background image

4. Refrigerant Piping Installation

4.1  Length  and  Drop  Height  Requirements  for  the  Piping 

Connections to the Indoor and Outdoor Units

The length and drop height requirements for the refrigerant piping are different 
for different indoor and outdoor units. Refer to the installation manual of the 
outdoor unit.

4.2 Piping Material and Size

1.  Piping material: Copper pipes for air handling.
2.  Piping  size:  Choose  and  purchase  copper  pipes  that  correspond  to  the 

length and size calculated for the selected model in the installation manual 
of the outdoor unit and your actual project requirements.

4.3 Piping Layout

1.  Seal the two ends of the piping properly before you connect the indoor and 

outdoor  piping.  Once  unsealed,  connect  the  piping  of  the  indoor  and 
outdoor units as quickly as possible to prevent dust or other debris from 
entering the piping system via the unsealed ends, as this may cause the 
system to malfunction.

2.  If the piping needs to go through walls, drill the opening in the wall, and 

place accessories like casings and covers for the opening properly.

3.  Place the refrigerant connecting piping and the communication wiring for the 

indoor and outdoor units together, and bundle them tightly to make sure air 
does not enter and condensate to form water that may leak from the system.

4.  Insert the bundled piping and wiring from outside the room through the wall 

opening  into  the  room.  Be  careful  when  you  lay  out  the  piping.  Do  not 
damage the piping.

4.4 Piping Installation

  Refer to the installation manual attached with the outdoor unit on installation 

of the refrigerant piping for the outdoor unit.

  All gas and liquid piping must be properly insulated; otherwise, this may cause 

water to leak. Use heat insulation materials that can withstand high tempera-
tures above 120°C to insulate the gas pipes. In addition, the insulation of the 
refrigerant piping should be reinforced (20 mm or thicker) in situations where 
there is high temperature and/or high humidity (when part of refrigerant piping 
part is higher than 30°C or when the humidity exceeds RH80%). Otherwise, 
the surface of the heat insulation material may be exposed.

  Before the works are carried out, verify that the refrigerant is R410A. If the 

wrong refrigerant is used, the unit may malfunction.

  Other than the specified refrigerant, do not let air or other gases enter the 

refrigeration circuit.

  If the refrigerant leaks during installation, make sure you fully ventilate the room.

  Use  two  wrenches  when  you  install  or  dismantle  the  piping,  a  common 

wrench and a torque wrench. See Figure 4.1.

 

 

•  Apply  the  appropriate  tightening  torque  according  to  the  installation 

conditions. Excessive torque will damage the socket cap, and the cap will 
not be tight if you apply insufficient torque, leading to leakages.

4.5 Air Tightness Test

Carry out the air tightness test on the system according to the instructions in the 
installation manual of the outdoor unit.

4.7 Vacuum

Create a vacuum in the system according to the instructions in the installation 
manual of the outdoor unit.

4.8 Refrigerant

Charge  the  system  with  refrigerant  according  to  the  instructions  in  the 
installation manual of the outdoor unit.

 

 

4.6 Heat Insulation Treatment for Gas-Liquid Piping Connections 

for the Indoor Unit

  The heat insulation treatment is carried out on the piping at the gas and liquid 

sides of the indoor unit respectively.

a.  The piping on the gas side must use heat insulation material that can 

withstand temperatures of 120°C and more.

b.  For the piping connections of the indoor unit, use the insulation casing 

for copper pipes (accessory 6) to carry out the insulation treatment, 
and close all gaps.

Unit 

body

Attached insulation 

heat pump belt

On-site 

piping side

Face upwards

Figure 4.5

Figure 4.1

Torque wrench
Pipe socket cap

Pipe fittings

Normal wrench

  Slot the refrigerant piping into the brass nut (accessory 13), and expand the 

pipe socket. Refer to the following table for the size of the pipe socket and 
the appropriate tightening torque.

Figure 4.2

External diameter

 (mm)

Tightening 

torque

Figure 4.3

Apply refrigerant oil

  Before the socket cap is installed on the pipe socket, apply some refrigerant 

oil on the socket (both inside and outside), and then rotate it three or four 
times before you tighten the cap. See Figure 4.3.

Precautions to take when welding the refrigerant pipes

• 

Before you weld the refrigerant pipes, fill the pipes with nitrogen first to 
discharge the air in the pipes. If no nitrogen is filled during welding, a large 
amount of oxide film will form inside the piping which may cause the air 
conditioning system to malfunction.

• 

Welding can be carried out on the refrigerant pipes when the nitrogen gas 
has been replaced or refilled.

• 

When the pipe is filled with nitrogen during welding, the nitrogen must be 
reduced to 0.02 MPa using the pressure release valve. See Figure 4.4.

Figure 4.4

• 

The Air Tightness Test helps to ensure that the air and liquid cut-off 
valves of the outdoor unit are all closed (maintain the factory defaults).

 

 

 

• 

For the vacuum, make sure that the air and liquid cut-off valves of the 
outdoor unit are all closed (maintain the factory status).

 

 

 

Caution

Caution

R0.4~0.8

A

45°±  2

90°± 4

Flared opening

diameter (A)

Flared opening

Φ

6.35

14.2-17.2N·m

8.3-8.7mm

Φ

9.53

32.7-39.9N·m

12-12.4mm

Φ

12.7

49.5-60.3N·m

15.4-15.8mm

Φ

15.9

61.8-75.4N·m

18.6-19mm

Φ

19.1

97.2-118.6N·m

22.9-23.3mm

Caution

Figure 4.4

1 Copper piping
2 Section being brazed
3 Nitrogen connection
4 Hand valve
5 Pressure-reducing valve
6 Nitrogen

9

Содержание , MDV-D18Q4/VN1-E

Страница 1: ...E At MDV D24Q4 VN1 E At MDV D28Q4 VN1 E At MDV D32Q4 VN1 E At MDV D36Q4 VN1 E At MDV D40Q4 VN1 E At MDV D48Q4 VN1 E At Thank you very much for purchasing our air conditioner Before using your air cond...

Страница 2: ......

Страница 3: ...and wires Improper wiring and installation may cause a fire Make sure the power cord communication and controller wiring are straight and level when you are working on the connections and the cover o...

Страница 4: ...ntent the mechanical parts will experience accelerated ageing which will severely compromise the service life of the unit 5 Where there are major voltage fluctuations Operating the unit using a power...

Страница 5: ...iameter 32 mm The inner diameter is based on the diameter of the copper and PVC pipes The thickness of the pipe casing is 10 mm or more Increase the thickness of the casing 20 mm or thicker when the t...

Страница 6: ...ctions for the installation site See Figure 2 3 for the schematic on the direction of airflow If part of the air vent must be blocked you may insert an air baffle at the vent of the unit body to block...

Страница 7: ...or mounting and drill four 12mm X 50 55 mm holes Then embed and set up the expansion hook anchors purchased accessory 4 in these holes See Figure 3 2 During the installation of the hooks purchased acc...

Страница 8: ...leakages Buffers Dimensions of unit 75 fresh air vent Refrigerant piping vent liquid side C Refrigerant piping vent gas side D 32 outer diameter of water discharge pipe Figure 3 10 Figure 3 11 Mounti...

Страница 9: ...ctive casing to wrap the connection terminals and use a reliable fixture to secure and strengthen the safety isolation of the terminals 4 Adjust the four panel hook screws see Figure 3 15 c to keep th...

Страница 10: ...on the installation dimensions of the air ducts Figure 3 22 See Figure 3 23 for the schematic on the air duct installation Figure 3 23 If only one air duct is connected The air volume in the air duct...

Страница 11: ...cessive torque will damage the socket cap and the cap will not be tight if you apply insufficient torque leading to leakages 4 5 Air Tightness Test Carry out the air tightness test on the system accor...

Страница 12: ...plugged to prevent water from leaking 5 Water Discharge Piping Installation 5 1 Water Discharge Piping Installation for Indoor Unit 1 Use PVC pipes for the water discharge pipes outer diameter 37 39 m...

Страница 13: ...supply terminal of the indoor unit Refer to Tables 6 1 and 6 2 for the specifications of the power cord and communication wire A wiring capacity that is too small will cause the electrical wiring to b...

Страница 14: ...Indoor and outdoor units Communication wire Connecting the shielded layer of the shielded wire Connect the shielded end of the shielded wire to the electronic controller box sheet metal here Signallin...

Страница 15: ...tralized control function for the indoor unit has been completed on the outdoor unit the toggle switch on main control panel of the outdoor unit must be set to auto addressing otherwise the indoor uni...

Страница 16: ...t s internal components while the unit is powered on can lead to electric shocks or injuries caused by moving parts such as the unit s fan Ensure that the power supply is disconnected before any servi...

Страница 17: ...ity for information about disposal procedures To avoid damaging the remote controller exercise caution when using it and replacing its batteries Do not place objects on top of it Do not place applianc...

Страница 18: ...n air filters inside indoor units Caution The unit performs stably in the temperature range given in above table If the indoor temperature is outside the unit s normal operating range it may stop runn...

Страница 19: ...ll Clean the filter every two weeks when you use it regularly b If the air conditioner is positioned in a dusty place clean the filter often c Replace the filter if it is too dusty to clean the replac...

Страница 20: ...will start after the intentional delay is complete Heating mode is running when the following panel lights are on operation and the DEF FAN LED indicator Cause the indoor unit activates protective me...

Страница 21: ...air inlet or outlet is blocked A refrigerant leak has occurred Low heating effect Doors or windows are not completely closed Close doors and windows Arrange for a professional technician to check the...

Страница 22: ...button is pressed Check whether the MODE indicated on the display is AUTO Check whether the MODE indicated on the display is DRY A power cut has occurred the power to the premises has been cut off Che...

Страница 23: ...P E E d E r o r r e t i n u r o o d t u O E E alarm l e v e l r e t a W FE Indoor unit has not been assigned an address Communication error with outdoor units T1 temperature sensor error T2 temperatu...

Отзывы: