IntesisBox IBOX-ASCII-KNX Скачать руководство пользователя страница 2

  

2 / 2

 

This information is subject to change without prior notice 

IntesisBox

 

is a registered trademark of Intesis Software S.L.U.

 

email

[email protected]

  

web

www.intesisbox.com 

 

phone: +34 938047134

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Enclosure 

Plastic, type PC (UL 94 V-0) 
Net dimensions (d

x

w

x

h): 90x88x56 mm  

Recommended space for installation (d

x

w

x

h): 130x100x100mm 

Color: Light Grey. RAL 7035 

 

Battery 

Size: Coin 20mm x 3.2mm 
Capacity: 3V / 225mAh 
Type: Manganese Dioxide Lithium 

Mounting 

Wall. 
DIN rail EN60715 TH35. 

 

Console Port 

Mini Type-B USB 2.0 compliant 
1500VDC isolation 

Terminal Wiring 

(for power supply and 
 low-voltage signals) 

Per terminal: solid wires or stranded wires (twisted or with 
ferrule) 

1 core: 0.5mm

2

… 2.5mm

2

 

2 cores: 0.5mm

2

… 1.5mm

2

 

3 cores: not permitted 

If cables are more than 3.05 meters long, Class 2 cable is required.

 

 

USB port 

Type-A USB 2.0 compliant 
Only for USB flash storage device  

(USB pen drive) 

Power consumption limited to 150mA  

(HDD connection not allowed)

 

Power 

1 x Plug-in screw terminal block (3 poles) 

9 to 36VDC +/-10%, Max.: 140mA. 
24VAC +/-10% 50-60Hz, Max.: 127mA 
Recommended: 24VDC 

 

Push Button 

Button A: KNX programming button (not used) 
Button B: Not used 

Operation 
Temperature 

0°C to +60°C 

Ethernet 

1 x Ethernet 10/100 Mbps RJ45 
2 x Ethernet LED: port link and activity 

 

Operational 
Humidity 

5 to 95%, no condensation 

Port A 

1 x KNX TP-1 Plug-in screw terminal block orange (2 poles) 

2500VDC isolation from other ports 
KNX power consumption: 5mA 
Voltage rating: 29VDC 

1 x Plug-in screw terminal block green (2 poles) 
Reserved for future use 

 

Protection  

IP20 (IEC60529) 

LED 
Indicators 

10 x Onboard LED indicators 

2 x Run (Power)/Error  
2 x Ethernet Link/Speed 
2 x Port A TX/RX 

2 x Port B TX/RX 

1 x Button A indicator 
1 x Button B indicator 

Switch A  

(SWA)

 

1 x DIP-Switch for PORT A configuration: 

Reserved for future use 

 

 

 

PORT B 

1 x Serial EIA232 (SUB-D9 male connector) 

Pinout from a DTE device 
1500VDC isolation from other ports 

(except PORT B: EIA485) 

1 x Serial EIA485 Plug-in screw terminal block (3 poles) 

A, B, SGND (Reference ground or shield) 
1500VDC isolation from other ports 

(except PORT B: EIA232)  

 

 

Switch B  

(SWB)

 

1 x DIP-Switch for serial EIA485 configuration: 

Position 1:  

ON:

 

120 Ω termination active 

Off:

 

120 Ω termination inactive (default) 

Position 2-3: 

ON:

 Polarization active 

Off:

 Polarization inactive (default)

 

 

 

 

CONNECTIONS 

ELECTRICAL & MECHANICAL FEATURES 

Power Supply 
Must use NEC Class 2 or Limited Power Source (LPS) and SELV

 

rated power supply. 

 

If using DC power supply: 
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted 
(check table below). The power supply can be connected to earth but only through the negative terminal, 
never through the positive terminal. 

 

If using AC power supply: 
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the 
AC power supply to earth, and make sure the same power supply is not supplying any other device. 

 

Ethernet / ASCII TCP (TCP) / Console (UDP & TCP) 
Connect  the  cable  coming  from  the  IP  network  to  the  connector  ETH  of  the  gateway.  Use  an  Ethernet  CAT5 
cable. If communicating through the LAN of the building, contact the network administrator and make sure traffic 
on the port used is allowed through all the LAN path (check the gateway user manual for more information). 

With 

factory settings, after powering up the gateway, DHCP will be enabled for 30 seconds. After that time, if 
no IP is provided by a DHCP server, the default IP 192.168.100.246 will be set. 

 

PortA / KNX 
Connect the KNX TP1 bus to connectors A3 (+) and A4 (-) 

of gateway’s PortA. Respect the polarity. 

 

PortB / ASCII 
Connect the EIA485 bus to connectors B1 (B+), B2 (A-) and B3 (SNGD) of 

gateway’s PortB. Respect the polarity. 

Connect  the  serial  cable  EIA232  coming  from  the  external  serial  device  to  the  EIA232  connector  of 
gateway’s PortB. This is a DB9 male (DTE) connector in which only the lines TX, RX and GND are used. 
Respect the maximum distance of 15 meters.  

 

Note for PortA and PortB; Remember the characteristics of the standard EIA485 bus: maximum distance of 
1200 meters, maximum 32 devices connected to the bus, and in each end of the bus it must be a termination 
resistor of 

120 Ω. The gateway has an internal bus biasing circuit that incorporates the termination resistor. If you 

install the gateway in one of the ends of the bus, then do not install an additional termination resistor in that end. 

 

Console Port 
Connect  a  mini-type  B  USB  cable  from  your  computer  to  the  gateway  to  allow  communication  between  the 
Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user 
manual for more information. 

 

USB 
Connect a USB storage device (not a HDD) if required. Check the user manual for more information. 

Power Supply 

Ethernet 
ASCII TCP 

USB  
storage 

Console 
Port 

100 mm (h) 

100 mm (w) 

130 mm (d) 

ASCII 
EIA485 

 

ASCII 
EIA232 

 

KNX 

Отзывы: