Esta  interfaz  debe  ser  instalada  por  personal  técnico 
acreditado  (electricista,  instalador  o  personal  técnico 
cualificado)  y  siguiendo  todas  las  instrucciones  de 
seguridad. 

 

La interfaz debe ser instalada en una ubicación con acceso 
restringido. 

 

Antes  de  manipular  en  el  interior  del  aire  acondicionado, 
asegúrese de que está completamente desconectado  de  la 
red eléctrica.  

 

En caso de instalación mural de la interfaz junto a la unidad 
interior  de  aire  acondicionado,  fije  la  interfaz  de  forma 
segura siguiendo las instrucciones del diagrama de abajo. 

 

This  interface  must  be  installed  by  accredited  technical 
personnel  (electrician,  installer  or  qualified  technical 
personnel) and they must follow all the safety instructions. 
 

 

This  interface  must  be  installed  in  an  acces  restricted 
location 

 

Before  manipulating  the  AC  indoor  unit,  make  sure  it  is 
completely disconnected from Mains Power. 
 

 

In  case  of  wall  mounting  of  the  interface  next  to  the  AC 
indoor  unit,  attach  the  interface  safely  following  the 
instructions of the diagram below. 

 

 

Desconecte el aire acondicionado de la red eléctrica. 

 

Fije la interfaz a la pared junto a la unidad interior del aire 
acondicionado  siguiendo  las  instrucciones  del  diagrama  de 
abajo o dentro de la unidad interior del aire acondicionado 
(respete las instrucciones de seguridad anteriores). 

 

Conecte  la  interfaz  al  bus  R1R2  en  cualquier  punto  del 

mismo.  El  bus  R1R2  es  el  bus  que  conecta  la  unidad 
interior de aire acondicionado y el mando por cable, es un 
par  de  hilos  que  se  conectan  los  terminales  R1  R2.  La 
conexión R1R2 no tiene polaridad. 

 

Conecte  el  bus  EIA-485  al  conector 

EIA485

  de  la  interfaz. 

Respete la polaridad. 

 

Tape  la  unidad  interior  del  aire  acondicionado  y  vuelva  a 
conectarla a la red eléctrica. 

 

Siga  las  instrucciones  del  Manual  de  Usuario  para  la 

configuración y puesta en servicio de la interfaz. 

 

Siga  las  instrucciones  de  la  página  siguiente  para 
configurar la interfaz a través de los micro interruptores. 

 

Disconnect the air conditioning from the Mains Power. 

 

Attach  the  interface  next  to  the  AC  indoor  unit  (wall 
mounting) following the instructions of the diagram below or 

install  it  inside  the  AC  indoor  unit  (respect  the  safety 
instructions given above). 

 

Connect  the  interface  to  R1R2  bus  in  any  point  of  the  bus. 
The  R1R2  bus  is  the  bus  that  connects  the  AC  indoor  unit 
and  the  wired  Remote  Controller.  It  is  a  two-wire  bus 
connecting  terminals  R1R2.  The  R1R2  connection  has  no 
specific polarity. 

 

Connect  the  EIA-485  bus  to  the  connector 

EIA485

  of  the 

interface. 

 

Close the AC indoor unit and reconnect it to Mains Power. 

 

Follow  the  instructions  on  the  User

’s  M

anual  to  configure 

and commission the interface. 

 

Follow  the  instructions  of  the  next  page  to  configure  the 
interface through on-board DIP-switches. 

 

  

WARNING 

  

ATENCIÓN 

Siga  atentamente  estas  instrucciones  de  seguridad  e 
instalación.  Un  manejo  inadecuado  puede  ocasionar  daños 
graves  para  su  salud  y  daños  irreparables  en  la  interfaz  y/o 
en la unidad interior del aire acondicionado. 

Follow  carefully  this  safety  and  installation  instructions.  Not 
proper work may lead to a serious damage for your health and 
may harm seriously the interface and/or the AC indoor unit. 

IMPORTANTE:

  El  cable  a  usar  para  la  conexión  de  PA-

RC2-MBS-1 al bus R1R2 puede ser cualquier cable de dos hilos. 
La  distancia  máxima  para  el  bus  R1R2  es  de  500  metros 
(1640.42 pies). Consulte el Manual del aire acondicionado para 
más detalles. 
 

IMPORTANT:

  The  cable  used  for  connection  of  PA-RC2-

MBS-1 to R1R2 bus can be any two-wire cable. The maximum 
distance  for  bus  R1R2  is  500  meters  (1640.42  ft).  Check  the 
Manual of the AC indoor unit for more details. 

 

El Manual de Usuario está disponible en: 
 

https://www.intesisbox.com/en/panasonic-modbus-vrf-pa-rc2-mbs-1/gateway/ 

The 

User’s Manual

 is available at:  

 

https://www.intesisbox.com/en/panasonic-modbus-vrf-pa-rc2-mbs-1/gateway/ 

 

Instrucciones de seguridad 

 

Safety intructions 

 

Instrucciones de instalación 

 

Installation instructions 

 

NOTA:

  En  algunas  unidades  interiores  no  existe  el  conector 

R1R2  y  en  su  lugar  existen  dos  cables  para  la  conexión  del 
Control Remoto. Utilice dichos cables para conectar el bus R1R2. 
Consulte  el  Manual  de  Usuario  de  su  unidad  interior  para  más 

información. 

 

R1  
R2 

90 mm / 3.5”

 

IntesisBox

®

 

PA-RC2-MBS-1 

MODBUS RTU 

EIA-485 

Bus

 

EIA485 

 A+  B- 

R1 R2 

AC Unit 

53 mm / 2.1”

 

Para fijación mural 

extraiga hacia fuera 
las grapas superior 
e inferior hasta oir 

el "click". 
 

For wall mounting 
extract the upper 
and down staples 

until you hear the 
"click".

 

1  2 

Unidad interior de A.A. 

AC Indoor Unit 

(No es obligatorio tenerlo en la red) 

(It is not mandatory to have it in the network) 

 

Internal 
electronic 
control board 

Tarjeta 
Control 
electrónico 

Conexión al bus R1R2. 
Cable de dos hilos. 

 

Connection to R1R2 
bus. Two wire cable. 

Remote Controller 

 

NOTE:

 In some indoor unit models the R1R2 connector is not 

available.  In  its  place  there  is  a  pair  of  cables  to  connect  the 
Remote Controller. Use these cables to connect the R1 R2 bus. 
Check your indoor unit User

’s M

anual for more information. 

Control Remoto 

Max 500 m / 1640.42 ft 