27
6.15 Fan Control
Outline
Fan control is carried out according to the follo ing priority.
1. Fan ON control for electric component cooling fan
2. Fan control when defrosting
3. Fan OFF delay when stopped
4. ON/OFF control in cooling operation
5. Tap control when drooping function is working
6. Fan control in forced operation
7. Fan control in indoor/outdoor unit silent operation
8. Fan control in powerful mode
9. Fan control in normal operation
Detail
Fan OFF Control hen Stopped
* Fan OFF delay for 60 seconds must be made when the compressor is stopped.
Tap Control in indoor/outdoor unit silent operation
1. When Cooling Operation
When the outdoor air temperature is lower than 99°F, the fan tap must be set to L.
2. When Heating Operation
When the outdoor air temperature is higher than 39°F, the fan tap must be turned to L (only for heat pump model).
Frequency
Compressor
Four way valve
Fan
Electronic expansion
valve opening
ON
OFF
ON
OFF
ON
OFF
0Hz
5sec.
350pps
450pps
450pps
Initial opening
PI control
5sec.
50sec.
50sec.
600sec.
60sec.
Function and Control
Содержание CEVI-09
Страница 1: ......
Страница 15: ...13 5 3 Printed Circuit Board TOP VIEW BOTTOM VIEW Schematic Diagram ...
Страница 16: ...14 HUR OLQH ZLUH XQGHU YROWDJH FRPPXQLFDWLRQ ZLUH GLVSDO ERDUG LQIUDUHG UHFHLYHU Schematic Diagram ground wire ...
Страница 17: ...15 TOP VIEW BOTTOM VIEW Schematic Diagram ...
Страница 18: ...16 FRONT VIEW BOTTOM VIEW Schematic Diagram ...
Страница 19: ...17 TOP VIEW BOTTOM VIEW Schematic Diagram ...
Страница 36: ...34 8 EXPLODED VIEWS AND PARTS LIST 8 1 Exploded View Indoor Unit Exploded Views and Parts list ...
Страница 37: ...35 Outdoor Unit 1 Cooling Only Models Exploded Views and Parts list ...
Страница 38: ...36 2 Cooling Heating Models Exploded Views and Parts list ...
Страница 68: ...66 13 Remove Motor Sub Assy 14 Remove Fan Motor Remove Motor Sub Assy 1 Removal Procedure ...
Страница 69: ......
Страница 70: ......
Страница 74: ......