MONOPLEX SLIDE OUT CONTROLLER
SERVICE MANUAL
Страница 1: ...servicing of this box should be done only by a qualified Service Technician Tools required Low current test light DC voltmeter Made in the USA by Intellitec SLIDE OUT ROOM CONTROLLER CURRENT ADJUST SWITCH GROUND MOTOR 1 12 VOLTS MOTOR 2 P N 00 00193 000 P N 00 00193 100 P N 00 00193 300 1485 Jacobs Rd Deland FL 32724 386 738 7307 P N 53 00193 100 Rev E 032119 www intellitec com Intellitec MONOPLEX...
Страница 2: ...hms resistor in the ground lead to sense current When the motor is started the controller ignores the current for approximately two seconds to allow for the start up surge It then begins to sense the current by measuring the voltage drop across the sense resistor When this voltage exceeds the preset value the controller shuts off the motor The value of current can be adjusted by the control on the...
Страница 3: ... 5 volts remove wire from controller and check voltage on the controller If it is now 2 5 volts switch wire is shorted to ground Locate switch wire problem Controller failed replace controller Motor bad Check voltage on motor should be 12 volts with indicator on Controller failed replace controller Current adjustment incorrect Adjust current trip level to higher value Mechanics of mechanism bindin...