Intermatic ET2715C Скачать руководство пользователя страница 7

USB error codes

If a problem occurs when attempting to perform a USB read or write operation the time switch will show an error code on the 
display. Following is a description of the different error codes:

OPFILE Er

File could not be created on the USB memory stick (stick may be write protected or corrupted)

wrFILE Er

Program data could not be written to the USB memory stick (stick may be full)

oPFILE ER File could not be opened for reading from the USB memory stick
rdFILE Er

File could not be read from the USB memory stick

MSDH Er

USB device is not a memory type device

FATFS Er

Fat file system error indicating the memory stick contains a data format that is incompatible with the time 
switch

DEVICE Er USB memory stick is defective
shCrct Er

The power supply for USB port on the time switch is not functioning

Specifications

Input Voltage:

 120-277 VAC, 60 Hz

Power Consumption:

 3 W MAX

Switch Configuration:

 SPDT x 1. See wiring diagrams in this manual. 

Switch Ratings:

 

Rating NO

Rating NC

Load Type

Voltage

Frequency

20 A

10 A

Resistive

120-240 VAC

60 Hz

20 A

10 A

Resistive

28 VDC

20 A

10 A

Inductive

120-240 VAC

60 Hz

20 A

3 A

Magnetic Ballast

120-277 VAC

60 Hz

10 A

-

Electronic Ballast

120/277 VAC

60 Hz

1 HP

1/4 HP

Motor

120 VAC

60 Hz

2 HP

1/2 HP

Motor

240 VAC

60 Hz

Events:

 Time switch can support up to 48 fixed ON and 48 fixed OFF events.

Clock Backup:

 100-hour Supercapacitor

Wire Size:

 AWG #14-#8

Minimum ON or OFF time:

 1 minute

Maximum ON or OFF time: 

Indefinite

Shipping Weight:

 2.5 lb. (1.1 kg)

Enclosures:

 Rainproof Type 3R indoor/outdoor lockable metal enclosure (ET2715CR), Type 1 indoor lockable metal enclosure 

(ET2715C), Rainproof Type 3R indoor/outdoor lockable plastic enclosure (ET2715CP)

Knockouts:

 Combination 1/2-3/4 in. size, 1 on rear and each side, 2 on bottom

Содержание ET2715C

Страница 1: ...quipment generates uses and radiates radio frequency energy and if not installed and used in accordance with instructions may cause harmful interference to radio communications Operation of this equip...

Страница 2: ...nockout first then the 3 4 knockout 6 Place the enclosure in the desired location providing space for the enclosure door to swing open fully 7 Securely mount enclosure using provided mounting holes 8...

Страница 3: ...select the current time NOTE Seconds can be set to 00 by pressing ENTER NEXT 3 Press MODE to save the time and move to the Enable Daylight Saving Time mode selection NOTE If the time switch programmin...

Страница 4: ...his event for the selected day 6 Press DAY to move to the next day of the week repeat step 5 7 When all the days are set press ENTER NEXT to save 8 The Event Number increments and the SET FIXED ON OFF...

Страница 5: ...ayed on the right side of the display 16 Press the or buttons to set the time for this holiday event to end 17 Press ENTER NEXT and the SET DATE and ON icons appear on the display The next holiday num...

Страница 6: ...ENTER and insUSb is displayed 3 Insert a USB memory stick into the USB port on the front face of the time switch 4 SCHEdL 01 is displayed Press or to increment decrement the schedule number on the di...

Страница 7: ...e time switch is not functioning Specifications Input Voltage 120 277 VAC 60 Hz Power Consumption 3 W MAX Switch Configuration SPDT x 1 See wiring diagrams in this manual Switch Ratings Rating NO Rati...

Страница 8: ...BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU...