background image

INSTALLATION INSTRUCTIONS

3-phase R-22 Split System Heat Pump

4

506 01 5001 00

UNIT SUPPORT

NOTE:

 Unit must be level 

|

 2 degrees (

a

 inch rise or fall

per foot of run) or compressor may not function properly.

A. GROUND LEVEL INSTALLATION

The unit must be level and supported above grade by
beams, platform, or a pad. Platform or pad can be of open
or solid construction but should be of permanent
materials such as concrete, bricks, blocks, steel, or
pressure-  treated timbers approved for ground contact.
Soil conditions must be considered so that the platform or
pad does not shift or settle and leave the unit partially
supported. Minimum pad dimensions are shown in Figure
2.

If beams or an open platform are used for support, it is
recommended that the soil be treated or area be graveled
to reduce the growth of grasses and weeds.

To minimize vibration or noise transmission, it is
recommended that supports not be in contact with the
building structure. However, slabs on grade constructions
with an extended pad are normally acceptable.

!

CAUTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in proper‐
ty damage.

Top surface of platform must be above estimated
snowfall level to prevent snow blocking coil and to
allow water melt to drain from unit.

B. ROOF TOP INSTALLATION

This type of installation is not recommended on wood
frame structures where low noise levels are required.

Supporting structure or platform for the unit must be level.
If installation is on a flat roof, locate unit minimum 6 inches
above roof level.

Place the unit over one or more load bearing walls. If there
are several units, mount them on platforms that are
self-supporting and span several load bearing walls.
These suggestions are to minimize noise and vibration
transmission through the structure. If the structure is a
home or apartment, avoid locating the unit over
bedrooms or study.

NOTE:

 When unit is to be installed on a bonded

guaranteed roof, a release must be obtained from the
building owner to free the installer from all liabilities.

C. FASTENING UNIT DOWN

If conditions or local codes require the unit be attached in
place, remove the knockouts in the base pan and install
tie down bolts through the holes (refer to Figure 2).

Contact local distributor for hurricane hold-down details
and the P.E. (Professional Engineer) certification, when
required.

!

CAUTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in proper‐
ty damage.

Inadequate unit support may cause excessive
vibration, noise, and/or stress on the refrigerant
lines, leading to refrigerant line failure.

Figure 2

Tie Down Knockouts

Base

Pan

Depth

C

B

A

Base Pan Width

a

” dia. Tie Down Knockouts

In Base Pan (2 places)

VIEW

FROM

TOP

Base Pan

Width x Depth

Tie Down

Knockouts

Minimum

Mounting Pad

Dimensions

A

B

C

@%w

 ~ @^c

(8

$v

@!4

@^ X~ @^2

#!x

 ~ #@v

(8

^b

@$n

#!2 ~ #@2

#%

 ~ #^b

(8

^b

@*v

#%

 ~ #^2

REFRIGERATION SYSTEM

A. COMPONENT MATCHES

Check to see that the proper system components are in
place, especially the indoor coil.

R-22 outdoor units can only be used with R-22 specific
indoor coils. If there is a refrigerant mis-match, consult
the indoor coil manufacturer to determine if a refrigerant
conversion kit is available for the indoor coil.

This outdoor unit is designed for use only with indoor coils
that utilize a hard shut-off TXV refrigerant metering
device. If any other type of metering device is installed on
the indoor coil, consult the indoor coil manufacturer to
determine if a hard  shut-off TXV conversion kit is
available.

Содержание H2H3 Series

Страница 1: ...manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labe...

Страница 2: ...r runoff will not enter the unit Locate unit away from areas where heat lint or exhaust fumes will be discharged onto unit as from dryer vents Locate unit away from recessed or confined areas where re...

Страница 3: ...it System Heat Pump 506 01 5001 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service...

Страница 4: ...orms that are self supporting and span several load bearing walls These suggestions are to minimize noise and vibration transmission through the structure If the structure is a home or apartment avoid...

Страница 5: ...in the field use dehydrated or dry sealed deoxidized copper refrigeration tubing Do not use copper water pipe Do not remove rubber plugs or caps from copper tubing until connections are ready to be ma...

Страница 6: ...ION UNIT OPERATION HAZARD Failure to follow this caution may result in improp er product operation Do not bury more than 36 of line set underground Refrigerant may migrate to cooler buried section dur...

Страница 7: ...g against inside of piston body 3 Find plastic bag taped to unit containing copper adapter tube with brass nut 4 Install adapter tube against retainer and thread brass nut onto liquid service valve Ti...

Страница 8: ...2 4 6 1000 1500 LEAK IN SYSTEM VACUUM TIGHT TOO WET TIGHT DRY SYSTEM 2000 MICRONS 2500 3000 3500 4000 4500 5000 3 7 5 Triple Evacuation Method The triple evacuation method should only be used when sys...

Страница 9: ...nces Use a copper conductor of the correct size from the grounding lug in control box to a grounded connection in the service panel or a properly driven and electrically grounded ground rod Supply Vol...

Страница 10: ...ircuit Connections LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION OUTDOOR THERMOSTAT EMERGENCY HEAT RELAY SUPPLEMENTAL HEAT RELAY SHR EHR C W 2 L G Y E O R C W 2 L G Y E O R ODT...

Страница 11: ...door fan motor lead from OF2 on control board refer to Figure 15 Tape lead to prevent grounding 3 Restart unit in heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in hea...

Страница 12: ...Operate unit a minimum of 10 minutes before checking charge NOTE If outdoor unit has a 2 speed fan motor motor will operate in low speed when outdoor ambient temperature is below 82 F Pull one of the...

Страница 13: ...satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop NOTE If indoor unit is equipped with a time delay relay circuit the blower runs an additional length of...

Страница 14: ...Stage Compressor Signal First Stage Compressor Signal 24 VAC for Thermostat Indicator 24 Volt Power 24 Volt Common 24 Volt Compressor Protection Function DC Compressor Solenoid ALERT LED TRIP LED DC S...

Страница 15: ...estriction 2 If high pressure switch present go to Flash Code 2 information 3 Intermittent thermostat demand signal 4 System or control board defective Yellow ALERT Flash Code 4 Locked Rotor LOCKOUT 1...

Страница 16: ...R and C are reverse wired TRIP LED and ALERT LED flashing together Verify R and C terminals are supplied with 19 28VAC ALERT Flash Code 3 Compressor short cycling displayed incorrectly Verify Y termi...

Отзывы: