Gas Supply And Manifold Check

Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate.

Gas Inlet Pressure Check

Gas inlet pressure must be checked and adjusted in accordance to the type of fuel being consumed.
With Power And Gas Off:

1. Connect a water manometer or adequate gauge to the inlet pressure tap of the gas valve.

Inlet gas pressure can also be measured by removing the cap from the drip leg and installing a predrilled cap with a hose
fitting.

With Power And Gas On:

2. Put unit into heating cycle and turn on all other gas consuming

appliances.

NOTE:

  Inlet Gas Pressure Must Not Exceed the Maximum Value Shown

in the Inlet Gas Pressure chart.

If operating pressures differ from above, make necessary pressure regulator adjustments, check
piping size, etc., and/or consult with local utility.

Manifold Pressure Check

1 Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.
2. Turn off all electrical power to the system.
3. Back outlet pressure test screw (inlet/outlet pressure boss) out one turn (counterclockwise,

not more than one turn).

4. Attach a hose and manometer to the outlet pressure boss of the valve.
5. Turn ON the gas supply.
6. Turn on power and energize main (M) solenoid. Do not energize the HI solenoid.
7. Measure gas manifold pressure with burners firing.  Adjust manifold pressure using the Manifold

Gas Pressure table.

8. Remove regulator cover screw from the low (LO) outlet pressure regulator adjust tower and

turn screw clockwise to increase pressure, or counterclockwise to decrease pressure.

9. Energize main (M) solenoid as well as the HI terminal.
10. Remove regulator cover screw from the HI outlet pressure regulator adjust tower and turn

screw clockwise to increase pressure, or counterclockwise to decrease pressure.

11. Turn off all electrical power and gas supply to the system.
12. Remove manometer hose from outlet pressure boss.
13. Turn outlet pressure test screw in to seal pressure port (clockwise,

7 in-lb minimum).

14. Turn on electrical power and gas supply to the system.
15. Turn on system power and energize valve.
16. Using a leak detection solution or soap suds, check for leaks at

pressure boss screw.  Bubbles forming indicate a leak. SHUT OFF
GAS AND FIX ALL LEAKS IMMEDIATELY.

NOTE:

 For gas to gas conversion, consult your dealer for appropriate

conversion.

Gas Input (Natural Gas Only) Check

To measure the gas input use a gas meter and proceed as follows:

1. Turn off gas supply to all other appliances except the unit.
2. With the unit operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide

the seconds by 2; if it is a 1 cubic foot dial, use the seconds as is. This gives the seconds per cubic foot of gas being delivered
to the unit.

3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT

Example:

 Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as determined by Step 2, then:

Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. 

NOTE: 

BTU content of the gas should be obtained from the gas supplier. This

measured input must not be greater than shown on the unit rating plate.

4. Relight all other appliances turned off in step 1. Be sure all pilot burners are operating.

Main Burner Flame Check

Flames should be stable, soft and blue (dust may cause orange tips but they must not be yellow) and extending directly
outward from the burner without curling, floating or lifting off.

Gas Line

Gas
Shutoff
Valve

Gas Line 
To Furnace

Drip Leg Cap 
With Fitting

Manometer Hose

Manometer

Open To
Atmosphere

 Measuring Inlet Gas Pressure

Alternate Method

Range

Nominal

Natural

Low Stage

1.6 -  2.2" w.c.

2.0" w.c.

High Stage

3.2 - 3.8" w.c.

3.5" w.c.

Propane

Low Stage

5.7 -  6.3" w.c.

6.0" w.c.

High Stage

9.7 - 10.3" w.c.

10.0" w.c.

Gas

Manifold Gas Pressure

Manifold Gas Pressure

Inlet Gas Pressure

Natural

Min. 5.0" W.C.,  Max. 10.0" W.C.

Propane

Min. 11.0" W.C. , Max. 13.0 " W.C.

INLET GAS PRESSURE

Содержание A/GPD1424 Series

Страница 1: ...website for the applicable Specifications Sheets referred to in this manual This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard National Standard...

Страница 2: ...erty damage and or product damage INDEX TO THE INSTALLER 2 TO THE OWNER 2 SHIPPING INSPECTION 2 SAFETY INSTRUCTIONS 2 ORDERING PARTS 5 CODES AND REGULATIONS 5 EPA REGULATIONS 5 NATIONAL CODES 5 PRE IN...

Страница 3: ...amage personal injury or loss of life AVERTISSEMENT RISQUE D INCENDIE OU D EXPLOSION Si les consignes de s curit ne sont pas suivies la lettre cela peut entra ner la mort de graves blessures ou des do...

Страница 4: ...ou d une bougie 8 Si un probl me de ventilation est observ pendant l un des essais d crits ci dessus des correctifs doivent tre apport s au syst me de ventilation conform ment au National Fuel Gas Co...

Страница 5: ...d then select the submenu for the type of product to be installed such as air conditioners or heat pumps to access a list of product pages that each contain links to that model s specification sheet E...

Страница 6: ...de air intake device economizer manual fresh air intake motorized fresh air intake too close to an exhaust outlet gas vent termination or plumbing vent outlet For specific distances required consult l...

Страница 7: ...unting the package unit Curb insulation cant strips flashing and general roofing material are furnished by the contractor GENERAL INFORMATION This unit is approved for outdoor installation ONLY To ass...

Страница 8: ...tallation de ce g n rateur de chaleur des altitudes sup rieures 2000 pi 610 m doit tre effectu e conform ment aux instructions accompagnant la trousse de conversion pour haute altitude fournie avec ce...

Страница 9: ...d connectors must be coated to protect against external corrosion when in contact with masonry plaster or insulation or are subject to repeated wettings by liquids water not rain water detergents or s...

Страница 10: ...1 PSIG Pressure Drop at 10 PSIG Setting Capacities in 1 000 BTU HR 3 8 1 2 5 8 3 4 7 8 1 2 3 4 30 309 700 1 303 2 205 3 394 1 843 3 854 40 265 599 1 115 1 887 2 904 1 577 3 298 50 235 531 988 1 672 2...

Страница 11: ...30V lead blue and a low speed 208V lead black If equipped connect the induced draft blower low speed 208V lead black in place of the low speed 230V lead blue Place the unused 230V lead on the PARK ter...

Страница 12: ...odels are shipped without horizontal duct covers If needed these kits may be ordered through Goodman s Service Parts department Down Discharge Applications Cut insulation around bottom openings and re...

Страница 13: ...a means of filtering all return air All units may be externally filtered Refer to the unit filter size chart in the appendix for filter size information Filters installed external to the unit should b...

Страница 14: ...tem HEATING CYCLE NATURAL GAS LP 1 The Dual Fuel unit will operate in gas heat mode when the thermostat calls for a W 1 or W 2 signal If outdoor thermostat is installed the unit will operate in gas he...

Страница 15: ...he compressor and outdoor fan will be de energized when the thermostat opens 6 The indoor blower continues to run at low cool speed for approximately 60 seconds after the thermostat is satisfied This...

Страница 16: ...ring the heating cycle it may cause the secondary limit to trip Once the blower compartment temperature drops below the limit reset temperature the limit will automatically reset Pre Operation Checks...

Страница 17: ...o the system 12 Remove manometer hose from outlet pressure boss 13 Turn outlet pressure test screw in to seal pressure port clockwise 7 in lb minimum 14 Turn on electrical power and gas supply to the...

Страница 18: ...is energized by 24VAC Adjust the CFM for the unit by changing the 24VAC leads to the speed terminal block on the motor NOTE Heating airflow must be adjusted to provide the temperature rise shown on ra...

Страница 19: ...more often if necessary because of local conditions and usage Dirty throwaway filters should be discarded and replaced with a new clean filter Dirty permanent filters should be washed with water thoro...

Страница 20: ...TE This will involve removing and reinstalling the heat ex changer door on the unit which is held by two screws If you are uncertain about your ability to do this contact a qualified servicer If a str...

Страница 21: ...21 APPENDIX...

Страница 22: ...SOR GAS VALVE CHECK PRESSURE SWITCH 3 FLASHES 2 FLASHES 4 FLASHES 5 FLASHES FALSE FLAME DETECTED OPEN LIMIT SWITCH WITHOUT INDUCER ON PRESSURE SWITCH OPEN CHECK FOR SHORTS IN FLAME SENSOR WIRING NORMA...

Страница 23: ...lashes Indoor Outdoor Thermostat Open Cooling Only Devices Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Signa...

Страница 24: ...PPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PANEL...

Страница 25: ...T1 LO INDUCER L2 PARK 24VAC COM 5 4 3 2 1 1 2 3 5 6 7 8 9 EM N G L T5 T4 T3 T2 T1 C 1 2 6 4 1 FS LS M C H1 RS VM ALS PS GV IGN H C F LO HEAT 6 3 1 2 4 5 OR BL PU YL OR BR OR P1 PIN 3 P1 PIN 5 P1 PIN 9...

Страница 26: ...LTERNATE CONFIGURATION LINE VOLTAGE OPTIONAL HIGH VOLTAGE HIGH VOLTAGE FIELD WIRING LOW VOLTAGE LOW VOLTAGE BK BLACK WIRE CODE PK PINK OR ORANGE GR GREEN BR BROWN BL BLUE RD RED WH WHITE YL YELLOW PU...

Страница 27: ...er Size 1 20 x 20 x 1 1 20 x 25 x 1 1 25 x 25 x1 2 20 x 20 x 1 Clearance in accordance with local installation codes the requirements of the gas supplier and the manufacturer s installation instructio...

Страница 28: ...28 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 29: ...44 1023 149 1285 242 0 3 922 165 49 1206 289 50 956 151 976 157 1237 250 0 4 886 173 51 1164 302 52 908 158 928 164 1189 257 0 5 835 182 54 1131 314 53 857 166 880 172 1141 265 0 6 781 188 58 1086 319...

Страница 30: ...9 137 49 1260 213 55 1317 230 1317 230 1453 269 0 2 1008 144 52 1212 221 57 1269 237 1269 237 1405 277 0 3 956 151 54 1165 229 59 1221 245 1221 245 1357 284 0 4 908 158 57 1117 236 62 1174 253 1174 25...

Страница 31: ...275 347 59 974 204 1261 338 1612 450 0 5 871 204 65 1224 357 61 910 212 1211 343 1563 458 0 6 811 213 X 1172 364 64 847 220 1168 356 1514 466 0 7 753 210 X 1130 379 X 784 227 1111 373 1466 474 0 8 704...

Страница 32: ...nd leaks Repair if necessary Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges Check all electrical connections and terminals Tighten as needed Verify that...

Страница 33: ...Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Circuit 1 Heatin...

Страница 34: ...34 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 35: ...35 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 36: ...OMERFEEDBACK We are very interested in all product comments Please fill out the feedback form on one of the following links Goodman Brand Products http www goodmanmfg com about contact us Amana Brand...

Отзывы: