In a TT or TN system, a residual current device (RCD)
must be used where the measured triggering residual
current does not exceed 100 mA. Residual current
devices with a measured triggering residual current of 30
mA are preferable. In an IT system, an insulation monit-
oring device needs to be used which switches off the
supply as soon as the insulation resistance is no greater
than 50 Ω per Volt of the rated voltage (refer also to
ABNT NBR IEC 60079-14:2009).
ATTENTION:
Never remove the
adapter/ cable gland!
Illustration 3:
Example heater with KLE connection
CAUTION
NOTICE: Do not remove adapter/ cable connec-
tion to connect up the heater!
This would cause irreversible damage to the heater and
this would mean that the explosion protection can no
longer be warranted.
The illustration may deviate from the heater.
1
2
J
L
N
PE
J
J
J
Junction box
TAE
TS
Heater
Option AM
bn=brown bl=blue ye/gn=yellow/green bk=black gy=grey
bn
bl
ye/gn
bk
gy
Illustration 4:
CP ..THERM with TAE