Program action:
Program A.1 Mobility scooter
-
If the mobility scooter is not used, not connected to a charger and the battery less than 80% of
the total capacity then an alarm (Alarm #1) will sound after 15 hours. This will remind the user to
charge his vehicle.
-
The alarm will stop and the timer will be reset if:
•
The mobility scooter is driven.
•
The battery of the mobility scooter is charged.
•
The program/reset button is pressed.
Program A.2 Mobility scooter with low voltage alarm
This program works in the same way as the program above (A.1 mobility scooter) but has an extra
feature, an under voltage alarm.
-
If the battery voltage drops below 10,8V the under voltage alarm (Alarm #2) will be activated
-
The alarm is reset if:
•
The battery of the mobility scooter is charged.
•
The program/reset button is pressed shortly.
Program A.3 Under voltage alarm
- As soon as the battery voltage drops below the threshold, configured
at “Program B: under
voltage value”
, the alarm (Alarm #3) will be activated.
-
The alarm will be reset if:
•
The battery voltage rises above the threshold, configured at “Program C: Reset values”.
•
The program/reset button is pressed shortly.
The alarm output of the BA makes it possible to connect a generator or battery charger. It will be
activated when the voltage drops below the under voltage threshold and be deactivated as soon
as the battery is charged. Only if Program D option 3 is chosen, the alarm output will work in
opposite. See Alarm #3 for further explanation.
Operation alarms:
Alarm #1 Mobility scooter
Buzzer: The buzzer keeps on beeping (one second on, one second off, etc.) until the alarm is reset.
Output: The output alarm will be activated until the alarm is reset.
Alarm #2 Mobility scooter with under voltage alarm
Buzzer: The buzzer beeps ten times (one second on, one second off, etc.) and then keeps quiet for
40 seconds. Hereafter this is repeated. The buzzer will be silenced directly if the alarm is
reset.
Output: The output alarm will be activated until the alarm is reset.