Interflex Datensysteme GmbH
1/13
1 IF-800 Outdoor / IF-801
We are pleased that you have decided to use a terminal of
the IF-80x series for recording access data.
Scope of delivery:
IF-80x terminal (slave)
I/O controller board for controlling locking devices
Material for fastening
8-pin terminal strip
Blue wire for grounding the back panel
Mortise lock
Plastic strips for sealing the mortise lock
Please check the completeness and condition of the
shipment upon receipt.
2 Function of the IF-80x Terminal
Terminals of the IF-80x series are part of an access control system. They are preferably installed directly
next to locking devices. They are generally connected to a master terminal, access manager or terminal
controller via an RS485 data cable. These terminals are designed for controlling the access of persons, who
identify themselves with RFID credentials, as well as for controlling and monitoring locking devices.
We recommend:
installing a separate, fuse-protected circuit.
keeping a minimum distance of 30 cm between the terminal and other systems with RFID readers.
keeping a distance of 10 cm between connecting cables and power lines.
3 Danger Due to Electric Current
Electric shock can cause severe injuries or death.
De-energize the device.
Please observe the accident prevention regulations and take all precautionary measures
to ensure the safe installation of the devices.
Connection to power supply voltage and initial operation may therefore only be carried out by people
trained in electrical engineering.
The electrical installation, in which the device is to be operated, must comply with national standards. To
guarantee trouble-free operation, we recommend carrying out the electrical installation according to the
principles of a TN-S system, which means using separate neutral and grounding conductors.
Secure the power cable with a strain relief.
The device must be equipped with an external separator to ensure that the device can be de-energized.
The device must be equipped with an external fuse protection with a maximum nominal current of 16 A.
95-10330_IF-800 V2016-10-20 Outdoor Terminal
IF-80x Outdoor Terminal