background image

®

Electronic 24 Hour Time Switches

With Battery Carryover

OWNER/INSTALLER INSTRUCTION MANUAL

ATTENTION: READ CAREFULLY BEFORE ATTEMPTING TO INSTALL YOUR INTERMATIC
TIME SWITCH. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL
INJURY AND/OR PROPERTY DAMAGE! RETAIN FOR FUTURE REFERENCE.

Description

The Intermatic Electronic 24 Hour Time Switch automatical-
ly switches loads according to a preset daily schedule.
This time switch is designed to directly switch loads up to 
30 amps and to switch resistive or inductive loads up to
the time switch rating. For use as a control timer in 
applications requiring 24 hour load control such as 
lighting, heating, air conditioning systems, pumps, 
etcetera. Up to eight set points or events (4 ON/4 OFF) can 
be preset. this schedule will repeat on a daily basis. The 
program can be overridden by using the MANUAL position.

Specifications

CLOCK VOLTAGE: 120, 208, 240, 277 V.A.C., 60 Hz.
Jumper Selectable
POWER CONSUMPTION: 3.0 Watts Max. (ET102C)

6.0 Watts Max. (ET104C)

CONTACT CONFIGURATION:  SPST model  ET102C
DPST model  ET104C.
SWITCH RATING: (Per Pole for ET104C)

30 Amps Inductive/Resistive, 24/120/240 V.A.C., 60 Hz.

20 Amps Resistive - 28 V.D.C.,

1 H.P. 120 V.A.C., 60 Hz.

2 H.P. 240 V.A.C., 60 Hz.

5 Amps Tungsten, 120/240 V.A.C., 60 Hz.

20 Amps Ballast 277 V.A.C., 60 Hz.

SET POINTS (EVENTS): 8 total (4 ON/4 OFF).
BATTERY POWERED CLOCK OPERATION: 3 Years minimum
(AA industrial grade alkaline supplied with time switch)
MIN. “ON” or “OFF” TIME: 1 minute.
MAX. “ON” or “OFF” TIME: 23 hours 59 minutes.
SHIPPING WEIGHT: 2.5 Lbs. (1.1 Kg)
CASE: Drawn steel; 7-3/4” (19.7 cm) high, 5” (12.7 cm)
wide, 3” (7.6 cm) deep; gray finish w/lockable spring hasp.
KNOCKOUTS: Combination 1/2 - 3/4” (one on back and 
each side, two on bottom).

General Safety Information

WARNING: Disconnect all power before installing or
servicing this time switch or its connected loads.
1. Follow all local electrical and safety codes, National

Electric Code (NEC), as well as Occupational Safety and 
Health Act (OSHA).

2. If the power disconnect point is out of sight, lock it in the “OFF” 

position and tag it to prevent unexpected application of power.

3. This time switch case must be grounded.
4. Do not exceed the maximum current carrying capacity of this

time switch.

5. Always replace the plastic  insulator covering the terminal 

before turning power “ON”.

AM        ON

5:20

ET100 SERIES

INCLUDING MODELS:

ET102C, ET102CM (SPST)

ET104C, ET104CM (DPST)

Содержание ET102C

Страница 1: ...e for ET104C 30 Amps Inductive Resistive 24 120 240 V A C 60 Hz 20 Amps Resistive 28 V D C 1 H P 120 V A C 60 Hz 2 H P 240 V A C 60 Hz 5 Amps Tungsten 120 240 V A C 60 Hz 20 Amps Ballast 277 V A C 60 Hz SET POINTS EVENTS 8 total 4 ON 4 OFF BATTERY POWERED CLOCK OPERATION 3 Years minimum AA industrial grade alkaline supplied with time switch MIN ON or OFF TIME 1 minute MAX ON or OFF TIME 23 hours 5...

Страница 2: ...ing as marked on circuit board See Fig 2 CAUTION DO NOT TOUCH THE CIRCUIT BOARD COMPONENTS SINCE STATIC DISCHARGE COULD DAMAGE THE MICROPROCESSOR 3 Replace the mechanism in the case if it has been removed 4 Lift the left side of the insulator off of the retaining post and pivot it up and away to expose the terminal strip 5 Strip the supply and load wires by removing 1 2 inch of insulation DO NOT U...

Страница 3: ...n achieve a fast roll of the displayed time This is useful when setting the time of day or setting the programmed set points events Up to 4 ON and 4 OFF set points 8 events can be programmed The load can manually be switched ON or OFF at any time only if the selector switch is in the RUN mode by pressing the ON OFF button Pressing the ON OFF button two times in the PROGRAM mode causes the event ti...

Страница 4: ...e unit free of charge This warranty applies only to the original purchaser and is not transferable The warranty does not apply to a damage caused by accident abuse mishandling dropping acts of God or any negligent use b units which have been subject to unauthorized repair opened taken apart or otherwise modified c units not used in accordance with directions d damages exceeding the cost of the pro...

Отзывы: