. The Optidrive P2 / HVAC use high voltages and 
currents, carry a high level of stored electrical energy, and are used to control 
mechanical plant that may cause injury. Close attention is required to system 
design and electrical installation to avoid hazards in either normal operation or 
in the event of equipment malfunction.  

 

System design, installation, commissioning and maintenance must be carried 
out only by personnel who have the necessary training and experience. They 
must  read  carefully  this  safety  information  and  the  instructions  in  this  Guide 
and follow  all information regarding transport, storage,  installation and use of 
the Option module, including the specified environmental limitations. 
 
Please  read  the  SAFETY  NOTICE  carefully,  and  all  Warning  and  Caution 
boxes elsewhere. 

CAUTION 

  Store the Optidrive Option Module in its box until required. It should be stored 

in a clean and dry environment. Temperature range 

–40

o

C to +60

o

C. 

  Install  the  Option  Module  into  the  Optidrive  by  inserting  the  module  into  the 

option  module  port  of  the  Optidrive  as  shown  in  the  mechanical  installation 
section. Do not use undue force in inserting the option module into the port. 

 

WARNING

  

  Optidrives  and  the  Option  Modules  should  be  installed  only  by  qualified 

electrical  persons  and  in  accordance  with  local  and  national  regulations  and 
codes of practice. 

 

Electric  shock  hazard!

  Disconnect  and 

ISOLATE

  the  Optidrive  before 

attempting any work on it. High voltages are present at the terminals and within 
the drive for up to 10 minutes after disconnection of the electrical supply. 

  Where  the  electrical  supply  to  the  drive  is  through  a  plug  and  socket 

connector, do not disconnect until 10 minutes have elapsed after turning off the 
supply. 

 
 
 
 

OPTIDRIVE P2 / HVAC EXTENDED 

I/O MODULE 

 

User Guide 

 

 

SAFETY NOTICES 

WARNING

 

is given where there is a hazard that could lead to injury or death 

of personnel. 

CAUTION

  is  given  where  there  is  a  hazard  that  could  lead  to  damage  to 

equipment. 
It  is  the  responsibility  of  the  installer  to  ensure  that  the  equipment  or  system 
into which the product is incorporated complies with the EMC legislation of the 
country of use. Within the European Union, equipment into which this product 
is incorporated must comply with 89/336/EEC, Electromagnetic Compatibility. 
 
 
 
 
 
 
 

 

Invertek Drives Ltd 
Offa’s Dyke Business Park 
Welshpool 
Powys 
SY21 8JF 
UK

 

 

Tel:   +44 (0) 1938 556868         email: 

[email protected]

 

Fax:  +44 (0) 1938 556 869        Web:  

www.invertek.co.uk

 

Part No. 

82-OPT-2-EXTIO-IN 

Version 1.00 / January 2011 

WARNING 

Within  the  European  Union,  all  machinery  in  which  this  product  is  used 
must  comply  with  the  Directive  89/392/EEC,  Safety  of  Machinery.  In 
particular, the equipment should comply with EN60204-1. 

SPECIFICATIONS

 

Model Number: 

 

OPT-2-EXTIO-IN 

Compatibility: 

 

Optidrive P2 / HVAC (ODP-2 / ODV-2) 

Digital Input x 3: 

 

8-30V DC Input 

Digital Input Response Time: 

< 8ms 

Max Relay switching voltage: 

250V AC / 30V DC

 

 

Max Relay switching current: 

6A (250V AC) / 5A (30V DC)

 

 

Environnemental :                

-

10ºC … +50ºC  

Conformity:                      

 

IP20,  UL94V-0 

Terminal Torque: 

 

0.5Nm (4.5 Ib-in) 

 

 

 

 

 

 