EM1400 Series Installation Guide

Installation Instructions: Low Voltage

Mount relay panel. Use the drill template in the 
plastic pocket of the panel door.

Cable

able

Cable

able

3/4, 1, & 11/4  in. 
K.O.s (line voltage)

3/4 in. K.O.s 
(low voltage)

18”

12”

6”

3/4, 1, & 11/4  in. 
K.O.s (line voltage)

!

  Routing line voltage cables through the sides of the 

enclosure is not allowed as it will violate NEC re-
quirements separating Class 1 and Class 2 circuits.

Plan where to land the line and load conductors 
before routing cables. Write down your plan on the 
panel schedule in the plastic pocket on the panel 
door.

Power supply should be supplied from a dedicated 
breaker. Land 120v or 277v on appropriate lugs 
and Neutral and Ground as indicated.

1.

2.

3.

!

Do not power-up the panel electronics until the bus 
has been activated (see the Quick Start Guide).

You can check for faults while landing conductors 
on the relays with the following steps:

Land Line and Load conductors on the same termi-
nal lug. Label “line” conductor with the breaker ID.  

Check the line. Switch breakers on and clear any 
faults.  Switch breakers off.

Move  the load conductors to the load terminal lug 
on each relay once tested.

Installation Instructions: Line Voltage

Torque Spec Instructions 

The Torque spec for the relay terminal block is 16in-
lbs.

With a 1” diameter = ½” radius screw driver, this 
means a turning force of 32 lbs. 

32 lbs

1" Diameter
Screw Driver

1/2"

Tighten and Wiggle

Copper is “ductile.” That means that it can compress 
and fl ow. To ensure a good connection in the terminal 
lug, follow this procedure.

4.

5.

6.

Содержание EM1400 SERIES

Страница 1: ...ing Schematic 7 Trouble Shooting 8 The EM1400 series is a programmable relay panel with 8 or 16 relays A master panel can stand alone or can control up to 16 digital devices photocell cards digital sw...

Страница 2: ...iate lugs and Neutral and Ground as indicated 1 2 3 Do not power up the panel electronics until the bus has been activated see the Quick Start Guide You can check for faults while landing conductors o...

Страница 3: ...ve the chassis from the enclosure Avoid rubbing the sides of the chassis against the enclosure Store the chassis in the original shipping case or any safe location until needed 1 2 3 4 1 2 Control of...

Страница 4: ...orth Electronics Backplate Neutral Hot Relay 1 To Load Overview Line Low Voltage Connections The EM1400 digital bus allows up to 16 digital devices not including photo cells or contact closures device...

Страница 5: ...s Contact Closure Inputs 14 programmable contact inputs can control any relay s in any panel s for manual on off or over ride Use shielded cable for distances over 150 feet Connect the drain wire to t...

Страница 6: ...ramming Buttons in Master Panel only Scroll and tab to access control features for the system Assign Button Used to assign an address or change an existing address to the relay control card Zone Butto...

Страница 7: ...ive 2 Zones 9 16 Active 4 6 8 10 Discrete Mode 12 8 Zone Mode 14 16 Zone Mode 16 1 3 5 7 9 11 13 15 Optional Input Address Assign Input 4 1 Photocell Input DualVoltage Input Card Power Supply Card Xfo...

Страница 8: ...ss an override switch is acti vated the relay will turn off 1 1 1 2 2 2 3 3 Online Bus Connector A B 12 Gnd Hand Auto Switch Zone 2 Zone 4 Zone 6 Zone 8 Zone 1 Zone 3 Zone 5 Zone 7 Assigns relays to a...

Отзывы: