Version 2.04
| Optidrive ODP-2 Solar Pump User Guide |
45
www.invertekdrives.com
9. Extended Parameters
9.1. Parameter Group 2 - Extended parameters
Par
Parameter Name
Minimum
Maximum
Default
Units
P2-01
Preset Speed 1
P1-02
P1-01
5.0
Hz / Rpm
P2-02
Preset Speed 2
P1-02
P1-01
10.0
Hz / Rpm
P2-03
Preset Speed 3
P1-02
P1-01
25.0
Hz / Rpm
P2-04
Preset Speed 4
P1-02
P1-01
0.0
Hz / Rpm
Preset Speeds / Frequencies selected by digital inputs depending on the setting of P1-13.
If P1-10 = 0, the values are entered as Hz. If P1-10 > 0, the values are entered as Rpm.
Setting a negative value will reverse the direction of motor rotation.
P2-05
Preset Speed 5 / Clean Speed 1
P1-02
P1-01
0.0
Hz / Rpm
Preset speed 5 is automatically reference by the Pump Clean function when this is enabled. When the Pump Clean function is disabled,
Preset speed 5 can be selected as per preset speeds 1 – 4.
P2-06
Preset Speed 6 / Clean Speed 2
P1-02
P1-01
0.0
Hz / Rpm
Preset speed 6 is automatically reference by the Pump Clean function when this is enabled. When the Pump Clean function is disabled
Preset speed 6 can be selected as per as per preset speeds 1 – 4.
P2-07
Preset Speed 7 / Boost Speed 1 / Stir Speed
P1-02
P1-01
0.0
Hz / Rpm
Preset speed 7 is automatically referenced by the Start Boost function, or the Pump Stir Function, when these functions are enabled.
When they are disabled, Preset speed 7 can be selected as per preset speeds 1 – 4.
P2-08
Preset Speed 8 / Boost Speed 2
P1-02
P1-01
0.0
Hz / Rpm
Preset speed 8 is automatically reference by the Stop Boost function when this function is enabled. When disabled, Preset speed 8 can
be selected as per preset speeds 1 – 4.
P2-09
Skip Frequency Centre Point
P1-02
P1-01
0.0
Hz / Rpm
P2-10
Skip Frequency Band Width
0.0
P1-01
0.0
Hz / Rpm
The Skip Frequency function is used to avoid the Optidrive operating at a certain output frequency, for example at a frequency which
causes mechanical resonance in a particular machine. Parameter P2-09 defines the centre point of the skip frequency band, and is
used conjunction with P2-10. The Optidrive output frequency will ramp through the defined band at the rates set in P1-03 and P1-04
respectively, and will not hold any output frequency within the defined band. If the frequency reference applied to the drive is within
the band, the Optidrive output frequency will remain at the upper or lower limit of the band.
P2-11
Analog Output 1 (Terminal 8) Function Select
0
11
8
-
Digital Output Mode. Logic 1 = +24V DC
0 : Drive Enabled (Running).
Logic 1 when the Optidrive is enabled (Running)
1: Drive Healthy.
Logic 1 When no Fault condition exists on the drive
2 : At Target Frequency (Speed).
Logic 1 when the output frequency matches the setpoint frequency
3 : Output Frequency > 0.0.
Logic 1 when the motor runs above zero speed
4 : Output Frequency >= Limit.
Logic 1 when the motor speed exceeds the adjustable limit
5 : Output Current >= Limit.
Logic 1 when the motor current exceeds the adjustable limit
6 : Motor Torque >= Limit.
Logic when the motor torque exceeds the adjustable limit
7 : Analog Input 2 Signal Level >= Limit.
Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit
Note:
When using settings 4 – 7, parameters P2-16 and P2-17 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal falls below the
value programmed in P2-17.
Analog Output Mode
8 : Output Frequency (Motor Speed).
0 to P-01
9 : Output (Motor) Current.
0 to 200% of P1-08
10 : Motor Torque.
0 to 200% of motor rated torque
11 : Output (Motor) Power.
0 to 150% of drive rated power
12 : PID Output.
Output from the internal PID Controller, 0 – 100%
13: DC Bus Level.
0 – 100.0% = 0 – 1000Vdc
9
Extended P
arameters