background image

USB error codes

If a problem occurs when attempting to perform a USB read or write operation the time switch will show an error code on the 
display. Following is a description of the different error codes:

OPFILE Er

File could not be created on the USB memory stick (stick may be write protected or corrupted)

wrFILE Er

Program data could not be written to the USB memory stick (stick may be full)

oPFILE ER File could not be opened for reading from the USB memory stick
rdFILE Er

File could not be read from the USB memory stick

MSDH Er

USB device is not a memory type device

FATFS Er

Fat file system error indicating the memory stick contains a data format that is incompatible with the time 
switch

DEVICE Er USB memory stick is defective
shCrct Er

The power supply for USB port on the time switch is not functioning

Specifications

Input Voltage:

 120-277 VAC, 60 Hz

Power Consumption:

 5 W MAX

Switch Configuration:

 SPST x 2. See wiring diagrams in this manual. 

Switch Ratings:

 

Rating

Load Type

Voltage

Frequency

30 A

Resistive

120-240 VAC

60 Hz

20 A

Resistive

28 VDC

30 A

Inductive

120-240 VAC

60 Hz

20 A

Magnetic Ballast

120-277 VAC

60 Hz

10 A

Electronic Ballast

120/277 VAC

60 Hz

5 A

Tungsten

120-277 VAC

60 Hz

1 HP

Motor

120 VAC

60 Hz

2 HP

Motor

240 VAC

60 Hz

Events:

 Time switch can support up to 48 fixed ON and 48 fixed OFF events.

Clock Backup:

 100-hour Supercapacitor

Wire Size:

 AWG #14-#8

Minimum ON or OFF time:

 1 minute

Maximum ON or OFF time: 

Indefinite

Shipping Weight:

 2.5 lb. (1.1 kg)

Enclosures:

 Rainproof Type 3R indoor/outdoor lockable metal enclosure (ET2725CR), Type 1 indoor lockable metal enclosure 

(ET2725C), Rainproof Type 3R indoor/outdoor lockable plastic enclosure (ET2725CP)

Knockouts:

 Combination 1/2-3/4 in. size, 1 on rear and each side, 2 on bottom

Содержание ET2725C

Страница 1: ...t This equipment generates uses and radiates radio frequency energy and if not installed and used in accordance with instructions may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference that requires the user to correct at his or her own expense MODELS ET2725C ET2725CR ET2725CP Shown in indoor outdoor lockable...

Страница 2: ...8 Use appropriately rated fittings for the installation 9 Snap the mechanism back into the enclosure 10 Strip 1 2 inch off the supply and load wires Use AWG 14 8 copper conductors rated at least 105ºC 11 Connect the wires to the proper terminals on the time switch and tighten the screws firmly See wiring diagrams 12 Connect ground wire to grounding terminal at the bottom of metal enclosures 13 Ret...

Страница 3: ... time switch NOTE If necessary hold or to scroll through the digits rapidly 1 Press MODE to scroll through the mode selections until SET and DATE icons appear at the top of the display The month flashes 2 Press or to select the current month and then press ENTER NEXT The day of the month flashes 3 Press or to select the current day of the month and then press ENTER NEXT The year flashes 4 Press or...

Страница 4: ...itially both circuits are included with this event Press ON OFF buttons to remove each circuit not affected by this event If the LOAD icon for the circuit is displayed then this circuit will respond to this event If the desired days for this event are Then MON SUN Press ENTER NEXT to save Go to step 9 MON FRI Press DAY once and then press ENTER NEXT to save Go to step 9 SAT SUN Press DAY twice and...

Страница 5: ... number 1 is also displayed on the right side of the display 13 Press the or buttons to set the time for this holiday event to start 14 Press ENTER NEXT and the OFF icon is displayed 15 The time display shows and event number 2 is also displayed on the right side of the display 16 Press the or buttons to set the time for this holiday event to end 17 Press ENTER NEXT and the SET DATE and ON icons a...

Страница 6: ...Press MODE to advance until wr USb is displayed 2 Press ENTER and insUSb is displayed 3 Insert a USB memory stick into the USB port on the front face of the time switch 4 SCHEdL 01 is displayed Press or to increment decrement the schedule number on the display 01 99 5 When the desired number is displayed press ENTER and this will write the data file to the USB memory stick The file name will be SC...

Страница 7: ...ort on the time switch is not functioning Specifications Input Voltage 120 277 VAC 60 Hz Power Consumption 5 W MAX Switch Configuration SPST x 2 See wiring diagrams in this manual Switch Ratings Rating Load Type Voltage Frequency 30 A Resistive 120 240 VAC 60 Hz 20 A Resistive 28 VDC 30 A Inductive 120 240 VAC 60 Hz 20 A Magnetic Ballast 120 277 VAC 60 Hz 10 A Electronic Ballast 120 277 VAC 60 Hz ...

Страница 8: ... BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES ALL IMPLIED WARRANTIES INCLUDING THE WARRANTY OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY MO...

Отзывы: