7.4 Control and protection function of unit

7.4.1 The unit has the following protection functions 
1) Current cut-off protection
2) Power supply phase sequence protection
3) Protection for over-low suction pressure 
4) Protection for compressor overcurrent
5) Protection for compressor overload
6) Anti-freezing protection

7) Protection for over-high discharge pressure
8) Protection for outlet and inlet water temperature 
difference 

7.4.2 The unit also has other control functions: 
1) Manual test function
2) Plug and play system
3) RS-485/RS232 Standard serial communication port.

7.5 Troubleshooting

Table 7-1

Error

Possible reason

Air or other non-condensing gas still 
in the system

Detect and settle measure

Discharge gas from fluorin charging inlet. Re-vacuum the system if 
necessary.

Air or other non-condensing gas still 
in the system

Discharge gas from fluorin charging inlet. Re-vacuum the system if 
necessary.

Fins in the condenser are dirty or 
foreign substance blocking fins.  

Insufficient chilling air volume or 
condenser fan error 

Excessive high air suction pressure 

Excessive refrigerant charging volume 

Over high ambient temperature

See “Excessive high air suction pressure” 

Discharge the excessive refrigerant

Excessive refrigerant charging volume 

Over high temperature in chilling water inlet

Insufficient water flow volume

Incrustant in evaporator 

Insufficient water flow

Incrustant in water side of heat exchanger

Over high temperature in chilling water inlet

Excessive high air suction pressure 

Over low temperature of chilling water

Excessive low air suction pressure 

Excessive refrigerant charging volume 

Insufficient refrigerant charging volume 

Insufficient air flow volume

Air loop short-circuit

Over heat air in the side of air heat exchanger

Refrigerant leakage or insufficient 
refrigerant volume

Over low temperature in chilling water 
inlet and outlet

Discharge the excessive refrigerant

Check and installation state

Test leakage or charge sufficient refrigerant to the system 

Eliminate incrustant 

Eliminate incrustant 

Check water temperature

See “Excessive high air suction pressure” 

Check chilling water temperature

Refrigerant leakage or insufficient 
refrigerant volume

Test leakage or charge sufficient refrigerant to the system 

See “Excessive low air suction pressure”  

Check ambient temperature around it

Discharge the excessive refrigerant

Charge sufficient refrigerant to the system

Check fan rotating direction

Reason about remove air short-circuit

Insufficient frost-removal operation

Error comes out from 4-way valve or thermal resistor. Replace a new one if necessary.

Check temperature difference at water inlet and outlet, and adjust the 
water flow volume 

Check temperature difference at water inlet and outlet, and adjust the
water flow volume 

Check thermal insulation layer of water pipe and the specification of this layer

Check ambient temperature

Over cool air in the side of air heat 
exchanger

Refrigerant leakage or insufficient r
efrigerant volume

Excessive low air suction pressure 

Check ambient temperature

Test leakage or charge sufficient refrigerant to the system 

See “Excessive low air suction pressure” 

Check and repair the condenser fan, recover the normal operation

Clean condenser fins.

Insufficient chilling water flow volume

Gas still in water loop

Error comes from pump or flow-type water volume control. Check and 
repair or replace a new one.  

Discharge air

Thermal resistor error

Over high air expelling pressure

Upon error have been confirmed, please replace a new one.

See “Over high air expelling pressure”

Hi-pressure switch error

Upon error have been confirmed, please replace a new one.

    Over high air 
discharge pressure
(Cooling operation)

    Over low air 
discharge pressure
(Cooling operation)

    Over low air 
suction pressure 
(Cooling operation)

    Over high air 
discharge pressure 
(Heating operation)

    Over low air 
discharge pressure 
(Heating operation)

  Over low air 
 suction pressure 
(Heating operation)

  Compressor stops 
because of freeze-proof
protection (Cooling 
operation)

Compressor stops because 
of Hi-pressure protection

    Over high air 
suction pressure 
(Heating operation)

Over high air 
suction pressure
(Cooling operation)

Network ON

ć

 

A

#

 

 

 

 

 

 

 

 

O&I manual

20

Содержание ICHS-420KC-3

Страница 1: ...www intensity com mx MAN I OICH120 1212 ICHS 420KC 3 35 Toneladas AIR COOLED MODULAR CHILLER Installation owner s MANUAL...

Страница 2: ...MAIN PARTS OF THE UNIT Air outlet Air outlet Air inlet Air inlet Air inlet Air inlet NO NAME Top cover NAME Condenser Compressor Evaporator NO Electric control box Water outlet Water inlet Compressor...

Страница 3: ...compact structure and easy transportation and lifting and in the meanwhile it also saves facilities including cooling tower cooling pump and so on for the user and reduces installation cost The units...

Страница 4: ...nd could result in cutting injuries 1 O I manual Never inspect or service the unit by yourself Ask a qualified service person to perform this work Do not dispose this product as unsorted municipal was...

Страница 5: ...chemicals to become deposited in the unit which could endanger the health of those who are hypersensitive to chemicals Do not place appliances which produce open fire in places exposed to the air flow...

Страница 6: ...people due to transfer of noise and vibration The base of the unit is provided with installation holes which can be used to connect the unit and the foundation firmly 3 1 7 In case of installation on...

Страница 7: ...3 1 and the space between adjacent modular units should not be less than 300mm the installation can also follow the direction B and C as shown in Fig 3 2 the spaces between the unit and the obstacle a...

Страница 8: ...therwise the performance of the unit will decline c The inlet pipe of the evaporator must be provided with a target flow controller to realize flow break protection for the unit Both ends of the targe...

Страница 9: ...zing pump is started up in winter For the water pipeline network including filters and heat exchangers dreg or dirt may seriously damages the heat exchangers and water pipes The installation persons o...

Страница 10: ...ow and three way resistance two way resistance or three way resistance as well as filter resistance H4 the longest terminal resistance 4 7 2 Installation the pump a The pump should be installed at the...

Страница 11: ...imal flow value prior to ex factory They should not be adjusted below the ex factory setting value or they may suffer failure After installing flow switches please press the flow switch lever several...

Страница 12: ...its with 2 modules 8 module units can be connected at mostly No 1 unit No 0 address main unit No n unit n 8 No n 1 unit No 2n 3 address No 2n 1 address Fig 4 8 less than 8 modules 9 O I manual No 1 ad...

Страница 13: ...on the main module The unit can be started up through the wired controller only after all addresses are set and the aforementioned items are determined The wired controller is 500m away from the outdo...

Страница 14: ...st be suppressed with standard resistance capacitance suppressors to avoid electromagnetic interference thus leading to failure of the unit and its controller and even damages to them 5 3 10 All weak...

Страница 15: ...nnection of control wires of pump the control wires of AC contactor of pump must pass the connection terminals p1 and P2 of the main unit as shown in Fig 5 3 Step 12 The connection way of the wire con...

Страница 16: ...E4 Under refrigeration mode and heating mode conduct adjustment according to the magnitude of unit outlet water temperature Adjustment range of constant speed capability ON and OFF Total outlet water...

Страница 17: ...ng and heating capability adjustment pump control auxiliary electric heater control total effluent temperature detection and water flow switch detection COM O 485 communication port fault code E2 high...

Страница 18: ...ng the auxiliary electric heater Attention Under heating mode when the main unit board detects total water outlet temperature to be lower than 45 the switch will be closed and the auxiliary electric h...

Страница 19: ...r flow specified in Table 7 1 6 2 Check item table after installation Checking item Description Yes No Whether installing site is meet for requirements Whether water system is meeting for requirements...

Страница 20: ...electric control schematic diagram or the faults caused by water breaking while the unit is in operation should be the user s responsibility Do not re start the unit within 10 min after the unit is s...

Страница 21: ...e which flashes with 2HZ and then adjust the minute by pressing Page up temperature and Page down temperature If no adjustment is made 8 seconds after entering the time setting state the time setting...

Страница 22: ...manual settings mode Press ADD and ADD keys to select how many unit is launch into running Press OK key to save the settings Unit will run after press ON OFF key 3 minutes later Turn off the unit Whe...

Страница 23: ...the system Eliminate incrustant Eliminate incrustant Check water temperature See Excessive high air suction pressure Check chilling water temperature Refrigerant leakage or insufficient refrigerant vo...

Страница 24: ...voltage protection Reference to mention in above the parts of air suction and discharge pressure error Replace damaged assembly Find out the error type and carry out the corresponding measure to settl...

Страница 25: ...ormal it displays There will be no display under the failure state of main unit communication connection d If it is under the host computer network control Network ON Network ON displays otherwise the...

Страница 26: ...s needed to wait for the up to date data of the modular unit received and selected by wired controller Before receiving the data the wired controller only displays on the data display Up area and the...

Страница 27: ...ressure Connection must be renewed after injection is completed Never inject oxygen acetylene or other flammable or poisonous gas to the refrigeration system at leakage detection and air tight test On...

Страница 28: ...k temperature of chilled water or hot water Inlet Outlet 6 check air temperature of air side heat exchanger Inlet Outlet 7 Check refrigerant suction temperature and superheating temperature Refrigeran...

Страница 29: ...utdoor temperature Compressor Air temperature of air side heat exchanger Temperature of chilled water or hot water Current of cooling water pump or hot water pump Dry bulb Wet bulb Indoor temperature...

Страница 30: ...ic resistance lose kPa Fin coil model Shell tube type heat exchanger Control of wired controller manual auto startup running state display failure alert etc High or low pressure switch freeze proof de...

Страница 31: ...M1 A A Heat1A COMP1A U V W KM2 COMP1B KM3 COMP2A KM4 Heat2B COMP2B Y G U V W U V W U V W Y G Y G Y G KM2 KM1 KM6 KM5 KM4 KM3 A B C A A B C A A B C A A B C Heat1B Heat2A KM5 A FAN1A U V W KM6 FAN1B KM7...

Страница 32: ...VKRX OG EH VKRUWH U WKDQ P Black Yellow Gray Query Fault 1RWHV 7K H ZLULQ J GLDJ UDP RI DX LO LDU KHDWH U DQG SXPS L V MXVW IRU UHIHUHQF H SOHD VH IROOR Z WKH LQ VWUXFWLRQ V RI FRUUH VSRQGLQJ DX LOLD...

Страница 33: ......

Отзывы: