background image

484 01 3600 00

5

A

(Inside Opening)

Furnace Outlet

Front Bracket

Rear Bracket

Coil Casing Width

Side Bracket

Side Bracket

NOTE:

 Weld 3 places 

in 4 corners

19 1/2” (495)

(Outside)

3/4” (19)
Flanges
(Where Shown)

B

c

A

B

C

12-3/4 (324)

17-1/2 (445)

2-1/4 (57)

16-1/16 (408)

21 (533)

2-1/4 (57)

19-9/16 (497)

24-1/2 (622)

2-1/4 (57)

17-5/8 (448)

19-3/8 (492)

4 (102)

21-1/4 (540)

23 (584)

4 (102)

23 (584)

24-1/2 (622)

4 (102)

DIMENSIONS Inches (mm)

A09395

Figure 5 

 

Recommended Transition

Connect Refrigerant Piping

Use accessory tubing package or field

supplied tubing of

refrigerant grade. Suction tube must be insulated. Do not

use damaged, dirty, or contaminated tubing because it may

plug refrigerant flow

control device. ALWAYS evacuate the

coil and field

supplied tubing before opening outdoor unit

service valves.

Connect Refrigerant Liquid and Suction

Lines

For matched and mismatched systems, use line sizes

recommended in outdoor unit Installation Instructions.
The coil can be connected to outdoor units using accessory

tubing packages or field

supplied tubing of refrigerant

grade. Always evacuate tubing and reclaim refrigerant when

making connections or flaring tubing. Leak check

connections before insulating entire suction line.

Suction Line

Suction line is designed for field sweat connection. Line is

plugged to keep out moisture and dirt. Remove these plugs

only when ready to make connection.
See Table 1 for coil connection tube size.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in product

damage.
To avoid valve damage to the refrigerant control device

while brazing, valves must be wrapped with a

heat

sinking material such as a wet cloth.

CAUTION

!

1. Remove cabinet access door.
2. Remove rubber plugs from coil stubs using a pulling

and twisting motion. Hold coil stubs steady to avoid

bending or distorting.

3. Wrap TXV and nearby tubing with a heat sinking

material such as a wet cloth.

4. Use 1/2 psig Nitrogen purge in the suction and out the

liquid line.

5. Braze using a Sil

Fos or Phos

copper alloy. Do not

use soft solder.

6. After brazing, allow joints to cool. Slide rubber

grommets over joints. Position tubing at center of

each grommet to ensure an air seal around the tube.

7. Always evacuate lines and reclaim refrigerant when

making connections or flaring refrigerant lines. Leak

check connections before insulating entire suction line.

8. If outdoor equipment will not be installed until a later

date, braze liquid and suction lines closed outside. Add

a Schraeder port test fitting to the suction line outside.

Refrigerant Metering Device

END4X, ENW4X coils have a factory

installed hard shut

off

TXV designed only for use with R

410A refrigerant. Use

only with outdoor units designed for R

410A.

NOTE

:  ALL TXV’S HAVE PRESET SUPERHEAT

SETTINGS AND ARE 

NOT 

FIELD

ADJUSTABLE.

Condensate Drain Line Connection

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property

damage.
When installing over a finished ceiling and/or living area,

install a field

fabricated secondary condensate pan

under the entire unit.

CAUTION

!

The coil is designed to dispose of accumulated water

through built

in condensate drain fittings. It is recommended

that PVC fittings be used on the condensate pan. Do not

over

tighten. Finger tighten plus 1

1/2 turns. Be sure to

install plastic plug in unused condensate drain fitting. Two

3/4 inch female threaded pipe connections are provided in

each coil condensate pan.
A trap is not necessary on the condensate line. Consult

local codes for additional restrictions or precautions. If local

codes require a trap then the following guidelines are

suggested to assure proper drainage. Install a trap in

condensate line of coil as close to the coil as possible. Make

trap at least 3 inches (76 mm) deep and no higher than the

bottom of unit condensate drain opening (See Figure 6).

Содержание END4X

Страница 1: ...ecognize safety information When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOT...

Страница 2: ...hen brazing S Place liquid filter dryer near ID unit to reduce the risk of debris clogging the valve S Make sure TXV bulb is securely fastened and wrapped in the indentation on vapor line tube END4X E...

Страница 3: ...2 622 3 8 7 8 23 1 8 587 No Yes Yes END4X60 C T 24A 5 24 1 2 622 3 8 7 8 23 1 8 587 No Yes Yes END4X61 C T 24A 5 24 1 2 622 3 8 7 8 23 1 8 587 No Yes No ENW4X36 C T 17A 3 17 1 2 445 3 8 3 4 16 3 16 4...

Страница 4: ...il directly on top of gas furnace with overhanging portion entirely on left side as in Figure 4 Alternative C Mark location of gas furnace flange on coil casing Remove coil from top of furnace Using t...

Страница 5: ...ap TXV and nearby tubing with a heat sinking material such as a wet cloth 4 Use 1 2 psig Nitrogen purge in the suction and out the liquid line 5 Braze using a Sil Fos or Phos copper alloy Do not use s...

Страница 6: ...oid drainage problems test the primary drain line by slowly pouring water into the pan Check piping for leaks and proper condensate drainage Using the secondary drain as explained in the previous note...

Страница 7: ...ERANT P Piston X TXV METERING DEVICE 18 18 000 BTUH 1 tons 19 18 000 BTUH 1 tons 24 24 000 BTUH 2 tons 30 30 000 BTUH 2 tons 31 30 000 BTUH 2 tons 36 36 000 BTUH 3 tons 37 36 000 BTUH 3 tons 42 42 000...

Отзывы: