GM40AVE SERIES TERMINAL DESIGNATIONS 

GM40AVE SERIES TYPICAL WIRING DIAGRAMS

COM2

NO 2

NC 2

COM

NO

NC

L 2/N

L 1

T

TIMER

When the GM40AVE is used to control a single phase 120 

VAC load, connect a jumper wire (J1) between L1 and COM. 

 

When the GM40AVE is used to control a single phase 240 

VAC load, connect a jumper wire (J1) between L1 and COM 

and connect a second jumper wire (J2) between L2 and 

COM2.

When the GM40AVE is used to control two single phase 120 

VAC loads, connect a jumper wire (J1) between L1 and COM 

and connect a second jumper wire (J2) between COM and 

COM2. 

NOTICE!

 Make sure that the combined amperage of Load 1 

and Load 2 do not exceed the limits of the feed circuit.

When the GM40AVE is used to control two single phase 277 

VAC loads, connect a jumper wire (J1) between L1 and COM 

and connect a second jumper wire (J2) between COM and 

COM2.

NOTICE!

 

 

Make sure that the combined amperage of Load 1 

and Load 2 does not exceed the limits of the feed circuit.

COM2

NO 2

NC 2

NO

NC

L 2/N

L 1

T

TIMER

L

N

120VAC

COM

LOAD

J1

COM2

NO 2

NC 2

NO

NC

L 2/N

L 1

T

TIMER

L1

L2

240VAC

COM

LOAD 

#1  

J1

J2

NO 2

NC 2

NO

NC

L 2/N

L 1

T

TIMER

L

N

120VAC

COM

LOAD 

#1  

LOAD 

#2 

J1

J2

COM2

NO 2

NC 2

NO

NC

L 2/N

L 1

T

TIMER

L

N

277VAC

COM

LOAD 

#1  

LOAD 

#2 

J2

J1

COM2

120 VAC One Load

240 VAC One Load

120 VAC Two Loads

277 VAC Two Loads

This Time Switch is designed to control one or two single phase loads.  Do Not use to directly control 

three phase loads.  Consult a qualified electrician if you are required to control three phase equipment. 

          3

The circuit conductors shall have an ampacity not 

• 

less than the maximum total load to be controlled.

For all connections, use min. 8 AWG wire for 40 A 

• 

loads or 10 AWG for 30 A loads, min. 90 

o

C (194 

o

F) rating.

Over current protection shall have an interrupting 

• 

rating sufficient for the application control circuit 

voltage and the total load current of the equipment 

being controlled.

A fuse or circuit breaker shall be connected in 

• 

series with each ungrounded conductor (and shall 

be able to simultaneously open each conductor).

Jumper wires are not included.

• 

NOTICE

        WARNING