![INVENTOR P9MVI32-09WiFi Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/inventor/p9mvi32-09wifi/p9mvi32-09wifi_installation-manual_2084103037.webp)
Page 37
l
l
l
l
l
11. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring
that this will not exceed the permissible voltage and current permitted for the equipment in
use. Intrinscially safe components are the only types that can be worked on while live in the
presence of a flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result
in the ignition of refrigerant in the atmosphere from a leak.
12. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental effects. The check shall also take into account the
effects of aging or continual vibration from sources such as compressors or fans.
15. Removal and evacuation
When breaking into the refrigerant circuit to make repairs of for any other purpose
conventional procedures shall be used, However, it is important that best practice is followed
since flammability is a consideration. The following procedure shall be adhered to:
remove refrigerant;
purge the circuit with inert gas;
evacuate;
purge again with inert gas;
open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be
flushed with OFN to render the unit safe. This process may need to be repeated several times.
Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to
fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down
to a vacuum. This process shall be repeated until no refrigerant is within the system.
13. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch(or any other detector using a naked flame)
shall not be used.
14. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable
refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the
sensitivity may not be adequate, or may need re-calibration.(Detection equipment shall be
calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition
and is suitable for the refrigerant. Leak detection equipment shall be set at a percentage of the
LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate
percentage of gas (25% maximum) is confirmed. Leak detection fluids are suitable for use with
most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine
may react with the refrigerant and corrode the copper pipe-work.
If a leak is suspected ,all naked flames shall be removed or extinguished. If a leakage of refrigernat
is found which requires brazing, all of the refrigerant shall be recovered from the system, or
isolated(by means of shut off valves) in a part of the system remote from the leak . Oxygen free
nitrogen(OFN) shall then be purged through the system both before and during the brazing process.
Содержание P9MVI32-09WiFi
Страница 41: ......
Страница 42: ...E 11 20 4 0 1 5 6 2 4 Componente aparat 10 3 8 1 20 2 21 3 22 4 23 1 11 2 12 3 12 4 14 5 15 6 16 7 18 8 18...
Страница 43: ...25 29 6 7 8 9 10 34 11 MC MC R32 R290 31 32 34 1 29 2 30 25 B 25 1 25 2 26 3 26 4 27...
Страница 44: ...4 Page 4 1 2 C C C 3 4 5 6 7 8 9 10 7 10 R32 R290...
Страница 45: ...5 Page 5 11 12 13 14 15 16 8 1 3 1 2 3 4 1 2 3 4 12 5...
Страница 46: ...6 1 1 1 1 5 5 2 1 2 Page 6 ST3 9 X 25 M LR03 ST2 9 x 10...
Страница 48: ...8 8 11 12 12 12 1 2 3 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in 2...
Страница 49: ...9 9 STEP 8 1 2 3 5 6 7 8 9 25 17 19 16 19...
Страница 50: ...10 Page 10 3 2 1 1 2 3 4 5 6 7 8 9 10 11 1 2 1 2 3 4 6 7 8 9 10 11 Air break switch 3 1 2 4 5 6 7 8 11 5...
Страница 51: ...11 Page 11 4 Fig 3 1 a 1 o o o o o o 1 c c c...
Страница 55: ...15 Page 15 Fig 3 6 Fig 3 7 Fig 3 8 3 3 15cm 6in 2 3 4 5 6 7 1 2 3 8 3 6 3 7 3 8...
Страница 56: ...16 Page 16 Fig 3 9 Fig 3 10 Fig 3 11 Fig 3 12 4 5 6 7 5 1 2 3 Teflon 4 5 3 9 3 9 3 10 3 12 3 11...
Страница 59: ...19 Page 19 Fig 3 14 7 1 3 14 2 3 3 14 8 1 4 2 3 4 5 6 7 3 14...
Страница 60: ...20 Page 20 5 n i 4 2 m c 0 6 60cm 24in 30cm 12in 200cm 79in 30cm 12in Fig 4 1 1 o 4 1 o o o o 4 1...
Страница 61: ...21 Page 21 A B Fig 4 2 Fig 4 3 Fig 4 4 90 4 2 4 3 4 4 1 2 3 90 4 4 4 1 2 4 3 4 2 4 4 2...
Страница 63: ...23 Page 23 1 2 3 4 5 6 7 8 4 1 2 3 4 90 100 5 1 5 6 1 8in 3mm 7 8 9 10 11 1 40in...
Страница 68: ...28 Page 28 Fig 5 9 Fig 5 10 5 6 7 3 6 5 9 5 10 1 5 9 2 3 4...
Страница 69: ...29 Page 29 7 76cmHg MC MC Fig 6 1 o o 1 2 3 4 5 15 76cmHG 105Pa 6 1...
Страница 71: ...31 Page 31 8 4...
Страница 72: ...32 Page 32 9 30 1 2 ON OFF 3 MODE 4 5 2 2...
Страница 73: ...33 Page 33 Fig 8 1 5 17O C 63 F 17 C MANUAL CONTROL 1 MANUAL CONTROL 8 1 2 2 COOL 4 Manual Control 8 1...
Страница 74: ...34 Page 34 10...
Страница 75: ...35 Page 35 11 R32 R290 1 2 3 4 5 6 7 8 l...
Страница 76: ...36 l l l l O 9 l l 10 10 1 10 2 l l...
Страница 77: ...37 11 12 13 14 LFL 25 OFN 15 l l l l l OFN OFN...
Страница 78: ...38 OFN 16 l l l l l l OFN 17 l l l l 80...
Страница 79: ...39 18 19 l l l l l l l 20 1 2 3 4 5...
Страница 118: ...NOTES...
Страница 119: ......