background image

Interflex Datensysteme GmbH   

1/13 

 

 

1  IF-800 Outdoor / IF-801 

We are pleased that you have decided to use a terminal of 

the IF-80x series for recording access data. 
Scope of delivery: 

  IF-80x terminal (slave) 

  I/O controller board for controlling locking devices 

  Material for fastening 

  8-pin terminal strip 

  Blue wire for grounding the back panel 

  Mortise lock 

  Plastic strips for sealing the mortise lock 

 

  Please check the completeness and condition of the 

shipment upon receipt. 

 

 

 

2  Function of the IF-80x Terminal 

Terminals of the IF-80x series are part of an access control system. They are preferably installed directly 

next to locking devices. They are generally connected to a master terminal, access manager or terminal 

controller via an RS485 data cable. These terminals are designed for controlling the access of persons, who 

identify themselves with RFID credentials, as well as for controlling and monitoring locking devices. 
We recommend: 

  installing a separate, fuse-protected circuit. 

  keeping a minimum distance of 30 cm between the terminal and other systems with RFID readers. 

  keeping a distance of 10 cm between connecting cables and power lines. 

 

3  Danger Due to Electric Current 

 

 

 

Electric shock can cause severe injuries or death.

 

De-energize the device.

 

Please observe the accident prevention regulations and take all precautionary measures 

to ensure the safe installation of the devices. 

  Connection to power supply voltage and initial operation may therefore only be carried out by people 

trained in electrical engineering. 

  The electrical installation, in which the device is to be operated, must comply with national standards. To 

guarantee trouble-free operation, we recommend carrying out the electrical installation according to the 

principles of a TN-S system, which means using separate neutral and grounding conductors. 

  Secure the power cable with a strain relief. 

  The device must be equipped with an external separator to ensure that the device can be de-energized. 

  The device must be equipped with an external fuse protection with a maximum nominal current of 16 A. 

 

95-10330_IF-800  V2016-10-20 Outdoor Terminal 

IF-80x Outdoor Terminal 

 

Содержание IF-80 Series

Страница 1: ...ted circuit keeping a minimum distance of 30 cm between the terminal and other systems with RFID readers keeping a distance of 10 cm between connecting cables and power lines 3 Danger Due to Electric Current Electric shock can cause severe injuries or death De energize the device Please observe the accident prevention regulations and take all precautionary measures to ensure the safe installation ...

Страница 2: ...s in sequence Install all cables Mount the IF 80x terminal Make the electrical connections and switch on the power Adjust the reader Set the hardware address Start initial operation and test 6 1 Laying the Cables 1 Power supply to mounting rail power supply unit 41 10106 4 Ethernet data cable from switch to IF 4070 controller or IF 5735 terminal Cable length maximum 100 m Power is supplied to the ...

Страница 3: ...Since the cable run to the IF 80x terminal is usually very long we recommend connecting the power supply and the relay contact with one cable pair each 6 3 Function of the Cables and Cable Types Function of Cable Max Length Recommended Cable Type 1 230 VAC power supply to 20 VAC 1 5 A power transformer order no 41 10106 NYM 3 x 1 5 mm 2 Low voltage cable J Y ST Y 4x2x 0 6 mm 3 Ethernet patch cable...

Страница 4: ...nd the end of the insulation of the data cable 3 Feed the connection cable through the strain relief 4 Install the strain relief in such a way that the end of the insulation with the drain wire is electrically connected to the back panel of the housing 10 5 Clamp the blue wire under a nut of the strain relief 12 6 Now connect all of the cables coming from the I O controller board to the terminal s...

Страница 5: ...5 cm distance from floor to bottom edge of the terminal 1 Mounting holes 5 Vertical mounting option with DIN appliance case 2 Alternative mounting hole for wall mounted cable inserted from the bottom 6 Mounting holes for US standard 3 Cable gland 7 Hole for adjusting the reader 4 Horizontal mounting option with DIN appliance case 8 Foam rubber ...

Страница 6: ...tom mounting hole 1 Depending on how the appliance case is installed you can additionally secure the back panel of the housing by installing screws in the two horizontal 4 or vertical 5 holes For further steps please refer to Attaching the IF 800 Outdoor IF 801 Terminal 6 This is how the drain wire is wrapped around the insulation 8 The blue wire and the PE wire from the I O controller board are c...

Страница 7: ...eps please refer to Attaching the IF 800 Outdoor IF 801 Terminal 10 The drain wire must have an electrical connection to the back panel of the housing 12 The cable lug of the blue wire is connected to the strain relief 11 Lug for fastening the wall reader with the M2x6 mm screw 13 Lug for mortise lock 6 6 Important Points to Note Regarding the Mounting Please observe the following when mounting th...

Страница 8: ...ice Use only the original screws and do not use any washers Screws placed too high can cause collisions with other components and damage the device Ensure short cable routing Cable loops can damage the device due to mechanical stresses Tighten the screw only slightly or leave it out Tightening the screw too tightly can result in mechanical stresses which can damage the device ...

Страница 9: ...mple Power Supply 7 Address switch on the I O controller board 4 Circuit example RS485 connection The spur line may not be longer than max 100 m Bridges BR1 When an I O controller board is used bridge 1 is always plugged in If an additional I O controller board is used bridge 1 on the second I O control board must be removed BR2 With bridge 2 the switching contacts of the relay are changed from NO...

Страница 10: ...or reaches maximum Setting the LEDs You can use the 2 button DIP switch 4 to set the LEDs according to the color of the display The switch setting is usually factory preset Check the setting of the DIP switches by referring to the table Design 1 white 2 blue Glass white OFF ON Glass black ON ON Other settings are reserved for additional designs 6 9 Setting the Hardware Address Switch 1 2 3 4 Addre...

Страница 11: ...e terminal number Example cfg address 8 has been set Enter the command etp address cx The controller responds with TC ET 8 Then the command 34xxyy is sent directly to the terminal Example Address 1 xx New address A uppercase corresponds to 41 Hex xx New address a lowercase corresponds to 61 Hex The command for setting address 1 is 344161 Correspondingly for address 2 344262 see table Via a warm bo...

Страница 12: ...C 3 1 H 8 etp 8 cx 344565 E 5 1 8 etp 8 cx A 1 etp 1 cx 344868 H 8 1 A 9 etp 9 cx 344262 B 2 2 7 Initial Operation Once you have connected the IF 80x terminal and set the address lock it using the mortise lock and screw it down with the M2x6 countersunk screw included in delivery Define the terminal in your time attendance access control software e g IF 6020 or IF 6040 Check the device using a Mif...

Страница 13: ...perature 25 C to 55 C Humidity Max 95 non condensing Product safety EN 60950 1 Compatibility EMC ETS 300330 1 2 EN 301489 1 3 CE Protection category III Degree of protection IP54 provided that the cables are installed according to instructions Dimensions L x W x D 130 5 x 87 x 24 mm Weight 0 32 kg 9 Disposal Once its service life comes to an end the device must be disposed of properly as electroni...

Отзывы: