16
6. Technical data and installation details
6.1 Controller
6.1.1 Single membrane station controller
The single-station controller is for residential or small applications to control one Membrane Station.
AL-CUNIT-S
Dimensions (H x W/(incl. switching power supply) x D):
201 x 198 (329) x 110 mm (8 x 7.8 (13) x 4.5 in)
Mains supply central controller (230V-IN):
110 - 230 V AC / 50-60 Hz
AC switching power supply input:
110 - 230 V AC / 50-60 Hz (24 VDC, 4.0 A)
AC switching power supply output:
24 V DC, 4.0 A
Cable length of mains supply:
3 x 1.0 mm² x 1.5 m (3 x 0.0016 in² x 5 ft)
Cable length of AC switching power supply:
3 x 0.75 mm² x 2.0 m (3 x 0.0012 in² x 6.6 ft)
Power outputs:
-
Blower (voltage according mains supply):
110 - 230 V AC / 50-60 Hz, max. 4 A
-
Sludge pump (voltage according mains supply):
110 - 230 V AC / 50-60 Hz, max. 4 A
Low voltage outputs:
-
Filtration pump:
24 V DC, max. 4 A
-
Backwash pump:
24 V DC, max. 4 A
-
Blower (Air):
24 V DC, max. 4 A (alternative)
Signal inputs:
-
Bioreactor MIN (BR min):
Float switch, normally open contact
-
Clear water tank MAX (CL max):
Float switch , normally open contact
-
Clear water tank MIN (CL min):
Pot, free contact (alternative)
Potential-free signal output:
-
Clear water tank MIN (CL min OUT):
Signal of CL max
Signal inputs:
-
Pressure sensor, membrane hub (ADr):
4 … 20 mA
-
Pressure sensor, blower (ADg):
4 … 20 mA
-
Programmer connection:
6 pol., RM 2.53
Protection type:
IP54
Material unit case:
PS, PA
Float switch:
Function:
Normally open contact (MIN = closed contact)
Cable length x Diameter, Material:
15 m x Ø8 mm, 2 x 0.75mm² (49 ft x Ø0.3 in,
2 x 0.0012 in²) , H07 RN-F
Protection type:
IP68
Material:
PP
Remote control:
no
BacNet:
no
Содержание AQUALOOP GW 10800
Страница 10: ...9 Tab Official listing https www intewa de en applications rain greywater harvesting greywaterrecycling...
Страница 12: ...11 Fig AQUALOOP System 1200 L day 317 GPD Fig AQUALOOP System 1800 L day 476 GPD...
Страница 13: ...12 Fig AQUALOOP System 3600 L day 952GPD Fig AQUALOOP System 5400 L day 1428 GPD...
Страница 37: ...36 Fig Electrical connection plan upper pump lower pump...
Страница 39: ...38 Fig Control cabinet of multiple membrane station controller...
Страница 42: ...41 7 1 3 Expansion membrane station controller Fig Control cabinet of expansion controller...
Страница 89: ...88 Designed and provided by INTEWA GmbH or to be separately approved alternative...