background image

Electronic 1-Circuit

24-Hour Time Switch

Installation and Setup Instructions

With 100-Hour Backup

Federal Communications Commission (FCC) Notice for ET2000 Series Time Switches

Description

This document explains the setup and configuration of the Intermatic ET2115 1-Circuit 
Electronic 24-Hour Time Switch. The ET2115 time switch automatically switches loads 
according to the entered 

daily

 schedule. The time switch can support up to 48 fixed ON 

and 48 fixed OFF events (96 total). 
The time switch features an LCD and panel-mounted control buttons to set, review, and 
monitor the time switch functions, including setting date and time, schedule creation, 
enabling or disabling Daylight Saving Time (DST) and configuring DST switchover dates.
Follow these instructions to complete the installation and programming of the ET2115 time 
switch.

This device complies with part 15 of the FCC rules. Operation of this device is subject to the following two conditions: (1) This device 
may not cause harmful interference, and (2) This device must accept any interference, including interference that may cause 
undesired operation. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to 
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the 
equipment is operated in a commercial environment. This equipment generates, uses and radiates radio frequency energy and, if 
not installed and used in accordance with instructions, may cause harmful interference to radio communications. Operation of this 
equipment in a residential area is likely to cause harmful interference that requires the user to correct at his or her own expense.

MODELS ET2115C, ET2115CR, ET2115CP

Shown in indoor/outdoor 

lockable metal enclosure 

NOTICE

•  Do NOT touch circuit board components, contact can create a static discharge, which can damage these electronic components.

•  Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
•  More than one circuit breaker or disconnect switch may be required to de-energize the equipment before servicing.
•  For plastic enclosures, bonding between conduit connections is not automatic and must be provided as part of the installation.
•  Installation and/or wiring must be in accordance with National and Local Electrical Code requirements.
•  Use #14-#8 AWG wires, rated at least 105°C - COPPER conductors ONLY.
•  If the power disconnect point is out of sight, lock it in the OFF position and tag it to prevent unexpected application power.
•  Make sure there is no wire insulation under the terminal plate on the time switch connector. Firmly tighten terminal screws.
•  For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of the UL514B (standard for fitting conduit and 

outlet boxes) are to be used.

•  Do not remove insulator that is covering terminals.
•  Do NOT exceed maximum current carrying capacity.
•  KEEP DOOR CLOSED AT ALL TIMES when not servicing.

Risk of Fire or Electric Shock

     WARNING

Содержание ET2000 Series

Страница 1: ...radiates radio frequency energy and if not installed and used in accordance with instructions may cause harmful interference to radio communications Operation of this equipment in a residential area i...

Страница 2: ...1 2 inch knockout first then the 3 4 knockout 6 Place the enclosure in the desired location providing space for the enclosure door to swing open fully 7 Securely mount enclosure using provided mounti...

Страница 3: ...select the current time NOTE Seconds can be set to 00 by pressing ENTER NEXT 3 Press MODE to save the time and move to the Enable Daylight Saving Time mode selection NOTE If the time switch programmin...

Страница 4: ...ll trigger relay operations To program holiday blocks follow these guidelines 1 Press MODE to advance until the SET DATE and ON icons appear on the display if this selection is not already active A ho...

Страница 5: ...event is erased 4 If necessary press ENTER NEXT to scroll through the other configured events 5 Press MODE to save the changes and exit Clearing Time Switch Memory During a Clear Time Switch Memory op...

Страница 6: ...into the time switch DONE is briefly shown on the display followed by REMOVE 8 Remove the USB memory stick and the time switch will advance to the next mode selection If all procedures are completed p...

Страница 7: ...20 277 VAC 60 Hz 1 HP 1 4 HP Motor 120 VAC 60 Hz 2 HP 1 2 HP Motor 240 VAC 60 Hz Events Time switch can support up to 48 fixed ON and 48 fixed OFF events Clock Backup 100 hour Supercapacitor Wire Size...

Отзывы: