32
inVENTer Connect controller platform | Installation instructions
INSTALLING THE DEVICES
Connecting cables
DANGER
Exposed electrical components.
Electric shock and injury due to live components (230V, 50Hz)!
•
Before working on electrical installations, disconnect all affected equipment from the power supply.
• Observe the requirements for protection class II when laying the power supply cable.
Do not lay live cables.
• Lay the mains connection cables and data cables separately.
Installation and connection must only be performed by qualified and trained personnel.
Stripping tool, small slotted screwdriver
Requirements:
•
The box is fitted.
• The cable has been laid.
• The power supply is disconnected.
►
Strip approx. 8.5 mm of the mains connection cable
with the stripping tool.
►
Fix this cable (blue/brown) in the screw terminal on
the programming unit's base plate:
• Connect the phase conductor with cable L
(brown).
• Connect the neutral conductor with cable N
(blue).
►
Push the mains connection cable into the box.
The mains connection cable is installed.
►
Strip approx. 8.5 mm of the RS485 data cable with
the stripping tool.
►
Secure the RS485 data cable (red/yellow) into the
screw terminal on the programming unit's base
plate:
• Signal cable A (red) to "1".
• Signal cable B (yellow) to "2".
►
Push the RS485 data cable into the box.
The RS485 data cable is installed.
The mains connection cable and, if necessary, the RS485 data cable are connected to the rear of
the base plate of the controller's programming unit.
Connecting the data cable
(only if the system devices communicate via cable)
Connecting the mains connection
cable
2 1
L N