Optidrive E2 Single Phase Output User Guide V3.10 

27 

www.invertekdrives.com 

 

 

Te

ch

n

ical 

Da

ta

 

9

 

9.

 

Technical Data 

9.1.

 

Environmental 

Operational ambient temperature range  

Open Drives 

:  

-10 … 50°C (frost and condensation free) 

 

 

 

 

 

Enclosed Drives 

-10 ... 40°C (frost and condensation free) 

Storage ambient temperature range 

 

 

:  

-40 … 60°C 

Maximum altitude 

 

 

 

 

:  

2000m. Derate above 1000m : 1% / 100m 

Maximum humidity 

 

 

 

 

95%, non-condensing 

9.2.

 

Rating Tables 

kW 

HP 

Nominal 

Input 

Current 

Fuse or MCB 

(type B) 

Supply Cable Size 

Nominal 

Output 

Current  

Motor Cable Size 

Max 

Motor 

Cable 

Length 

Min Brake 

Res Value 

Non UL 

UL 

mm 

AWG / kcmil 

mm 

AWG / kcmil 

0.5 

12.4 

16 

15 

1.5 

 

1.5 

 

25 

0.75 

16.1 

25 

20 

2.5 

 

10.5 

1.5 

 

50 

47 

kW 

HP 

Nominal 

Input 

Current 

Fuse or MCB 

(type B) 

Supply Cable Size 

Nominal 

Output 

Current  

Motor Cable Size 

Max 

Motor 

Cable 

Length 

Min Brake 

Res Value 

Non UL 

UL 

mm 

AWG / kcmil 

mm 

AWG / kcmil 

0.37 

0.5 

6.8 

10 

10 

1.5 

 

4.3 

1.5 

 

25 

0.75 

12.8 

16 

15 

1.5 

 

1.5 

 

25 

1.1 

1.5 

16.2 

25 

25 

2.5 

 

10.5 

1.5 

 

50 

47 

 

9.3.

 

Additional Information for UL Compliance 

Optidrive E2 is designed to meet the UL requirements. In order to ensure full compliance, the following must be fully observed. 

 

For an up to date list of UL compliant products, please refer to UL listing NMMS.E226333 

 

The drive can be operated within an ambient temperature range as stated in section 9.1 

 

For IP20 units, installation is required in a pollution degree 1 environment 

 

For IP66 (Nema 4X) units, installation in a pollution degree 2 environment is permissible 

 

UL Listed ring terminals / lugs must be used for all bus bar and grounding connections 

 
Input Power Supply Requirements 
Supply Voltage 

200 – 240 RMS Volts for 230 Volt rated units, + /- 10% variation allowed. 240 Volt RMS Maximum 

Imbalance 

Maximum 3% voltage variation between phase – phase voltages allowed 
All Optidrive E2 units have phase imbalance monitoring. A phase imbalance of > 3% will result in the drive tripping.  
For input supplies which have supply imbalance greater than 3% (typically the Indian sub- continent & parts of Asia 
Pacific including China) Invertek Drives recommends the installation of input line reactors. 

Frequency 

50 – 60Hz + / - 5% Variation 

Short Circuit Capacity 

Voltage Rating 

Min kW (HP) 

Max kW (HP) 

Maximum supply short-circuit current 

115V 

0.37 (0.5) 

1.1 (1.5) 

5kA rms (AC) 

230V 

0.37 (0.5) 

4 (5) 

5kA rms (AC) 

All the drives in the above table are suitable for use on a circuit capable of delivering not more than the above 
specified maximum short-circuit Amperes symmetrical with the specified maximum supply voltage. 

Motor Cable 

75°C Copper must be used 

Fusing 

UL Class T Fuses must be used 

Incoming power supply connection must be according to section 4.3 
All Optidrive E2 units are intended for indoor installation within controlled environments which meet the condition limits shown in section 9.1 
Branch circuit protection must be installed according to the relevant national codes. Fuse ratings and types are shown in section 9.2 
Suitable Power and motor cables should be selected according to the data shown in section 9.2 
Power cable connections and tightening torques are shown in section 3.1 
Optidrive E2 provides motor overload protection in accordance with the National Electrical Code (US).  

 

Where a motor thermistor is not fitted, or not utilised, Thermal Overload Memory Retention must be enabled by setting P-50 = 1 

 

Where a motor thermistor is fitted and connected to the drive, connection must be carried out according to the information shown 
in section 7.5 

 

 

Содержание ODE-2-11005-1H012-01

Страница 1: ...ase Output User Guide V3 10 User Guide Single Phase Output AC Variable Speed Drive for PSC Shaded Pole Single Phase Motors 0 37 1 1kW 0 5 1 5HP IP20 Open IP66 Nema 4X Enclosed Units Installation and O...

