background image

If a soft start other than the factory setting of 15 seconds is desired
press 

SET UP;

and the date will be displayed. Then press

PULSE: 

SS (for Soft Start) appears in the left two displays with 

3 dashes in the rightmost displays. Enter the soft start desired 
by keying in a number from 1 to 127 seconds, and then press

OK.

This new soft start allows you to lengthen or shorten the 
15-second soft start and will affect all available circuits.

INSTRUCTIONS FOR REVIEWING/REVISING DATA

REVIEW PROCEDURE

• Place the Run/Set switch in the Set position to review.
• You must review Clock info (date, time), Astro and 

Holiday dates in SET-UP mode.  

• You must review all load activity (Fixed times, Astro times, Pulse

operations, Interval operations and special “Holiday” load 
activities) in PROGRAM mode.  

• In PROGRAM, select only one load at a time using the 

ENABLE switch. If more than one circuit is enabled, you will 
only see switch activities common to all Enabled circuits.

REVIEW CLOCK,  CALENDAR,  ASTRO DATA AND
HOLIDAY DATES

To initiate review, press SET-UP (the date is displayed), then press
REV (Review). Continue to press REV for each program you wish to
review. SET-UP stops after the time is displayed if no ASTRO
information has been entered, allowing you to enter Astro data
(Zone, Sunrise and Sunset). If ASTRO information has been entered,
pressing REV after reviewing the Sunset time will cause the message
“End of Review” to be displayed. Review will then automatically
advance to HOLIDAY, allowing you to select a specific holiday
reference # (01–99) for review. If you want to review all holiday
dates, press REV without selecting a reference number, and the first
reference # will appear. (Not necessarily reference #1 since
holidays review in chronological order beginning Jan. 1). Continue
to press REV to walk through the Ref # and the Start and Stop
dates for each holiday until “End of Review” is displayed. For single
day holidays, Start and Stop dates will be the same. Note Astro
sunrise and sunset times are re-calculated daily by the timer and will
differ from times entered or reviewed on a previous date.

10

REVISE SETUP DATA

To revise or delete displayed information during Setup Review,
simply press CLEAR. When reviewing Astro Sunrise and Sunset
times, you may need to press CLEAR more than one time since
each operation deletes only one digit. You can then immediately 
make the revision. Be sure to press OK to enter the new data.
Note that after any revisions to the sunrise Astro time, the sunset
Astro time must be re-entered and okayed. Press REV to continue
the review

.

REVIEW PROGRAM

• Be sure to select one load at a time. Failing to do so will allow 

you to only review switching activities which are common to all 
the circuits selected. In other words, if circuits #1 and circuits #2
are both enabled and are both programmed to come ON at 8:00
A.M., but OFF at different times, the 8:00 A.M. ON time will 
be the only set point shown in Review. You must be in the 
PROGRAM mode in order to review the programmed load 
activities.

• In the PROGRAM mode, you can review switching activities 

regardless of whether you programmed them as Fixed Times, 
Astro Times, Pulse Switching or Interval Switching. Special 
Holiday load activities or interval overrides are also reviewed in 
Program.

REVIEW WEEK LONG SWITCHING ACTIVITIES

The normal load switching schedule is a composite of all
applicable individual day schedules, day group schedules and
copied days.The week long review feature allows this composite
schedule to be easily reviewed; by simply pressing the REV key
repeatedly, without first selecting a day, the timer will step thru all
scheduled switching times chronologically, beginning at 12:00
AM Sunday, or by pressing the REV key once, then pressing the
OK key, the timer will automatically step thru each scheduled
switching time, displaying each time for about 2 seconds. Press the
OK key to pause auto review. Press the OK key again to resume
auto review; or press the rev key to continue review manually. 
The scheduled switching times may only be reviewed, not cleared
during week long review. Follow the steps below for individual
day/day group review if any scheduled events need to be cleared.

11

Содержание ET70815CR

Страница 1: ...Special Instructions 28 30 Typ Wiring Configurations 31 32 Troubleshooting 33 36 Error Messages 36 38 INSTRUCTIONS Pg CHARTS Pg REFERENCE Pg Next Generation Models ET70815CR ET70815CR24 ET71615CR ET71615CR24 Vol 4 Installation Date ______________________ Battery Replacement Recommended _______________________ 8 years after installation Intermatic Plaza Spring Grove Illinois 60081 9698 Printed in U...

Страница 2: ...nto the two categories shown on the front panel SET UP and PROGRAM 3 Next Generation INTRODUCTION This easy to program microprocessor based time switch provides flexible 24 hour 7 day or full year load control Its unique self prompting feature simplifies programming by leading you through with flashing prompts The 2 rows of LEDs on the left side flash and indicators in the digital display light wh...

Страница 3: ... SAT 7 WKDY 8 WKND 9 ALL 0 Next Generation SET UP is performed once during installation to set the internal CLOCK ASTRO sunrise sunset times and HOLIDAY references After entering and okaying the ASTRO Zone the timer will display calculated center of time zone times when prompting for sunrise and sunset entries You may OK these enter actual sunrise sunset times or enter offset times for early or la...

Страница 4: ...me as is normal INTVL To initiate an override interval set the RUN SET switch to RUN set the switch for the desired load to Enable press the INTVL key and hold and press the ON OFF button for the load you wish to override The green load indicator flashes during the interval to show override selection At the end of an override interval the load and green LED will turn off regardless of the load sta...

Страница 5: ...ou cannot copy to or from a day group OK CLEAR COPY HELP 4 The COPY feature copies the programmed schedules of all the circuits of the copy from day to the corresponding circuits of the copy to day regardless of the positions of the circuit Enable switches Individual circuit schedules may not be copied independently HELP provides help messages specific to each step in SET UP and PROGRAM If you mak...

Страница 6: ...culated daily by the timer and will differ from times entered or reviewed on a previous date 10 REVISE SETUP DATA To revise or delete displayed information during Setup Review simply press CLEAR When reviewing Astro Sunrise and Sunset times you may need to press CLEAR more than one time since each operation deletes only one digit You can then immediately make the revision Be sure to press OK to en...

Страница 7: ...ROG then press the day key SUN 1 through SAT 7 or the day group key wkDY 8 wkND 9 or ALL 0 to select the day or day group to review NOTE If you have entered data as a day group and attempt to review any of the days individually the message End of Review will be displayed This is because you must review data just as it was entered in this example as a day group Press REV at which point the colon wi...

Страница 8: ...me zone The building owner wants the lights Off 30 min after sunrise and On 30 min prior to sunset Two Holiday or special schedules July 4th and a 2 week office closing 12 22 97 thru 1 5 98 Press TUE 3 OK selects day 2 3 0 PM OK selects time 1 2 1 9 7 OK selects date 5 OK selects zone 14 The time switch now displays the calculated center of time zone sunrise time of 7 33 AM Since the building owne...

Страница 9: ...slide switches to Enable Load 1 and Disable 2 Press PROG completes programming for Saturday data INTVL 3 0 OK sets user selectable interval duration to 30 minutes Note a day or day group is not selected since Interval override is selected on demand by the building occupants Interval override duration selection is now complete The interval override will not begin until called for by the user via th...

Страница 10: ...M Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM SWITCHING TIMES Day Day CIRCUITS SWITCH ON SWITCH OFF PULSE INTVL ASTRO Group 9 10 11 12 Override AM PM N O T I M E E N T R Y R E Q U I R E D Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM...

Страница 11: ... PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM HOLIDAY REFERENCE Up to 99 holidays or holiday durations can be programmed 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 1...

Страница 12: ... PM Sec AM PM 22 HOLIDAY SWITCHING TIMES HOLIDAY CIRCUITS SWITCH ON SWITCH OFF PULSE INTVL ASTRO Ref 1 2 3 4 Override AM PM N O T I M E E N T R Y R E Q U I R E D Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM P...

Страница 13: ...PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM HOLIDAY SWITCHING TIMES HOLIDAY CIRCUITS SWITCH ON SWITCH OFF PULSE INTVL ASTRO Ref 13 14 15 16 Override AM PM N O T I M E E N T R Y R E Q U I R E D Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM PM Sec AM PM AM P...

Страница 14: ...heck the local newspaper for actual local times 26 After the astro zone is entered the approximate sunrise and sunset times for the center of the time zone will be displayed Depending on your location relative to the center you may want to change offset this time Following are approximate offsets plus or minus for selected cities in 5 minute increments SUNRISE SUNSET Albuquerque 5 5 Atlanta 25 25 ...

Страница 15: ...acts are isolated to enable switching loads of a voltage different than the timer power voltage You may need to connect power to the common COM terminals Add jumpers as required Do not mix solid and stranded wires under the same terminal 29 Next Generation SPECIAL INSTRUCTIONS Enclosure Mounting Follow the instructions included with the 2 mounting brackets They have several holes 3 are slotted for...

Страница 16: ...extend beyond the enclosure wall typically into the conduit NOTE If your application requires more than 4 circuits of remote override order Intermatic accessory 156ET9402A for 8 circuits of override or 156ET9403A for 16 circuits of override Re installing Logic Module Carefully plug the cable connector straight into the connector on the rear of the logic module The shape on both connectors must lin...

Страница 17: ... for automatic switching After a power interruption all loads will be Off and will catch up to the present programmed state as of midnight of the present day Schedules that turn On one day then Off one or more days later need a redundant switch On time at 12 00 AM See Load Controls for details Make sure the SET RUN switch is set to RUN Note that override intervals are not ended by scheduled Off ev...

Страница 18: ...m Solution s Load Switches Using the REV function check program times at Incorrect against the times you entered in the chart Time Review SETUP to see if the timer is following a holiday schedule Holiday dates and sched ules from the prior year do not automatically clear or adjust They must be manually revised or removed annually When using pulse or interval On program ming the load will switch On...

Страница 19: ...icable ERR 0d INTERVAL entry not applicable 36 Problem Solution s Events programmed via Day Group or Copy Day methods will not show when reviewing individual days or vice versa Difficulty in When using pulsed output for switching a Programming latching relay or contactor without self Reviewing On clearing contacts one circuit is dedicated to Off Latching the load Turn On Pulse and another to the P...

Страница 20: ... the selected circuits has a program conflict ERR 1d The day of the week entry does not agree with the previously entered date the date has been cleared and you must re enter both ERR IE Out of memory ERR IF Holidays may not overlap Press REVIEW to identify the conflict NOTE Error messages are subject to change with later software revisions 38 ...

Отзывы: