7.4.
User PI Control Mode
P-15
Digital input 1 (T2)
Digital input 2 (T3)
Digital input 3 (T4)
Analog input (T6)
Comments
0, 2, 4,
5
8..12
Open: Stop (disable)
Closed: Run (enable)
Open : PI control
Closed : Preset speed 1
PI feedback analog input
No Effect
Analog Input 1 can provide
an adjustable PI setpoint, by
setting P-44 = 1
1
Open: Stop (disable)
Closed: Run (enable)
Open : PI control
Closed : Analog input 1
PI feedback analog input
Analog input 1
Analog Input 1 can provide
an adjustable PI setpoint, by
setting P-44 = 1
3, 6, 7
Open: Stop (disable)
Closed: Run (enable)
Open : PI control
Closed : Preset speed 1
External trip input :
Open: Trip, Closed: Run
PI feedback analog input
Connect external motor
thermistor PTC type or
similar to digital input 3
Example Wiring
PI Mode P-12=5, P-15=0
PI Mode P-12=5, P-15=1
PI Mode P-12=5, P-15=3
+24 Volt
+24 Volt
+24 Volt
Run (Enable)
Run (Enable)
Run (Enable)
PI / Preset Speed 1
PI / Local (Hand)
PI / Preset Speed 1
PI Feedback
PI Feedback
External Trip
+10 Volt
Local (Hand) Ref
PI Feedback
0 Volt
0 Volt
0 Volt
Remote closed loop PI feedback control
with Local Preset speed 1
Remote closed loop PI feedback control with
Local Analog speed input
Remote closed loop PI feedback control with
Local Preset speed 1 and motor thermistor
trip
NOTE
By default the PI reference is set for a digital reference level set in P-45.
When using an Analog reference set P-44 = 1 (analog) and connect reference signal to analog input 1 (T6).
The default settings for proportional gain (P-41), integral gain (P-42) and feedback mode (P-43) are suitable for most HVAC and pumping
applications.
The analog reference used for PI controller can also be used as the local speed reference when P-15=1.
7.5.
Motor Thermistor Connection
1 : + 24 Volt
The motor thermistor should be connected between terminals 1 and 4 as shown. A
setting of P-15 where Digital Input 3 is programmed for ‘External Trip’ must be used.
The current flow through the thermistor is automatically controlled to prevent a
failure.
4 : External Trip