IntesisBox
®
BACnet/IP Server - LON
Doc. Rev.1
Installation Manual
URL
tel
http://www.intesis.com
[email protected]
+34 938047134
3 / 5
This information is subject to change without notice.
Connections
________________________________________________________________________________________
Notes:
1.
Must use NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply.
If using DC power supply:
•
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted
(9 to 30 Vdc). The power supply can be connected to earth but only through the negative terminal, never
through the positive terminal.
If using AC power supply:
•
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the
AC power supply to earth, and make sure the same power supply is not supplying any other device.
2.
BACnet/IP connection: Connect the cable coming from the BACnet/IP client to the connector ETH of IntesisBox, use
a crossover or a straight ethernet CAT5 cable connecting to a hub or switch of the LAN of the building. Contact the
network administrator and make sure that UDP traffic and the port used (47808 by default) are allowed through all
the LAN path.
3.
Use the software LinkBoxBacnet to configure IntesisBox. See the user's manual for details.
Console wire 1.8 m long.
DB9 Female - DB9 Male
standard. It is supplied.
LinkBoxBacnet
Only needed for
configuration
See Note 3
Power
See Note 1
BACnet/IP
See Note 2
LON
TP/FT-10
PC Console
- +
Ethernet
BACnet/IP
IntesisBox
®
www.intesis.com
Ethernet
RJ45
B A
LON TP/FT-10
CMN 24Vac
9 - 30Vdc
Max.125 mA
24Vac
Max.127mA
50-60Hz