DESCRIPTION

The LightMaster PC Series Lighting Control system inde-

pendently controls one or two circuits based on the amount 

of natural light in an area. When the detected light drops 

below the configured foot-candle setting, LightMaster turns 

circuits ON. When natural light rises above the setting, 

LightMaster turns circuits OFF. Each circuit has adjustable 

time delay dials from 0 to 100 seconds to prevent unwant-

ed switching caused by headlights, lightning, and other 

conditions. LightMaster can be used with LS2 high-range 

opaque sensors for typical outdoor dusk-to-dawn applica-

tions or with LS1 clear sensors for indirect light applica-

tions.

Dimensions

MOUNTING THE LightMaster SENSORS:

Follow these guidelines to mount the LS1 or LS2 sen-

sor.

•   If sensor is mounted directly to enclosure of con-

troller, use standard conduit connection means.

•   If sensor is mounted remotely from controller, either 

route sensor wiring separately from class 1 wiring 

or use wiring for sensor rated for the minimum volt-

age of adjacent class 1 wiring.

•   The light level sensor can be mounted indoors or 

outdoors.

•    It must be mounted vertically with the wires facing 

down.

•   The wiring length should not exceed 330 feet and 

should not be run in close proximity to current car-

rying wires.

•   If you are using the sensor for dusk/dawn sensing, 

position the sensor with the arrow facing a wall.

•   If you are using the sensor to control interior light-

ing, awnings, or shades, position the sensor with 

the arrow facing away from the building towards 

the sunlight.

•   Be sure to position the sensor so unwanted light-

ing, such as car headlights, will not influence it.

    

WARNING

Risk of Fire or Electric Shock

•   Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or 

servicing.

•   More than one circuit breaker or disconnect switch may be required to de-energize the 

equipment before servicing.

•  Use #22 - #12 AWG wire - COPPER conductors ONLY. Rated 90°C Min.
•   Installation and/or wiring must be in accordance with national and local electrical code 

requirements.

•   For outdoor locations, raintight, or wet locations, conduit hubs that comply with requirements 

of the UL514B (standard for fitting for conduit and outlet boxes) are to be used.

•   Photoelectric sensor shall be directly mounted to enclosure using standard conduit 

connection means.

•   When photoelectric sensor is mounted in a remote location, wiring shall be routed separately 

from Class 1 wiring.

•   When photoelectric sensor is mounted in a remote location and routed with Class 1 wiring, 

the wiring insulation shall be rated for the minimum voltage of the Class 1 wiring.

•  KEEP DOOR CLOSED AT ALL TIMES when not servicing.

NOTICE

  

The warranty will be void if the wrong voltage is applied. Connect the wires in accordance with 
the wiring diagram.

MOUNTING THE LightMaster MODULE

There are multiple mounting options for the LightMas-

ter module. Follow the applicable guidelines for the 

appropriate mounting method for your facility.
•  

Surface Mount in a control panel or enclosure 

with a standard DIN rail

  

     Place the top two protruding guides located 

on the back of the unit over the top lip of 

the DIN Rail and snap into place.

•  

Mount as a Stand alone unit

    

•    Mount the LightMaster in a TYPE 3R indoor/

outdoor enclosure.

NOTE: Also available: LM2 Series system with included 

TYPE 3R enclosure.