![Intertek GPG 16 SEER Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/intertek/gpg-16-seer/gpg-16-seer_installation-instructions-manual_2080764020.webp)
20
C
LEANING
B
URNERS
1. Shut off electric power and gas supply to the unit.
2. Remove the screws securing the manifold to the burner
retention bracket. Remove the manifold and rotate each
burner counterclockwise to remove.
3. Remove the burners.
4. Use a bottle brush to clean burner insert and inside of the
burners.
5. Replace burners and manifold, inspect the burner assembly
for proper seating of burners in retention slots.
6. Reconnect electrical power and gas supply.
For further information on the yearly inspection, consult the
User Manual. It is recommended that a qualified servicer inspect
and service the unit at least once each year.
Turn the unit on at the thermostat. Wait a few minutes, since
any dislodged dust will alter the normal flame appearance. Flames
should be predominantly blue and directed into the tubes. They
should not be yellow. They should extend directly outward from
the burner ports without curling downward, floating or lifting off the ports.
ACCESSORIES AND FUNCTIONAL PARTS
S
HEET
M
ETAL
A
CCESSORIES
Additional accessories can be purchased to fit specific application needs. Parts and
instructions are available from your distributor.
F
UNCTIONAL
P
ARTS
Functional Parts List
G
ENERAL
I
NFORMATION
1. Refer to the description in Functional Parts List when ordering any of the listed functional parts. Be sure to provide the
unit model and serial numbers with the order.
2. Although only functional parts are shown, all sheet metal parts, doors, etc. may be ordered by description.
3. Parts are available from your distributor.
Check the burner flames for:
1. Good adjustment
2. Stable, soft and blue
3. Not curling, floating, or lifting off.
Burner Flame
Burner
Bracket
Burner
Manifold
Manifold Assembly
Auxil ia ry Li mi t Switch
Fl ame Sens or
Blower Hous i ng
Gas Orifice
Blower Wheel
Gas Va lve
Burner
Hea t Exchanger
Ci rcula tor Blower Motor
High Limit Swi tch
Ca pa citor
High Pres s ure Switch
Compres s or
Igni ter
Condens er Coil
Igni tion Control
Condens er Fa n Bl ade
Induced Dra ft Bl ower
Condens er Fa n Motor
Pres s ure Switch
Contactor
Pres s ure Switch Hos e
Ga s Ma nifold
Thermos ta ti c Expa ns ion Val ve
Eva pora tor Coil
Trans former
Fl ame Roll out Switch
FUNCTIONAL PARTS