Страница 2: ...gs out of the box 1 Connect a START STOP switch from Terminal 1 to 2 Close the contact START enable the drive Open the contact STOP the drive 2 Connect a 10k potentiometer on terminal 5 6 7 to vary th...

Страница 3: ...h is set to the REV position set parameter value in P 15 Check page 15 for configuring the FWD REV switch for Local Remote Hand off Auto applications Local Power Isolator with Lock off provision Fuses...

Страница 4: ...motor switching frequency motor cable lengths and installation methods adopted Note For shielded motor cable lengths greater than 100m and up to 200m an output dv dt filter must be used please refer t...

Страница 5: ...Wiring 13 4 7 Connection Diagram IP20 Open IP66 Nema 4X Non Switched Units 14 4 8 Connection Diagram IP66 Nema 4X Switched Units 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4...

Страница 6: ...Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Within the European Union all machinery in which this product is used mu...

Страница 7: ...0 1 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size With Filter Without Filter With Filter Without Filter ODE 2 12037 1KB12 01 ODE 2 12037 1K012 01 0 37 ODE 2 12005 1HB12...

Страница 8: ...162 6 38 5 0 20 123 4 84 82 3 23 50 1 97 5 5 0 22 10 0 39 1 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 109 4 29 63 2 48 5 5 0 22 10 0 39 1 7 3 8 Mounting Bolts All Frame Sizes 4 x M4...

Страница 9: ...s 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmental condition requirements for the drive shown in section 9 1 The...

Страница 10: ...pe For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched...

Страница 11: ...t 3 11 1 IP66 Nema 4X Switched Unit 3 11 2 IP66 Nema 4X Non Switched Unit Drive LED Display Keypad Local Speed Potentiometer A REV 0 FWD Selector Switch B Local Power Isolator Removable Cover Control...

Страница 12: ...must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to one of the ground terminals on the drive Ground Fault Monit...

Страница 13: ...operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor manufacturer should be consulted and preventative m...

Страница 14: ...2 Default No Function 4 Digital Input 3 Default Analog Preset Speed 5 10 Volt Output 6 Analog Input 1 Default 0 10 Volt 7 0 Volt 8 Analog Output Default 0 10 Volts 9 0 Volt 10 Relay Output Default Dri...

Страница 15: ...I Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Spee...

Страница 16: ...will show 4 Close the control switch terminals 1 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer The display shows zero speed in Hz with the potentiometer...

Страница 17: ...et the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the motor...

Страница 18: ...en set to the default value of zero all speed related parameters are displayed in Hz and the slip compensation for the motor is disabled Entering the value from the motor nameplate enables the slip co...

Страница 19: ...pm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected by digital inputs depending on the setting of P 15 If P 10 0...

Страница 20: ...a 0 10V signal and the scaling factor is set to 200 0 a 5 volt input will result in the drive running at maximum frequency speed P 01 P 36 Serial Communications Configuration See Below This parameter...

Страница 21: ...nce between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficie...

Страница 22: ...uency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain op...

Страница 23: ...ence Connect external motor thermistor PTC type or similar to digital input 3 7 Open Stop disable Closed Run enable Open Run Closed Fast Stop External trip input Open Trip Closed Run Analog input 1 re...

Страница 24: ...orward Run Open Run Closed Fast Stop External trip input Open Trip Closed Run Open Keypad speed ref 24V Preset speed 1 Close digital input 3 to carry out a fast stop P 24 provided P 05 0 Example Wirin...

Страница 25: ...Run Enable Run Enable Run Enable PI Preset Speed 1 PI Local Hand PI Preset Speed 1 PI Feedback PI Feedback External Trip 10 Volt Local Hand Ref PI Feedback 0 Volt 0 Volt 0 Volt Remote closed loop PI f...

Страница 26: ...ress 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2 nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Ch...

Страница 27: ...s for 230 Volt rated units 10 variation allowed 240 Volt RMS Maximum Imbalance Maximum 3 voltage variation between phase phase voltages allowed All Optidrive E2 units have phase imbalance monitoring A...

Страница 28: ...eration time reduce load inertia or add further brake resistors in parallel Ensure minimum resistance values form the rating tables are observed Internal power stage fault Check wiring to motor look f...

Отзывы: