Intermatic ET2000 Series Скачать руководство пользователя страница 5

Setting Operating Mode

The time switch can be set to one of three operating modes: AUTO (default setting), ENERGY SAVER or MANUAL. Once operating 
mode is selected the time switch setup is complete.
NOTE: If no scheduled events are programmed, only MANUAL mode is available.
In AUTO mode, the time switch follows the user-programmed events and the circuit turns ON and OFF at the programmed time(s).

To place in AUTO mode, press MODE and advance until the 

AUTO

 icon appears on the display.

In AUTO mode, pressing an ON/OFF button temporarily overrides the current state of the circuit. The time switch returns to the
normal schedule at the next programmed event.

In ENERGY SAVER mode the time switch operates similarly to AUTO mode with the following exceptions:

The ON/OFF buttons manually activate the circuit for only a 2-hour period.

When a 2-hour period is active, pressing ON/OFF extends the active period by 2 hours.

Pressing and holding (for 3 seconds) the ON/OFF button will turn OFF the circuit.

For ENERGY SAVER mode, press the MODE button until the 

AUTO

 icon on the display flashes.

In MANUAL mode the time switch does not follow any programmed events and only activates the circuit when the ON/OFF button is
pressed.

For MANUAL mode, press the MODE button until the 

MANUAL

 icon appears on the display.

Deleting (Clearing) an Event

Fixed events can be deleted from the time switch. If you need to delete an event, follow this procedure.
1.

If necessary, press MODE to scroll through the different mode selections until SET FIXED ON/OFF EVENTS

 

 appear on the

display.

2.

Press ENTER/NEXT as necessary to scroll through the scheduled events until you see the event you want to delete.

3. Press + and –

 at the same time 

until the display shows --:-- --. This indicates the event is erased.

4.

If necessary, press ENTER/NEXT to scroll through the other configured events.

5.

Press MODE to save the changes and exit.

Clearing Time Switch Memory

During a “Clear Time Switch Memory” operation, the time switch resets all programmed settings to their factory default value. The 
following occurs:

After a brief period of time the time switch model number appears, followed by the USB Boot Loader version, EE Boot Loader
version, the firmware revision and finally the Reset Reason Code.

MEMCLR is displayed followed by DONE when the operation is completed.

To perform a “Clear Time Switch Memory” operation do the following:
1.

Press and hold ENTER/NEXT.

2.

While pressing and holding ENTER/NEXT, press and release the RESET (round) button. Do not release ENTER/NEXT.

3. Continue to press and hold ENTER/NEXT until 

MEM CLEAR

 then 

DONE

 briefly appears.

Writing Time Switch Program Data to a USB Memory Stick

The time switch has the capability to copy its programmed data (event schedules, holidays, output configuration, DST on/off setting, 
DST rule setting and geographical location) to a USB memory stick. Follow these steps to transfer all programming from the time 
switch to a USB memory stick:
1.

Press MODE to advance until 

wr USb

 is displayed.

2.

Press ENTER and 

insUSb

 is displayed.

3. Insert a USB memory stick into the USB port on the front face of the time switch.
4.

SCHEdL 01

 is displayed. Press + or - to increment/decrement the schedule number on the display (01-99).

5.

When the desired number is displayed, press ENTER and this will write the data file to the USB memory stick. The file name will
be 

SCHEDLxx.TXT

 where xx is the schedule number selected in the previous step.

6. After the file is written 

REMOVE

 is shown on the display.

7.

Remove the USB memory stick and the time switch will advance to the next mode selection. If all procedures are completed,
press MODE repeatedly until back to the operating mode selection (AUTO, ENERGY SAVER, MANUAL).

Содержание ET2000 Series

Страница 1: ...radiates radio frequency energy and if not installed and used in accordance with instructions may cause harmful interference to radio communications Operation of this equipment in a residential area i...

Страница 2: ...1 2 inch knockout first then the 3 4 knockout 6 Place the enclosure in the desired location providing space for the enclosure door to swing open fully 7 Securely mount enclosure using provided mounti...

Страница 3: ...select the current time NOTE Seconds can be set to 00 by pressing ENTER NEXT 3 Press MODE to save the time and move to the Enable Daylight Saving Time mode selection NOTE If the time switch programmin...

Страница 4: ...ll trigger relay operations To program holiday blocks follow these guidelines 1 Press MODE to advance until the SET DATE and ON icons appear on the display if this selection is not already active A ho...

Страница 5: ...event is erased 4 If necessary press ENTER NEXT to scroll through the other configured events 5 Press MODE to save the changes and exit Clearing Time Switch Memory During a Clear Time Switch Memory op...

Страница 6: ...into the time switch DONE is briefly shown on the display followed by REMOVE 8 Remove the USB memory stick and the time switch will advance to the next mode selection If all procedures are completed p...

Страница 7: ...20 277 VAC 60 Hz 1 HP 1 4 HP Motor 120 VAC 60 Hz 2 HP 1 2 HP Motor 240 VAC 60 Hz Events Time switch can support up to 48 fixed ON and 48 fixed OFF events Clock Backup 100 hour Supercapacitor Wire Size...