IntesisBox

®

 Modbus Server – Mitsubishi Heavy Industries AC 

 

Connections and indications 

 

________________________________________________________________________________________ 

Notes: 
 

1. 

Mains power conection: 230VAC (see sectionTechnical Characteristics). The device provides switch and a protection fuse. Use the supplied cable with IntesisBox (1,6m). 
 

2. 

Console conection: Connect the supplied console cable with IntesisBox (1.8 meters long, standard DB9 male-DB9 female) between your PC and the console port of the 
device. Use the software LinkBoxMB to configure IntesisBox. See the user's manual for details. 

 

3. 

Modbus connection: IntesisBox allows different connection types: Modbus TCP (ETH port), Modbus RTU EIA485 (C1 port), or Modbus RTU EIA232 (C2 port), this must 
be configured within LinkBoxMB software. 

 

 

Modbus TCP: Connect the cable coming from the Modbus TCP master device to the connector ETH of IntesisBox, use a crossover ethernet CAT5  cable if 
connecting directly to the Modbus TCP master device, or an straight ethernet CAT5 cable if connecting to a switch or hub o f the LAN of the building. If 
connecting using the LAN of the building contact the network administrator and make sure that TCP/IP traffic and the TCP port  used (502 by default) are 
allowed through all the LAN path. 

 

Modbus  RTU  EIA485:  Connect  the  EIA485  bus  to  the  connector  Modbus  RTU  EIA485  of  IntesisBox  (C1).  Respect  the  polarity.  Remember  the 
characteristics of  the  standard  EIA485  bus:  maximum  distance of 1200  meters,  maximum  32 device  connected, and  a 120  ohms  term inator  resistor  in 
each  end of the  bus. IntesisBox  comes with  an  internal bus byasing circuit which  incorporates  internal bus  terminator  resistor,  and  thus  if  you  co nnect 
IntesisBox in one end of the bus then it is not necessary to install additional 120 ohms resistor in that end. 

 

Modbus RTU EIA232: Connect the serial EIA232 cable coming from the Modbus RTU master device to the Modbus RTU EIA232 connector of IntesisB ox 
(C2), this is a male DB9 connector (DTE) in which only lines TX, RX and GND are used, see pinout details in the user's manual. Respect the maximum 
distance of 15 meters for this EIA232 line. 

 

4. 

A-B connection: Connect the SuperLink

®

 bus coming from the Mitsubishi Heavy Industries AC to the conector A-B of IntesisBox. Recpect the polarity, and consult your 

distributor for more details.   

 
5. 

The device provides a “RESET” button. 

 

6. 

The device provides a selector to choose the SuperLink

® 

bus type. If it belong to the OLD version (SuperLink

®

 1), or to the NEW version (SuperLink

®

 2). 

 

7. 

OP led: indication that the device is operative. 

 

8. 

ERROR led: the led is ON when there is a communication error. 

 

9. 

HOST led: the led is blinking when there is connectivity between the two circuits that compose IntesisBox. 

 

10. 

PAC led: the led is blinking when there is activity in the SuperLink® bus, ie when there is communication between IntesisBox and AC system. 
 
 

 

Device front view 

 

Device back view 

 

7  8  9  10 