End
Y
N
Y
N
Y
N
Overheat and high
temperature protection
Is outdoor ambient temperature higher than 53?
20 minutes after the complete
unit is powered off.
Is heat dissipation of the indoor unit
and outdoor unit abnormal?
Normal protection, please operate
it after the outdoor ambient temp-
erature is normalized.
Improve the heat
dissipation environ-
ment of the unit
Does the outdoor fan work normally?
1. Check if the fan terminal OFAN
is connected correctly
2. Resistance between any two
terminals is measure by an ohm
gauge and should be less than 1K
Ohm.
Replace the
control panel
AP1
Replace the fan
capacitor C1
Replace the
outdoor fan
48
Содержание C1VI-09
Страница 1: ...C1VI 09 C1VO 09 C1VI 12 C1VO 12 ...
Страница 2: ...a b e 2 3 3 7 7 8 8 9 10 11 12 12 12 14 16 16 19 24 24 26 27 28 ...
Страница 3: ...Simply 29 30 31 31 35 39 39 62 59 43 46 44 59 ...
Страница 5: ...2 ...
Страница 6: ...C1VI 09 C1VO 09 C1VI 09 C1VO 09 C1VI 09 3 ...
Страница 7: ...C1VO 09 4 ...
Страница 8: ...C1VI 12 C1VO 12 C1VI 12 C1VO 12 C1VI 12 5 ...
Страница 9: ...C1VO 12 6 ...
Страница 12: ...9 ...
Страница 13: ...10 ...
Страница 17: ...1 2 3 4 5 6 7 8 9 10 11 12 14 ...
Страница 18: ...11 10 9 8 7 6 13 12 14 5 4 3 2 1 15 ...
Страница 24: ...21 ...
Страница 25: ...A L B C D O 0 O 0 L1 A1 B1 C1 D1 heating angle cooling angle 22 ...
Страница 26: ...23 ...
Страница 27: ...24 ...
Страница 28: ...25 ...
Страница 33: ...Fig a filter Air filter Fig b Fig c Healthy 30 ...
Страница 35: ...C1VI 09 32 ...
Страница 37: ...C1VI 12 34 ...
Страница 38: ...1 2 3 4 5 7 8 9 10 11 13 14 15 16 17 18 19 20 21 22 6 12 C1VO 09 35 8 2 Outdoor Unit ...
Страница 39: ...C1VO 09 36 ...
Страница 40: ...1 2 3 4 5 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 6 C1VO 12 37 ...
Страница 41: ...C1V0 12 38 ...
Страница 46: ...43 ...
Страница 47: ...44 ...
Страница 48: ...45 ...
Страница 57: ...54 ...
Страница 59: ...56 ...
Страница 60: ...57 ...
Страница 61: ...58 ...
Страница 62: ...59 ...
Страница 63: ...60 ...
Страница 64: ...61 ...
Страница 70: ......