T and T Tamper Switch 

These two pins connect to the tamper switch, which opens 

when the housing cover is opened. 

COM (I/O) Common or Ground 

These two pins are connected to ground and serve as the 

ground reference when using pins R, S, X, and D. 

DIP Switch Options 

The factory default (

D

) setting is on for all switches. 

S2-1 (sounder enable) 

 

On.

 Sounder is enabled for all modes (

D

). 

 

Off.

 Sounder is completely disabled. 

S2-2 (LED control) 

 

On.

 LED is enabled (

D

). 

 

Off.

 LED is disabled except during warm-up. 

S2-3 (timer reset mode) 

 

On.

 Relay timer does not reset with motion (

D

). 

 

Off.

 Relay timer resets with motion. 

S2-4, S2-5, S2-6 (relay time) 

These switches determine how long the lock relay stays 

energized when motion is detected (Table 1). 

Table 1: 

Relay Time Settings 

Relay time 

S2-4 

S2-5 

S2-6 

1/2 seconds (D) 

On 

On 

On 

1 second 

On 

On 

Off 

2 seconds 

On 

Off 

On 

4 seconds 

On 

Off 

Off 

8 seconds 

Off 

On 

On 

16 seconds 

Off 

On 

Off 

32 seconds 

Off 

Off 

On 

64 seconds 

Off 

Off 

Off 

 

S2-7 (door monitor mode) 

 

On.

 Monitor the door switch (

D

). 

 

Off.

 Do not monitor the door switch. 

S2-8 (relay mode) 

 

On.

 Fail safe mode (

D

) is enabled. 

 

Off.

 Fail secure mode is enabled. 

Initial Power Up 

After mounting and wiring the sensor, apply AC or DC power 

to the input power terminals (V+ and V-). Allow at least 2 

minutes following power up for the sensor to stabilize before 

conducting any tests. 

To walk test the detection pattern, approach the door from all 

directions and watch the walk test LED for detection. See 

Pattern Adjustment

 if changes are required in the detection 

area. 

Reassemble the sensor and completely walk test again 

following any lens adjustment. 

To select the appropriate relay time, set the DIP switches as 

shown in 

DIP Switch Options

 on page 4. 

LED Indicator 

The LED turns red for the duration of the lock relay time 

when motion is detected and flashes twice per second 

during the 20-second warm-up period. The LED turns yellow 

when the radar detects motion. The LED turns green when 

the passive infrared (PIR) detects motion. 

Internal Sounder 

A continuous tone will sound 15 seconds prior to the end of 

the relay timer period. A beeping tone will sound at the end 

of the external input (

X

) signal if the door is open. 

Pattern Adjustment 

The RCR-REX has both PIR and radar detection patterns 

that may be adjusted independently. 

PIR Detection Pattern 

Figure 10 shows the passive infrared (PIR) detection pattern. 

Figure 10: 

PIR Detection Pattern 

 

 

 

Содержание RCR-REX

Страница 1: ...ee of static electricity before handling sensor circuit boards Touch a grounded bare metal surface before touching circuit boards or wear a grounding strap 2 Remove the screw holding the circuit board PCB cradle axle to the back housing and carefully remove the circuit board with cradle from the housing Figure 2 Figure 2 Remove the circuit board and cradle 3 Route wiring to the sensor mounting loc...

Страница 2: ...magnetic lock door strike as shown in Figure 5 Figure 5 Spike Protection Note Failure to spike protect the sensor may result in shortening the life of the relay contacts RCR REX and a Keycard Reader Figure 6 shows the wiring normally used when a keycard reader is on one side of the door and the RCR REX is on the other side of the door Both swiping a keycard or the detection of motion by the RCR RE...

Страница 3: ...nder modes If the unit is powered up with S ungrounded then the unit assumes that S is unused Whenever S is grounded after power up the unit assumes that S is being used to externally activate the sounder Thereafter when S is ungrounded for at least 100 milliseconds the sounder will unconditionally turn on and stay on until S is grounded This pin must be switched with a dry contact or an open coll...

Страница 4: ...Off Fail secure mode is enabled Initial Power Up After mounting and wiring the sensor apply AC or DC power to the input power terminals V and V Allow at least 2 minutes following power up for the sensor to stabilize before conducting any tests To walk test the detection pattern approach the door from all directions and watch the walk test LED for detection See Pattern Adjustment if changes are req...

Страница 5: ...in parallel to the door switch and alarm circuit the sensor will allow normal egress and will monitor alarms from the door being held or forced open The sensor will monitor the operation of the door switch without affecting the access control system When the sensor detects motion the lock relay contacts open unlocking the door and the monitor relay contacts close preventing an alarm from being sen...

Страница 6: ...e RCR REX cover and locate the PIR lens 3 Slip the mask into the two side brackets that hold the PIR lens in place Figure 15 Be careful not to dislodge the lens 4 Close the cover Figure 15 Mask installation Specification Voltage 12 to 30 VAC or VDC Current 23mA typical 27mA maximum at 12 VDC 15mA typical 17mA maximum at 24 VDC 31mA typical 38mA maximum at 12 VAC 26mA typical 29mA maximum at 24 VAC...

Страница 7: ...to operate the equipment FCC ID CGGAA2 Disclaimer Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of UTC Fire Security Americas Corporation Inc Contact Information www utcfireandsecurity com or www interlogix com For ...

Отзывы: