background image

Indoor unit

terminal strip

Outdoor unit

terminal strip

4C

(NOT INCLUDED)

16 AWG 

2

30K unit: 12 AWG 3C
36K unit: 10 AWG 3C
(NOT INCLUDED)

208/230 VAC

 

LINE

 

IN

1

S

2

1

S

G

L1

L2

G

L1

L2

I

N
D
O
O

U
N

I

ELECTRICAL WIRING - INDOOR UNIT

Electrical safety regulation 
1. Supply voltage should be in the range of 90% to 110% of rated voltage.
2. Check specification label on outdoor unit for the breaker size.
3. Ensure the system is properly grounded.
4. Connections must be as the wiring diagram.
5. All wiring must be in compliance with all local and national electrical codes.
6. Installer to be certified in accordance with local codes.

The cable size and the current of the 
 fuse or switch are determined by the 
 maximum current indicated on the 
 product label  which located on the 
 side panel of the unit. 
Please refer to the product label before 
 selecting the cable, fuse and switch.
  

Install the outdoor unit on a rigid base.
Confirm the discharge air outlet direction is not blocked.
If the outdoor unit  is exposed to strong wind such as a seaside, make sure the fan can operate 
properly by placing the unit lengthwise along the wall or install  a wind shield.
See example of wind protection below.

Be sure there is no obstacle which may block exhaust  air.

Strong 
wind

Strong 
wind

Barrier 

Incorrect

Correct

Seal

Drain joint

Base pan hole
of outdoor unit

(A)

(B)

              The drain joint may vary with different models.
For the drain joint with the seal (Fig.A), first fit the seal onto 
the drain joint, then insert the drain joint into the base pan 
hole of outdoor unit, rotate  90 degrees to securely assemble. 
To install drain joint as shown in Fig.B, insert  the  drain 
 joint into the base pan hole of outdoor unit until it clicks into 
position. 

Connecting the drain joint with an extension drain hose (not supplied).

6

DRAIN JOINT INSTALLATION

OUTDOOR UNIT INSTALLATION

7

Oblique

O

90

Roughness

Burr

REFRIGERANT PIPE CONNECTION

1. Cut the copper tubing with a sharp tubing cutter.
2. Remove flare nuts attached to indoor and 
    outdoor unit and place them on the copper tubing 
    after removing all burrs and flare 
    the copper tubing.
3. Firmly hold copper pipe in a die in the 
    dimension shown in the table below.

.

Align pipes to be connected.
Tighten the flare nut with fingers,
and then tighten it with a spanner and torque 
wrench as shown.
Excessive torque can break nut depending 
on installation conditions.

Outer diam.

(inch)

A(inch)

Max.

Min.

3/8"

0.063"

0.039"

5/8"

0.087"

0.079"

Bar

Copper pipe

Clamp handle

Handle

Bar

"A"

Indoor unit tubing

Flare nut

Pipings

.

Outer

diam.

Tightening

torque(lbs.ft)

Additional tightening

torque(lbs.ft)

φ

5/8"

φ

3/8"

33.2

(459kgf.cm)

34.7

(479kgf.cm)

18.4

(255kgf.cm)

19.2

(265kgf.cm)

AIR PURGING AND TEST OPERATION

8

9

1. Remove the electrical  cover from the outdoor unit by removing the mounting screws.
2. Connect the cables to the terminals as identified with their respective matched numbers 
    on the terminal block of indoor and outdoor units.
3. Secure the cable to the terminal strip with the cord clamp.
4. To prevent the ingress of water, form a loop of the connective cable as illustrated in the installation 
    diagram of indoor and outdoor units.
5. Insulate unused cords (conductors) with PVC-tape. Process them so they do not touch any electrical 
    or metal parts.

Liquid side: 

φ

3/8"

 R410A: (Design length - 16.4 ft) x 0.43 oz./ft.        

Connective pipe length

Less than 16.4 ft.

More than 16.4 ft.

Air purging method

Use vacuum pump

Additional amount of refrigerant to be charged

Open the valve stem until it fully opens to  
the stop. Do not try to open it further.
Securely tighten the valve stem cap with 
a spanner or the like.
Valve stem cap tightening torque. See 
Tightening torque table.

.

.

.

Flare nut

Stopper

Cap

Valve body

Valve stem

Use vacuum pump

DO NOT EXCEED THE SPECIFIED MAXIMUM LINE LENGTH - SEE PRODUCT LABEL. 

The service ports have a 5/16" connection to gauges. 
When relocating the system to another location, using vacuum pump to perform evacuation 
and leak testing..

.

.

.

Air and moisture in the refrigerant system will damage the operation of the system and reduce the life 
of the compressor. Therefore, the indoor unit and tubing between the indoor and outdoor unit must be 
leak tested and evacuated to remove any non-condensables and moisture from the system.
Check that each tube (both liquid and gas side tubes) between the indoor and outdoor units have 
 been properly connected and all wiring for the test run has been completed. 
Pipe length and refrigerant amount:

Outdoor
unit

Indoor
unit

Refrigerant 

Packed valve

Half union

Gas side
Liquid side

A

C

D

B

1. Completely tighten the flare nuts, A, B, C, D, connect 
    the manifold valve charge hose to a charge port of the 
    packed valve on the gas pipe side.
2. Connect the charge hose connection to the vacuum 
    pump.
3. Fully open the handle Lo of the manifold valve.
4. Operate the vacuum pump to evacuate. After starting 
    evacuation, slightly loose the flare nut of the packed 
    valve on the gas pipe side and check that the air is 
    entering. (Operation noise of  the vacuum pump changes 
    and a compound meter indicates 0 instead of minus)
5. After the evacuation is complete, fully close the handle 
    Lo of the manifold valve and stop the operation of the 
    vacuum pump.
    Evacuate for 15 minutes or more and check the 
     indicating gauge is -76cmHg(-14.7 psi).

O

6. Turn the stem of the packed valve B about 45  counter-
    clockwise for 6~7 seconds after the gas exits, then 
    tighten the flare nut again. Make sure the pressure display 
    in the pressure indicator is a little higher than the atmosphere 
    pressure.
7. Remove the charge hose from the Low pressure charge hose.
8. Fully open the packed valve stems B and A.
9. Replace the valve caps of the service ports.

Manifold valve

Compound meter

-76cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Packed valve

Perform test operation after completing refrigerant  leak check at the flare 
nut connections and electrical safety check.
    Check that all tubing and wiring have been properly connected and tight.
    Check that the gas and liquid side service valves are fully open.
1. Connect the power, press the ON/OFF button on the remote 
    controller to turn the unit on.
2. Use the remote to select COOL, HEAT, AUTO and FAN and 
    confirm all the functions operate properly.. 

O

3. When the room ambient temperature is too low (lower than 62 F), 
     the unit cannot be controlled by the remote controller in the cooling 
    mode, manual operation must be used. Manual operation is used only when the remote controller is 
    disable or maintenance is necessary.
    Hold the panel sides and lift the panel up to an angle until it remains open (clicking sound).
    Press the Manual control button to select the AUTO or COOL, the unit will operate under 
     AUTO or COOL mode (see User Manual for details).
4.  Test should last about 30 minutes.

Electrical wor k

Connect the cable to the indoor unit

Flaring

Tightening connection

1. Air purging

2. W hen using the Vacuum Pump

4. Operation Testing

3. Safety and leak test

A: Lo packed valve  B: Hi packed valve 
C and D are ends of indoor unit connection.

CAUTION

1. Soap water method:
     Apply a soap/water solution or a liquid detergent to the indoor line set 
     connections and outdoor service port connections with a soft brush 
     to check for leakage of the connecting points of the tubing. If bubbles 
     are observed, it indicates leakage and must be immediately corrected.
2.  Leak detector
     Use the leak detector to check for leakage.

O
U

T

D
O
O

U
N

I

ELECTRICAL WIRING - OUTDOOR UNIT

CAUTION

5

Indoor unit
check point

D

B

C

A

Outdoor unit
check point

Cover

NOTE:

                  Before performing any electrical work, turn the systems main power off.
1. The inside and outside connecting cable can be connected without removing the front grille.
2. The indoor power cord type is H05VV-F or H05V2V2-F, the outdoor power cord and 
    interconnected cord type is H07RN-F.
3. Lift the indoor unit panel up, remove the electrical box cover by removing the screw.
4. Ensure the color of wires of outdoor unit and the terminal identifications. are the same to the
     indoor unit respectively.
5. Wrap those cables not connected with terminals with insulation tapes, so that they will not touch 
    any electrical components. 
6. Secure the cable with the cord clamp.
    

NOTE:

NOTE: 

Panel

Electrical box
cover

Terminal block of indoor unit

Terminal block of outdoor unit

Cover

Screw

Manual control 

Button

AUTO/COOL

1 2 S

To outdoor unit

To indoor unit

To power supply

 1     2     S    L1   L2

950-0182revC

November 27, 2013

              Exceeding the tightening torque will damage the flare surface. 

NOTE: 

NOTE: 
1. Use a small screwdriver 
for terminals. 
2. Breaker size and wiring 
must be sized per the rating 
plate amperage. If  smaller
than required breaker is used 
there is a possibility of damage 
and safety issues. 
3. Use breaker as specified in 
product label on the unit.

***

 

DO NOT CROSS WIRES BETWEEN TERMINALS. ***

***DO NOT INSTALL A LIQUID LINE SIGHT GLASS OR FILTER DRIER IN THE SYSTEM. ***

..

International Refrigeration Products warrants the accompanying split air conditioner or heat pump system
to be free of defects in material and workmanship for the applications specified in the operation manual 
and installation manual for a period of one (1) year on parts and five (5) years on compressor, valid from the 
date of original retail purchase in the United States or Canada. Labor or shipping is not covered under this 
warranty. 

Warranty card must be completed and sent in to activate the warranty for the accompanying unit. Warranty 
may also be activated via the website www.irproducts.biz

WARRANTY

TECHNICAL SUPPORT

 

If you need technical support please call (215) 750-9876 M-F 8:00 am to 4:30 pm.

 

International Refrigeration Products 

1035 Wheeler Way, Langhorne, PA 19047 

.

Отзывы: