Federal Communications Commission (FCC) Notice for ET2000 Series Time Switches

Description

This document explains the setup and configuration of the Intermatic ET2805 1-Circuit 
Electronic Astronomic 7-Day Time Switch. The ET2805 time switch automatically switches 
loads according to the entered 

weekly

 schedule. The time switch can support up to 48 

fixed ON and 48 fixed OFF events (96 total) and up to 2 Astro events. Each fixed event can 
be applied to any combination of days.
The time switch features an LCD and panel-mounted control buttons to set, review, and 
monitor the time switch functions, including setting date and time, schedule creation, 
enabling or disabling Daylight Saving Time (DST) and configuring DST switchover dates.
Follow these instructions to complete the installation and programming of the ET2805 time 
switch.

This device complies with part 15 of the FCC rules. Operation of this device is subject to the following two conditions: (1) This device 
may not cause harmful interference, and (2) This device must accept any interference, including interference that may cause 
undesired operation. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to 
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the 
equipment is operated in a commercial environment. This equipment generates, uses and radiates radio frequency energy and, if 
not installed and used in accordance with instructions, may cause harmful interference to radio communications. Operation of this 
equipment in a residential area is likely to cause harmful interference that requires the user to correct at his or her own expense.

MODELS ET2805C, ET2805CR, ET2805CP

Shown in indoor/outdoor 

lockable metal enclosure 

NOTICE

•  Do NOT touch circuit board components, contact can create a static discharge, which can damage these electronic components.

•  Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
•  More than one circuit breaker or disconnect switch may be required to de-energize the equipment before servicing.
•  For plastic enclosures, bonding between conduit connections is not automatic and must be provided as part of the installation.
•  Installation and/or wiring must be in accordance with National and Local Electrical Code requirements.
•  Use #14-#8 AWG wires, rated at least 105°C - COPPER conductors ONLY.
•  If the power disconnect point is out of sight, lock it in the OFF position and tag it to prevent unexpected application power.
•  Make sure there is no wire insulation under the terminal plate on the time switch connector. Firmly tighten terminal screws.
•  For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of the UL514B (standard for fitting conduit and 

outlet boxes) are to be used.

•  Do not remove insulator that is covering terminals.
•  Do NOT exceed maximum current carrying capacity.
•  KEEP DOOR CLOSED AT ALL TIMES when not servicing.

Risk of Fire or Electric Shock

     WARNING

Содержание ET2805C

Страница 1: ...rcial environment This equipment generates uses and radiates radio frequency energy and if not installed and used in accordance with instructions may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference that requires the user to correct at his or her own expense MODELS ET2805C ET2805CR ET2805CP Shown in indoor ...

Страница 2: ... metal enclosures 13 Return the insulator to its original position and replace the screw 14 Close enclosure door 15 Apply power to the time switch Wiring Diagrams 1 2 inch Initial Setup The following sections provide instructions for the initial setup of the time switch Programming Overview The steps to program the time switch include setting the current date time Astro zone Astro events fixed eve...

Страница 3: ...M on Sunday of the user configured starting and ending weeks Select LST for the fifth Sunday of a month 6 Press or to select an ending month and press ENTER NEXT 7 Press or to select an ending week and press ENTER NEXT 8 Press MODE to save the DST rules and move to the next mode selection Setting Astro Zone and Time Zone The astronomic feature of this time switch provides a sunset ON event and a s...

Страница 4: ...to advance to the Offset mode selection if this selection is not already active The SET and SUNUP icons appear at the top of the display The default sunup is displayed 2 Press or to adjust the time for sunup and press ENTER NEXT OFFSET briefly appears on the display and then the offset time in minutes is displayed NOTE Offsets can be set to a maximum of 2 hours 120 minutes before or after a sunup ...

Страница 5: ... screen to set fixed switching times Odd numbered events are for ON switching and even numbered events are for OFF switching These events can be enabled for selected days of the week Follow these steps to set fixed time events if no fixed events need to be set press MODE to move to the next mode selection 1 Press MODE to advance until SET FIXED ON OFF EVENTS and ON icons appear on the display if t...

Страница 6: ...ss ENTER NEXT and the day of the month the 1 will flash 5 Press the or buttons to choose the day that the holiday will start 6 Press ENTER NEXT and the OFF icon is displayed 7 The time display will flash and also show 1H 8 Press the or buttons to choose the month that the holiday will end 9 Press the ENTER NEXT and the day of the month the 1 will flash 10 Press the or buttons to choose the day tha...

Страница 7: ...press and hold ENTER NEXT until MEM CLEAR then DONE briefly appears Writing Time Switch Program Data to a USB Memory Stick The time switch has the capability to copy its programmed data event schedules holidays output configuration DST on off setting DST rule setting and geographical location to a USB memory stick Follow these steps to transfer all programming from the time switch to a USB memory ...

Страница 8: ...ORATED 7777 Winn Road SPRING GROVE ILLINOIS 60081 9698 www intermatic com 158 01684 LIMITED TWO YEAR WARRANTY If within the warranty period specified this product fails due to a defect in material or workmanship Intermatic Incorporated will repair or replace it at its sole option free of charge This warranty is extended to the original household purchaser only and is not transferable This warranty...

Отзывы: