BACnet/IP Server - Modbus TCP Master
User’s Manual r1 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SL
URL
Email
tel
http://www.intesis.com
[email protected]
+34 938047134
21 / 27
Bac.Name
Description
BACnet object name for the signal. This name is included into the BACnet's
Object_name
property for the point and it will be collected by any BACnet
explorer.
Restrictions
Maximum 30 characters
Edit mode
Text edit
Comments
Recommended to give a descriptive name to each point with indication of
the Modbus TCP slave/register associated
Bac.Type
Description
BACnet object type for the signal.
Values
AI = Analog Input.
AO = Analog Output.
AV = Analog Value.
DI = Digital Input.
DO = Digital Output.
DV = Digital Value.
MI = Multistate Input.
MO = Multistate Output.
MV = Multistate Value.
Edit mode
Single / Multiple Values selection.
Comments
Edit using the mouse right-button-click pop-up menu
Bac.ID
Description
BACnet object instance number for the point. It can be manually entered by
the user or can be automatically assigned by LinkBoxBacnet when saving the
configuration (section 5.1.4)
Restrictions
All the object instance numbers for objects of the same type must be
different
Edit mode
Text edit or AutoEnumeration
Comments
It is recommended to let LinkBoxBacnet assign automatically object instance
numbers for the points