This information is subject to change without notice.
Connections
________________________________________________________________________________________
Notes:
1.
Must use NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply.
If using DC power supply:
•
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (9 to 30 Vdc).
The power supply can be connected to earth but only through the negative terminal, never through the positive terminal.
If using AC power supply:
•
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the AC power
supply to earth, and make sure the same power supply is not supplying any other device.
2.
ASCII EIA232 connection: Connect the cable coming from the programmable controller to the connector ASCII EIA232 of IntesisBox,
this is a standard EIA232 Db9 male connector (DTE) in which only lines TX, RX and GND are used, see user's manual for details.
Respect the maximum distance of 15 meters for this cable.
3.
Use the software LinkBoxEIB to configure IntesisBox. Consult the user's manual for details.
LinkBoxEIB
Only for configuration
See Note 3
Console Cable 1.8 m.
Standard DB9F - DB9M.
Supplied.
Power
See Note 1
PC Console
- +
IntesisBox
®
www.intesis.com
ASCII
EIA232
See Note 2
EIA232
ASCII
KNX TP-1
(Bus EIB)
+ -
KNX TP-1
CMN 24Vac
9 - 30Vdc
Max.125 mA
24Vac
Max.127mA