INSTALLATION INSTRUCTIONS

R-410A Split System Air Conditioner

421 01 5101 00

7

Figure 5

Liquid Line Filter-Drier

Installed at Indoor Coil

38-11-84

Filter-Drier
(arrow points towards indoor coil)

F. SERVICE VALVES

Service valves are closed and tube stubs are plugged
from the factory. Outdoor units are shipped with a
refrigerant charge sealed in the unit. Leave the service
valves closed until all other refrigerant system work is
complete or the charge will be lost. Leave the plugs in
place until line set tubing is ready to be inserted.

Service valve bodies are brass and tube stubs are
copper.

G. BRAZING CONNECTIONS

!

WARNING

FIRE HAZARD

Failure to remove refrigerant and oil charge before
brazing could result in personal injury, death, and/
or property damage.

Refrigerant and oil mixture could ignite and burn
as it escapes and contacts brazing torch. Make
sure the refrigerant charge is properly removed
from both the high and low sides of the system be‐
fore brazing any component or lines.

Clean line set tube ends with emery cloth or steel brush.
Remove any grit or debris.

Insert line set tube ends into service valve tube stubs.

Apply heat absorbing paste or heat sink product between
service valve and joint. Wrap service valves with a heat
sinking material such as a wet cloth.

Braze joints using a Sil-Fos or Phos-copper alloy.

!

CAUTION

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product
damage.

Braze with Sil-Fos or Phos-copper alloy on cop‐
per-to-copper joints and wrap a wet cloth around
rear of fitting to prevent damage to TXV.

H. EVACUATING LINE SET AND INDOOR COIL

The unit is shipped with a factory refrigerant charge. The
liquid line and suction line service valves have been
closed after final testing at the factory. Do not disturb
these valves until the line set and indoor coil have been
evacuated and leak checked, or the charge in the unit
may be lost.

NOTE:

 Do not use any portion of the factory charge for

purging or leak testing. The factory charge is for filling the
system only after a complete evacuation and leak check
has been performed.

!

CAUTION

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product
damage.

Never use the outdoor unit compressor as a vacu‐
um pump. Doing so may damage the compressor.

Line set and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. If
deep vacuum equipment is not available, the alternate
triple evacuation method may be used by following the
specified procedure.

If vacuum must be interrupted during the evacuation
procedure, always break vacuum with dry nitrogen.

Содержание C4A3 Series

Страница 1: ...following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Labeling and Signal Words CAUTION WARNING TABLE OF CONTENTS Inspect New Unit 2 Safety Considerations 2 Location 2 Clearances 2 3 Unit Support 4 Refrigeration System 5 8 Elec...

Страница 2: ...kes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit away from areas where heat lint or exhaust fumes will be discharged onto unit as from dryer vents Locate unit away from recessed or confined areas where recirculation of discharge air may occ...

Страница 3: ...stem Air Conditioner 421 01 5101 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service 24 Service 24 Service 4 4 wide fence 18 18 ...

Страница 4: ...f level Place the unit over one or more load bearing walls If there are several units mount them on platforms that are self supporting and span several load bearing walls These suggestions are to minimize noise and vibration transmission through the structure If the structure is a home or apartment avoid locating the unit over bedrooms or study NOTE When unit is to be installed on a bonded guarant...

Страница 5: ...al TXV installation is shown in Figure 3 Figure 3 Typical TXV Installation TXV SENSING BULB EQUALIZER TUBE ÉÉ ÉÉ ÉÉ ÉÉ 8 O CLOCK 4 O CLOCK STRAP SENSING BULB EITHER SIDE SUCTION TUBE INDOOR COIL SUCTION TUBE LIQUID TUBE B REFRIGERANT LINE SETS The refrigerant line set must be properly sized to assure maximum efficiency and proper oil circulation Refer to Product Specifications and Long Line Applic...

Страница 6: ...n improp er product operation Do not leave system open to atmosphere any lon ger than absolutely required for installation Inter nal system components especially refrigerant oils are extremely susceptible to moisture con tamination Keep ends of tubing sealed during installation until the last possible moment Figure 4 Routing and Suspending Refrigerant Lines INSULATION SUCTION TUBE LIQUID TUBE OUTD...

Страница 7: ...ve and joint Wrap service valves with a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy CAUTION PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product damage Braze with Sil Fos or Phos copper alloy on cop per to copper joints and wrap a wet cloth around rear of fitting to prevent damage to TXV H EVACUATING LINE SET AND INDOOR COIL The...

Страница 8: ...oisture 5 Repeat this procedure as indicated in Figure 7 6 After the final evacuate sequence confirm there are no leaks in the system If a leak is found repeat the entire process after repair is made Figure 7 Triple Evacuation Sequence CHECK FOR TIGHT DRY SYSTEM IF IT HOLDS DEEP VACUUM EVACUATE BREAK VACUUM WITH DRY NITROGEN WAIT EVACUATE CHARGE SYSTEM BREAK VACUUM WITH DRY NITROGEN EVACUATE WAIT ...

Страница 9: ...ine Voltage connections with raintight conduit and fittings Most codes require a disconnect switch outdoors within sight of the unit Consult local codes for special requirements Route electrical supply Line Voltage wiring through knockout hole in bottom of Control Box Connect wires to Contactor and Ground Lug according to Wiring Diagram on unit Refer to Figure 8 Route thermostat wiring through rub...

Страница 10: ... THERMOSTAT FURNACE Y G W HEAT STAGE 1 COOL STAGE 1 INDOOR FAN AIR CONDITIONER 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C THERMOSTAT FAN COIL Y G W2 HEAT STAGE 1 COOL STAGE 1 INDOOR FAN AIR CONDITIONER 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C THERMOSTAT FAN COIL Y G W2 HEAT STAGE 1 COOL STAGE 1 INDOOR FAN AC with Red wire connected to power Comfort Alert R C Y ...

Страница 11: ...ure by attaching an accurate thermistor type sensor or electronic thermometer to liquid line near outdoor coil 4 Refer to unit rating plate for required subcooling temperature 5 Refer to Figure 10 Find the required liquid line temperature where the rating plate subcooling temperature intersects measured liquid service valve pressure 6 If the measured liquid line temperature is higher than the char...

Страница 12: ...thout the RED R low voltage lead wire connected The Comfort Alert device operates by monitoring the compressor power leads and the thermostat demand signal Y terminal It draws constant 24 VAC power at the R and C terminals Figure 11 Comfort Alertt Diagnostics some models R Y C 24 VAC Common Thermostat Demand 24 VAC Hot Compressor Wires Pass Through Holes 3 R S C Power LED Alert LED Trip LED MAINTE...

Страница 13: ...forma tion 4 If low pressure switch present go to Flash Code 1 informa tion Yellow ALERT Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor bearings are seized Yellow ALERT Flash Code 5 Open Circuit 1 Outdoor unit power disconnect is open 2 Compressor circuit breaker or fu...

Страница 14: ...C refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere POE oils may cause damage to certain plastics and roofing materials Wrap all filter driers and se...

Отзывы: