IntesisBox LON-KNX Скачать руководство пользователя страница 5

 

           

       

 

 

 

                         
 
                                      

 

 

 

IntesisBox

®

 LON - KNX

 

Doc. Rev.3 

Installation Manual 

 

 

URL 

email 

tel 

 

http://www.intesis.com                                          
info@intesis.com 
+34 938047134 
 

    5 / 6 

This information is subject to change without notice.

 

 

 
 

Enclosure 

Plastic, type PC (UL 94 V-0).  
Dimensions: 159mm x 105mm x 58mm. 

Color 

Grey. RAL 7035. 

Power 

De 9 a 30Vcc +/-10%, Máx.: 210mA 
24Vca  +/-10% 50-60Hz, Máx.: 212mA 
Must use a NEC Class 2 or Limited Power Source (LPS) and SELV 
rated power supply. 
Plug-in screw terminal block (2 poles) for 12 AWG cable. 

Terminal wiring 
(for power supply 
and low-voltage 
signals) 

Per terminal: solid wires or stranded wires  (twisted or with 
ferrule) 
1 core: 0.5mm

2

… 2.5mm

2

 

2 cores: 0.5mm

2

… 1.5mm

2

 

3 cores: not permitted 

Mounting 

Wall 
DIN rail EN60715 TH35. 

LON Port  

1 x LON TP/FT-10. Plug-in screw terminal block (2 poles) for 12 
AWG cable. TNV-1 

KNX Port 

1 x KNX TP1 (EIB) opto isolated. Plug-in screw terminal block (2 
poles) for 12 AWG cable. TNV-1 

LED indicators  

1 x Power. 
2 x KNX port activity (Tx, Rx). 
2 x Gateway status: LA (LON status), LB (KNX status) 
1 x KNX programming.

1

 

2 x LON Service LED. 

Switches 

1 x KNX programming.

1

 

2 x Service LON. 

Console port 

USB. Type B female standard connector. SELV 

Ethernet port 

1 x Ethernet 10/100Base-T connector RJ45. 

Configuration 

Via USB console port and/or Ethernet interface 

2

 

Firmware 

Allows upgrades via USB console port and/or Ethernet interface 

Operational 
temperature 

0°C to +60°C

 

Operational 
humidity 

10% to 90%, non condensation 

Protection 

IP20 (IEC60529). 

RoHS conformity  

Compliant with RoHS directive (2002/95/CE). 

Norms and 
standards 

CE conformity to EMC directive (2004/108/EC) and Low-voltage 
directive (2006/95/EC) 
EN 61000-6-2 
EN 61000-6-3 
EN 60950-1 
EN 50491-3 

 
 

1

   Not operational for the moment. Reserved for future use. 

 

2

   Standard cable USB type A-B of 1,8 meters length is supplied with the device for connection to a PC USB port for configuring 

and monitoring the device. The configuration software, compatible with Windows

®

 operating systems, is also supplied.

 

 

Technical characteristics 

 

Содержание LON-KNX

Страница 1: ...charge to the unit in environments with static levels above 4 kV precautions should be taken when the device is mounted outside an enclosure When working in an enclosure ex making adjustments setting switches etc typical anti static precautions should be observed before touching the unit Safety Instructions WARNING Follow carefully this safety and installation instructions Improper work may lead t...

Страница 2: ...he figure below 2 Use the holes of the clips to fix the box in the wall using screws Use the template below for the wall holes Wall mount Clips in their original position for DIN rail mount Clips in position for wall mount Top view of the box Bottom view of the box 114mm Ø 3mm LA LB PROG BUS 159mm 105mm TX RX POWER PC Console USB 1 1 1 1 1 1 1 1 1 I B O X L O N K N X 2 0 0 KNX TP 1 EIB Tx Rx PROG ...

Страница 3: ...on is subject to change without notice With the clips of the box in their original position insert first the box in the upper edge of the DIN rail and later insert the box in the down part of the rail using a small screwdriver and following the steps in the figure below DIN rail mount DIN rail EN60715 TH35 1 2 3 Side view of the box ...

Страница 4: ...tive terminal If using AC power supply Make sure the voltage applied is of the value admitted 24 Vac Do not connect any of the terminals of the AC power supply to earth and make sure the same power supply is not supplying any other device 2 Use the software LinkBoxLON to configure IntesisBox Consult the user s manual for details LinkBoxLON Only for configuration See Note 2 Console Cable USB standa...

Страница 5: ... indicators 1 x Power 2 x KNX port activity Tx Rx 2 x Gateway status LA LON status LB KNX status 1 x KNX programming 1 2 x LON Service LED Switches 1 x KNX programming 1 2 x Service LON Console port USB Type B female standard connector SELV Ethernet port 1 x Ethernet 10 100Base T connector RJ45 Configuration Via USB console port and or Ethernet interface 2 Firmware Allows upgrades via USB console ...

Страница 6: ...ntesis com 34 938047134 6 6 This information is subject to change without notice Dimensions External dimensions Free space recommended to install the device with spacing enough for external connections 159 mm 130 mm 60 mm KNX Port Power Console Port 159 mm 105 mm 58 mm LON Port Ethernet Port ...

Отзывы: