INSTALLATION INSTRUCTIONS

R

410A Horizontal Split System Heat Pumps

NH4H4

These instructions must be read and understood completely before attempting installation.

A07532

Fig. 1

 - 

NH4H4

NOTE

:  Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION

2

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Complete Pre

Installation Checks

2

. . . . . . . . . . . . . . . . . . .

Rig and Mount Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Complete Refrigerant Piping Connections

3

. . . . . . . . . . . . .

Make Electrical Connections

4

. . . . . . . . . . . . . . . . . . . . . . . .

START

UP

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SERVICE

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MAINTENANCE

7

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,

or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury, or property

damage. Consult a qualified installer, service agency, or your

distributor or branch for information or assistance. The qualified

installer or agency must use factory

authorized kits or accessories

when modifying this product. Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.

Have a fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and attached to the unit. Consult local building codes and

the current editions of the National Electrical Code (NEC)

NFPA70.
In Canada, refer to the current editions of the Canadian Electrical

Code CSA C22.1.
Recognize safety information. This is the safety

alert symbol 

.

When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury. Understand

the signal words 

DANGER

WARNING

, and 

CAUTION. 

These

words are used with the safety

alert symbol. 

DANGER 

identifies

the most serious hazards which 

will 

result in severe personal injury

or death. 

WARNING 

signifies hazards which 

could 

result in

personal injury or death. 

CAUTION 

is used to identify unsafe

practices which 

may 

result in minor personal injury or product and

property damage. 

NOTE 

is used to highlight suggestions which

will

 result in enhanced installation, reliability, or operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch. Lock out and

tag switch with a suitable warning label.

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

pollution.
Remove and recycle all components or materials (i.e. oil,

refrigerant, etc.) before unit final disposal.

CAUTION

!

Содержание NH4H4

Страница 1: ...all warnings or cautions included in literatureand attached to the unit Consult local building codes and the current editions of the National Electrical Code NEC NFPA70 In Canada refer to the current...

Страница 2: ...nterchange components between the AccuRater device types Matching of outdoor unit with indoor unit may require field replacement of piston Replace piston if required before connecting refrigerant line...

Страница 3: ...accessories If either refrigerant tubing or indoor coil is exposed to the atmosphere the system must be evacuated following good refrigeration practices Run refrigerant tubes as directly as possible a...

Страница 4: ...ct in the unit control box as shown on the unit label diagram and Fig 5 Unit must be grounded LEGEND NEC National Electrical Code TB Terminal Board TB Connections Field Wiring Factory Wiring A07428 Fi...

Страница 5: ...h opens WARNING PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury or death DO NOT attempt to simulate these system abnormalities high pressures pose a serious safet...

Страница 6: ...ng Mode Solenoid De energized Refrigerant Charging WARNING PERSONAL INJURY AND OR EQUIPMENT DAMAGE HAZARD Failure to follow this warning could result in personal injury and or equipment damage Wear sa...

Страница 7: ...could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range NOTE If line length is beyond 80 ft 24 38 m or greater than 20 ft 6 10 m vertical sep...

Страница 8: ...4X24 A EA 4X30 A EN A D 4X30 A EHD4X30A FEM4P30 A TXV FEM4X30 B FMA4P30 A TXV FMA4X30 A FM C U 4P30 A TXV FM C U 4X30 A FXM4X30 A 3 FS M U 4P30 A TXV EA 4X36 A EN A D W 4X36 A EHD4X36A FEM4P36 A TXV F...

Страница 9: ...43 6 14 11 12 15 9 20 7 25 4 115 47 8 13 14 10 18 8 23 5 Where a dash appears do not attempt to charge system under these conditions or refrigerant slugging may occur Charge must be weight in NOTE Sup...

Страница 10: ...10 428 01 9702 01 Specifications subject to change without notice Copyright 2015 International Comfort Products Lewisburg TN 37091 USA...

Отзывы: